PROTECTION FUNCTION
Window WDF 14 Version - 0
Δ
T=T1-Ts Running
mode
Δ
T
>
2
℃
Cooling
-1
≤Δ
T
≤
2
℃
Fan-only
The machine will choose actual running mode in auto mode in the below cases:
¾
Power on or change mode to auto mode or adjust temperature in auto mode, the machine will
choose actual running mode again.
¾
A: In auto mode, if the compressor keeps not running for 15 minutes. judge condition B
B: If 1<
Δ
T or
Δ
T <-4
℃
, the machine will choose actual running mode again according to T1-Ts till
the compressor stops..
7.2.4.3 Fan mode
(1) Compressor stops.
(2) Temperature setting function is disabled.
(3) The speed of indoor fan can be optionally chosen as High/ Mid /Low.
7.3 Temperature sensor is open circuit or short circuit.
Defect code
malfunction explanation
Er
Room temperature sensor error.
En
Evaporator temperature sensor error.
Eo
Condenser temperature sensor error.
Ed
Evaporator de-frosting defect.
Malfunction display:
When the malfunction happened at the same time, the priority is: Er> En> E0>Ed
Содержание AWWR-WDF009-C11
Страница 1: ...PRECAUTION Window WDF Series Models AWWR WDF009 C11 AWWR WDF012 C11...
Страница 9: ...DIMENSION Window WDF 7 Version 0 3 Dimension...
Страница 13: ...WIRING DIAGRAM Window WDF 11 Version 0 6 Wiring Diagram...
Страница 20: ...INSTALLATIOIN Window WDF 18 Version 0...
Страница 30: ...EXPLODED VIEW AND PART LIST Window WDF 28 Version 0 12 Exploded view and part list AWWR WDF009 C11...
Страница 32: ...EXPLODED VIEW AND PART LIST Window WDF 30 Version 0 AWWR WDF012 C11...
Страница 34: ......
Страница 35: ...Window WDF 1 Version 0 SERVICE MANUAL Window WDF Series...