INSTALLATION DETAILS
JMF Series 23 Version - 1
7.4 Installation for the first time
Air and moisture in the refrigerant system have undesirable effects as below:
●
Pressure in the system rises.
●
Operating current rises.
●
Cooling or heating efficiency drops.
●
Moisture in the refrigerant circuit may freeze and block capillary tubing.
●
Water may lead to corrosion of parts in the refrigerant system.
Therefore, the indoor units and the pipes between indoor and outdoor units must be leak tested
and evacuated to remove gas and moisture from the system.
Gas leak check (Soap water method):
Apply soap water or a liquid neutral detergent on the indoor unit connections or outdoor unit
connections by a soft brush to check for leakage of the connecting points of the piping. If bubbles
come out, the pipes have leakage.
1. Air purging with vacuum pump
1) Completely tighten the flare nuts of the indoor and outdoor units, confirm that both the
2-way and
3-way valves are set to the closed position.
2) Connect the charge hose with the push pin of handle lo to the 3-way valves gas service port..
3) Connect the charge hose of handle hi connection to the vacuum pump.
4) Fully open the handle Lo of the manifold valve.
5) Operate the vacuum pump to evacuate.
6) Make evacuation for 30 minutes and check whether the compound meter indicates -0.1Mpa. If
(Indoor unit)
(Liquid side)
(Gas side)
Vacuum
pump
Vacuum
pump
Lo
Hi
Handle Hi
Two-way valve
Close
Manifold valve
Compound meter
Pressure
gauge
-
0.1Mp
a
Handle Lo
Charge hose
Charge hose
(Outdoor unit)
Close
Three-way valve
Содержание Electra ELAU-VMF007-H11
Страница 17: ...WIRING DIAGRAM JMF Series 17 Version 1 ELSI JMF024 N11...
Страница 18: ...WIRING DIAGRAM JMF Series 18 Version 1 6 2 Outdoor Unit ELAU JMF007 H11 ELAU JMF009 H11 ELAU JMF012 H11...
Страница 19: ...WIRING DIAGRAM JMF Series 19 Version 1 ELAU JMF018 H11...
Страница 20: ...WIRING DIAGRAM JMF Series 20 Version 1 ELAU JMF024 H11...
Страница 72: ...JMF Series 72 Version 1 SERVICE MANUAL JMF Series...