![Airwell GC 12 LT Скачать руководство пользователя страница 18](http://html1.mh-extra.com/html/airwell/gc-12-lt/gc-12-lt_service-manual_2880095018.webp)
PERFORMANCE DATA & PRESSURE CURVES
5-5
SM TELECOM 1-A.0 GB
5.7
SX 30 TELECOM / GC 30T LT R410A
5.7.1
Cooling Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR
DB OU COIL (°C)
DATA
ENTERING AIR WB/DB ID COIL ( °C)
15/21
17/24
19/27
21/29
23/32
15
(1)
TC
8.75
9.06
9.27
9.49
9.64
SC
5.53
5.77
5.99
6.14
6.26
PI
1.96
1.97
1.97
1.98
1.99
20
(1)
TC
8.46
8.92
9.20
9.42
9.62
SC
5.42
5.72
5.96
6.13
6.24
PI
2.13
2.14
2.15
2.16
2.16
25
TC
8.01
8.65
9.09
9.37
9.59
SC
5.28
5.61
5.91
6.08
6.20
PI
2.30
2.32
2.34
2.35
2.37
30
TC
7.49
8.15
8.81
9.12
9.39
SC
5.12
5.44
5.78
5.95
6.07
PI
2.49
2.52
2.54
2.56
2.59
35
TC
6.93
7.52
8.30
8.72
9.13
SC
4.87
5.22
5.65
5.81
5.93
PI
2.68
2.73
2.77
2.79
2.81
40
TC
6.31
6.86
7.49
8.19
8.61
SC
4.59
4.94
5.34
5.51
5.63
PI
2.89
2.94
2.99
3.02
3.05
46
TC
5.47
5.98
6.58
7.27
7.83
SC
4.23
4.53
4.87
5.04
5.16
PI
3.16
3.21
3.28
3.33
3.36
LEGEND
TC –
Total Cooling Capacity, kW
SC – Sensible Capacity, kW
PI – Power Input, kW
WB – Wet Bulb Temp., (
o
C)
DB – Dry Bulb Temp., (
o
C)
ID – Indoor
OU –
Outdoor
(1) Marked area is below standard operating limits. For operating in low ambient
conditions, refer to Optional Accessories (Chapter 15).
CONTENTS
Содержание GC 12 LT
Страница 13: ...OUTLINE DIMENSIONS 4 3 SM TELECOM 1 A 0 GB 4 5 Outdoor Unit GC 30T LT CONTENTS...
Страница 22: ...WIRING DIAGRAMS 7 2 SM TELECOM 1 A 0 GB 7 3 Outdoor Unit GC 12 LT GC 18 LT 7 4 Outdoor Unit GC 30T LT CONTENTS...
Страница 28: ...CONTROL SYSTEM 11 3 SM TELECOM 1 A 0 GB 11 1 4 Main PCB Controller CONTENTS...
Страница 68: ...EXPLODED VIEWS SPARE PARTS LISTS 13 4 SM TELECOM 1 A 0 GB 13 4 Indoor Unit SX 30 TELECOM CONTENTS...
Страница 70: ...EXPLODED VIEWS SPARE PARTS LISTS 13 6 SM TELECOM 1 A 0 GB 13 6 Outdoor Unit GC 12 LT CONTENTS...
Страница 72: ...EXPLODED VIEWS SPARE PARTS LISTS 13 8 SM TELECOM 1 A 0 GB 13 8 Outdoor Unit GC 18 LT CONTENTS...
Страница 78: ...OPTIONAL ACCESSORIES 14 3 SM TELECOM 1 A 0 GB 14 3 RCW RCW2 Wiring Connections as Shown on Kit CONTENTS...
Страница 87: ...APPENDIX A 15 1 SM TELECOM 1 A 0 GB APPENDIX A INSTALLATION AND OPERATION MANUAL CONTENTS...