SELF-DIAGNOSTICS FEATURE
5 Seconds
Red Flash
Table 1
☼
☼
☼
☼
☼
Problem
¾
Green Flash
¾
Return Air Sensor is disconnected.
☼
- - - -
Return Air Sensor is Shorted.
☼
- - -
☼
Return Air Sensor is out of operational
Range.
☼
- -
☼
-
Indoor Coil Sensor is disconnected.
-
☼
- - -
Indoor Coil Sensor is Shorted.
-
☼
- -
☼
Indoor Coil Sensor is out of operational
Range.
-
☼
-
☼
-
Indoor Coil Sensor temperature reading
does not change.
This could indicate a problem with the
refrigerant charge or another problem with
the refrigeration system.
-
☼
-
☼
☼
Outdoor Coil Sensor is disconnected.
-
-
☼
- -
Outdoor Coil Sensor is Shorted.
-
-
☼
-
☼
(Reserved). -
-
☼
☼
-
Outdoor Coil Sensor temperature reading
does not change.
This could indicate a problem with the
refrigerant charge or another problem with
the refrigeration system.
- -
☼
☼
☼
Outdoor Coil Sensor and Indoor Coil Sensor
temperature readings do not change.
Check the compressor operation or this
could indicate a problem with the refrigerant
charge or another problem with the
refrigeration system.
-
☼
☼
☼
☼
No Fault
-
-
-
-
-
☼
= Flash on - = off See Notes next page and Thermistor resistance values page
21.
Notes.
1-
If faults occur in more than one thermistor (except in the second last row on table 1) only one
fault will be indicated at a time according to the following order 1- Outdoor coil thermistor, 2-
indoor coil thermistor and 3- Return air temp thermistor.
2-
To take the system out of the fault diagnostic operation push the mode button, the reset button
or send a command signal from the remote controller.