INSTALLATION DETAILS
HMF Series 28 Version - 1
Procedure:
1). Confirm that both the 2-way and 3-way valves are set to the closed position.
2). Connect the charge set and a charging cylinder to the service port of the 3-way valve
Leave the valve on the charging cylinder closed.
3). Air purging.
Open the valves on the charging cylinder and the charge set. Purge the air by loosening the flare nut on
the 2-
way valve approximately 45’ for 3 seconds then closing it for 1 minute; repeat 3 times.
After purging the air, use a torque wrench to tighten the flare nut on the 2-way valve.
4). Check the gas leakage
Check the flare connections for gas leakage.
5). Discharge the refrigerant.
Close the valve on the charging cylinder and discharge the refrigerant by loosening the flare nut on the
2-way valve approxim
ately 45’ until the gauge indicates 0.3 to 0.5 Mpa.
6). Disconnect the charge set and the charging cylinder, and set the 2-way and 3-way valves to the open
position
Be sure to use a hexagonal wrench to operate the valve stems.
7). Mount the valve stems nuts and the service port cap
Be sure to use a torque wrench to tighten the service port cap to a torque 18N.m.
Be sure to check the gas leakage.
7.7 Re-installation while the outdoor unit need to be repaired
1. Evacuation for
the whole system
Содержание AWAU-YMF007-H11
Страница 17: ...WIRING DIAGRAM HMF Series 17 Version 1 AWSI HMF024 N11...
Страница 18: ...WIRING DIAGRAM HMF Series 18 Version 1 6 2 Outdoor Unit AWAU YMF007 H11 AWAU YMF009 H11 AWAU YMF012 H11...
Страница 19: ...WIRING DIAGRAM HMF Series 19 Version 1 AWAU YMF018 H11...
Страница 20: ...WIRING DIAGRAM HMF Series 20 Version 1 AWAU YMF024 H11...
Страница 72: ...HMF Series 72 Version 1 SERVICE MANUAL HMF Series...