CONTROL SYSTEM
11-24
SM TELECOM 1-A.0 GB
11.12 Protection
11.12.1
Cooling Mode Protections
a. Indoor
Coil
Defrost
Mode: COOLING,
DRY,
AUTO
Temp:
Selected desired temp.
Fan: Any
Timer: Any
I-FEEL: ON or OFF
Control Function
Protects the indoor coil from ice formation at low ambient temperatures.
ICT [
o
c]
+2
ON
OFF
ON
OFF
t1
t2
t3
COMP
OFAN
+1
+5
+14
0
-1
ON
OFF
IFAN
t1
t1 = 5 min minimum for each COMP starting.
t2 = OFAN cycling (alternate between ON and OFF every 30 sec) for 20 min maximum.
t3 = COMP and OFAN stops for 10 min minimum.
CONTENTS
Содержание GC 12 LT
Страница 13: ...OUTLINE DIMENSIONS 4 3 SM TELECOM 1 A 0 GB 4 5 Outdoor Unit GC 30T LT CONTENTS...
Страница 22: ...WIRING DIAGRAMS 7 2 SM TELECOM 1 A 0 GB 7 3 Outdoor Unit GC 12 LT GC 18 LT 7 4 Outdoor Unit GC 30T LT CONTENTS...
Страница 28: ...CONTROL SYSTEM 11 3 SM TELECOM 1 A 0 GB 11 1 4 Main PCB Controller CONTENTS...
Страница 68: ...EXPLODED VIEWS SPARE PARTS LISTS 13 4 SM TELECOM 1 A 0 GB 13 4 Indoor Unit SX 30 TELECOM CONTENTS...
Страница 70: ...EXPLODED VIEWS SPARE PARTS LISTS 13 6 SM TELECOM 1 A 0 GB 13 6 Outdoor Unit GC 12 LT CONTENTS...
Страница 72: ...EXPLODED VIEWS SPARE PARTS LISTS 13 8 SM TELECOM 1 A 0 GB 13 8 Outdoor Unit GC 18 LT CONTENTS...
Страница 78: ...OPTIONAL ACCESSORIES 14 3 SM TELECOM 1 A 0 GB 14 3 RCW RCW2 Wiring Connections as Shown on Kit CONTENTS...
Страница 87: ...APPENDIX A 15 1 SM TELECOM 1 A 0 GB APPENDIX A INSTALLATION AND OPERATION MANUAL CONTENTS...