Electrical Control Function
224
Electrical Control System
Bit5
Frequency limit
caused by T4.
It means frequency limit
caused by T4,T3 and
current.
Bit4
Frequency limit
caused by T2.
Bit3
Frequency limit
caused by T3.
Bit2
Frequency limit
caused by T5.
Bit1
Frequency limit
caused by current
Bit0
Frequency limit
caused by voltage
16
DC fan motor speed
17
IGBT radiator temp.
The display value is between 30~120 degree. If the temp. is
lower than 30 degree, the digital display tube will show “30”.If
the temp. is higher than 99 degree, the digital display tube will
show single digit and tens digit. (For example, the digital
display tube show “0.5”,it means the IGBT radiator temp. is
105 degree. the digital display tube show “1.6”,it means the
IGBT radiator temp. is 116 degree)
18
Indoor unit number
The indoor unit can communicate with outdoor unit well.
19
Condenser pipe temp. of 1# indoor unit
If the temp. is lower than 0 degree, the digital display tube will
show “0”.If the temp. is higher than 70 degree, the digital
display tube will show “70”. If the capacity demand is 0, , the
digital display tube will show “0. If the indoor unit is not
connected, the digital display tube will show: “――”(heating
T2
,
cooling T2B)
20
Condenser pipe temp. of 2# indoor unit
21
Condenser pipe temp. of 3# indoor unit
22
1# Indoor unit capacity demand code
Actual data*HP*10
If capacity demand code is higher than 99, the digital display
tube will show single digit and tens digit. (For example, the
digital display tube show “5.0”,it means the capacity demand
is 15. the digital display tube show “60”,it means the capacity
demand is 6.0). If the indoor unit is not connected, the digital
display tube will show: “――”
23
2# Indoor unit capacity demand code
24
3# Indoor unit capacity demand code
Содержание AWAU-YLD012-H11
Страница 14: ...Dimensions Console Type 135 2 Dimensions AWSI XAD012 N11 AWSI XAD018 N11 ...
Страница 15: ...Service Space 136 Console Type 3 Service Space ...
Страница 16: ...Wiring Diagrams Console Type 137 4 Wiring Diagrams AWSI XAD012 N11 AWSI XAD018 N11 ...
Страница 21: ...Field Wiring 142 Console Type 10 Field Wiring AWSI XAD012 N11 AWSI XAD018 N11 ...
Страница 24: ...Exploded View and Spare Part list Console Type 145 Exploded View of indoor unit AWSI XAD018 N11 ...
Страница 31: ...Wiring Diagrams 152 Outdoor Units 4 Wiring Diagrams AWAU YLD012 H11 ...
Страница 32: ...Wiring Diagrams Outdoor Units 153 AWAU YLD018 H11 AWAU YLD024 H11 AWAU YLD030 H11 AWAU YLD036 H11 ...
Страница 33: ...Wiring Diagrams 154 Outdoor Units AWAU YLD036 H13 AWAU YLD048 H13 ...
Страница 34: ...Wiring Diagrams Outdoor Units 155 AWAU YLD060 H13 ...
Страница 40: ...Exploded View and Spare Part list Outdoor Units 161 Exploded View of outdoor unit AWAU YLD018 H11 ...