RATING CONDITIONS
3-1
SM TELECOM 1-A.0 GB
3. RATING
CONDITIONS
Standard conditions in accordance with ISO 5151, ISO 13253 (for ducted units)
and EN 14511.
Cooling:
Indoor: 27
o
C DB 19
o
C WB
Outdoor: 35
o
C DB
Heating:
Indoor: 20
o
C DB
Outdoor: 7
o
C DB 6
o
C WB
3.1
Operating Limits R410A
Indoor
Outdoor
Cooling
Upper limit
32
o
C DB 23
o
C WB
46
o
C DB
Lower limit
21
o
C DB 15
o
C WB
21
o
C DB
Heating
Upper limit
27
o
C DB
24
o
C DB 18
o
C WB
Lower limit
20
o
C DB
-9
o
C DB -10
o
C WB
Voltage
1PH
198 – 264 V
3PH
360 – 440 V
CONTENTS
Содержание GC 12 LT
Страница 13: ...OUTLINE DIMENSIONS 4 3 SM TELECOM 1 A 0 GB 4 5 Outdoor Unit GC 30T LT CONTENTS...
Страница 22: ...WIRING DIAGRAMS 7 2 SM TELECOM 1 A 0 GB 7 3 Outdoor Unit GC 12 LT GC 18 LT 7 4 Outdoor Unit GC 30T LT CONTENTS...
Страница 28: ...CONTROL SYSTEM 11 3 SM TELECOM 1 A 0 GB 11 1 4 Main PCB Controller CONTENTS...
Страница 68: ...EXPLODED VIEWS SPARE PARTS LISTS 13 4 SM TELECOM 1 A 0 GB 13 4 Indoor Unit SX 30 TELECOM CONTENTS...
Страница 70: ...EXPLODED VIEWS SPARE PARTS LISTS 13 6 SM TELECOM 1 A 0 GB 13 6 Outdoor Unit GC 12 LT CONTENTS...
Страница 72: ...EXPLODED VIEWS SPARE PARTS LISTS 13 8 SM TELECOM 1 A 0 GB 13 8 Outdoor Unit GC 18 LT CONTENTS...
Страница 78: ...OPTIONAL ACCESSORIES 14 3 SM TELECOM 1 A 0 GB 14 3 RCW RCW2 Wiring Connections as Shown on Kit CONTENTS...
Страница 87: ...APPENDIX A 15 1 SM TELECOM 1 A 0 GB APPENDIX A INSTALLATION AND OPERATION MANUAL CONTENTS...