5-15
PERFORMANCE DATA
SM TQDCI 1-A.1 GB
5.7 K
12
DCI
5.7.1
Cooling Capacity Factors - Run Mode (Unit A,B,C or D)
230[V] : Indoor Fan at High Speed.
ID COIL ENTERING AIR DB/WB TEMPERATURE [ºC]
OD COIL
ENTERING AIR DB
TEMPERATURE
[ºC]
DATA
22/15
24/17
27/19
29/21
32/23
-10 - 20
(protection range)
TC
80 - 110 % of nominal
SC
80 - 105 % of nominal
PI
25 - 50 % of nominal
25
TC
0.97
1.03
1.09
1.16
1.22
SC
1.01
1.03
1.05
1.07
1.09
PI
0.79
0.80
0.82
0.83
0.85
30
TC
0.92
0.98
1.05
1.11
1.17
SC
0.98
1.00
1.03
1.05
1.07
PI
0.88
0.89
0.91
0.92
0.94
35
TC
0.87
0.94
1.00
1.06
1.13
SC
0.96
0.98
1.00
1.02
1.04
PI
0.97
0.99
1.00
1.02
1.03
40
TC
0.83
0.89
0.95
1.02
1.08
SC
0.93
0.95
0.97
1.00
1.02
PI
1.06
1.08
1.09
1.11
1.12
46
TC
0.77
0.83
0.90
0.96
1.02
SC
0.90
0.92
0.94
0.96
0.99
PI
1.17
1.19
1.20
1.22
1.23
LEGEND
TC – Total Cooling Capacity, kW
PI – Power Input, kW
WB – Wet Bulb Temp., (
o
C)
DB – Dry Bulb Temp., (
o
C)
ID – Indoor
OD – Outdoor
5.7.2 Capacity
Correction
Factors
27/19
22/15
24/17
29/21
32/23
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
1.4
20
25
30
35
40
45
50
Outdoor Temperature [deg C]
C
apa
ci
ty
R
at
io