Troubleshooting
Electrical Control System
233
2.4.1.5. Indoor fan speed has been out of control.
Shut off the power supply
and turn it on 5 seconds
later. Is it still displaying
the error code?
Shut off the power supply,
rotate the fan by hand.
Does it rotate properly?
The unit operates normally.
Find out the cause and
have it solved. For
example, check
whether the fan is
blocked or the bearing
is broken?
Check the wires of fan
motor. Are all the
connections good?
No
Yes
No
Correct the connections.
No
Yes
Check whether the main PCB is
normal through index 2?
Yes
Yes
Check whether the fan
motor is normal through
index 1?
Yes
Replace the fan
motor
Replace the
main PCB.
The
malfunction is
solved?
No
No
If the
malfunction is
still existing,
replace the
main PCB
No
Содержание AWAU-YLD012-H11
Страница 14: ...Dimensions Console Type 135 2 Dimensions AWSI XAD012 N11 AWSI XAD018 N11 ...
Страница 15: ...Service Space 136 Console Type 3 Service Space ...
Страница 16: ...Wiring Diagrams Console Type 137 4 Wiring Diagrams AWSI XAD012 N11 AWSI XAD018 N11 ...
Страница 21: ...Field Wiring 142 Console Type 10 Field Wiring AWSI XAD012 N11 AWSI XAD018 N11 ...
Страница 24: ...Exploded View and Spare Part list Console Type 145 Exploded View of indoor unit AWSI XAD018 N11 ...
Страница 31: ...Wiring Diagrams 152 Outdoor Units 4 Wiring Diagrams AWAU YLD012 H11 ...
Страница 32: ...Wiring Diagrams Outdoor Units 153 AWAU YLD018 H11 AWAU YLD024 H11 AWAU YLD030 H11 AWAU YLD036 H11 ...
Страница 33: ...Wiring Diagrams 154 Outdoor Units AWAU YLD036 H13 AWAU YLD048 H13 ...
Страница 34: ...Wiring Diagrams Outdoor Units 155 AWAU YLD060 H13 ...
Страница 40: ...Exploded View and Spare Part list Outdoor Units 161 Exploded View of outdoor unit AWAU YLD018 H11 ...