TROUBLESHOOTING
Window WDF 26 Version - 0
Water drips from the unit.
Check whether the ambient humidity is too high.
Check whether the indoor outlet airflow foam is too wet, and louver drip.
Check whether the unit is correctly installed.
Check whether the air outlet foam install normally.
No
No
No
No
Check whether the foam of evaporator base is damaged.
No
Check whether the drain passage of evaporator is blocked. Replace if failed.