ELECTRONIC FUNCTION
HMF Series 39 Version - 1
Defrosting action
:
For other models:
Condition of defrosting:
1,AC will enter defrosting mode if all of the following items is satisfied.
1.1 After the compressor keeps running 8 minutes,
Δ
T
max-
Δ
T
min
≥
4
℃(Δ
T=T2-T1
)
1.2 AC meets A1 or A2.
A1: The cumulative compressor running time is between 45~120 minutes. Meanwhile the value of
T2-T1 meets the below table.
℃
Δ
T
High speed
<
TH
DEFROST
Medium speed
<
TM
DEFROST
Low speed
<
TL
DEFROST
Breeze/off
No need to compare the T2 and T1
A2: The cumulative compressor running time is over 120 minutes. Meanwhile the value of
Δ
T
meets the below table.
℃
Δ
T
High speed
<
TH
DEFROST
+2
Medium speed
<
TM
DEFROST
+2
Low speed
<
TL
DEFROST
+2
1.3
℃
T2
High speed
<
43
℃
Medium speed
<
46
℃
Low speed
<
48
℃
About the setting defrosting time:
runtime
(
minute
)
Defrosting time
(
minute
)