Troubleshooting
Electrical Control System
249
2.4.3.11. P3 malfunction
P3 display
Current protection of compressor
Judge 1: Check whether the
input current of the power
supply wire is more than
14A (For 24K it is 18A,For
36K 1phase it is 21.5A,For
36K 3phase it is11A)
Yes
Replace the electric control box
Check whether
the refrigerant
system is ok
Judge 2: Check whether the
outdoor ambient
temperature is higher than
50
℃
No
Stop the unit
Yes
Judge 3: Check whether the
outdoor unit is bad ventilation
No
Make the outdoor unit ventilate well
Yes
Judge 5: The refrigerant
pipe is blocked
No
Let the refrigerant out, then use the high
pressure nitrogen or refrigerant to blow pipe,
vacuumize and charge the refrigerant again
Yes
Judge 4: Check whether the
heat exchanger is dirty
No
Clean the heat exchanger
Yes
Yes
Replace outdoor main
board,and check whether
the system can run normally
No
Yes
Trouble is solved
Содержание AWAU-YLD012-H11
Страница 14: ...Dimensions Console Type 135 2 Dimensions AWSI XAD012 N11 AWSI XAD018 N11 ...
Страница 15: ...Service Space 136 Console Type 3 Service Space ...
Страница 16: ...Wiring Diagrams Console Type 137 4 Wiring Diagrams AWSI XAD012 N11 AWSI XAD018 N11 ...
Страница 21: ...Field Wiring 142 Console Type 10 Field Wiring AWSI XAD012 N11 AWSI XAD018 N11 ...
Страница 24: ...Exploded View and Spare Part list Console Type 145 Exploded View of indoor unit AWSI XAD018 N11 ...
Страница 31: ...Wiring Diagrams 152 Outdoor Units 4 Wiring Diagrams AWAU YLD012 H11 ...
Страница 32: ...Wiring Diagrams Outdoor Units 153 AWAU YLD018 H11 AWAU YLD024 H11 AWAU YLD030 H11 AWAU YLD036 H11 ...
Страница 33: ...Wiring Diagrams 154 Outdoor Units AWAU YLD036 H13 AWAU YLD048 H13 ...
Страница 34: ...Wiring Diagrams Outdoor Units 155 AWAU YLD060 H13 ...
Страница 40: ...Exploded View and Spare Part list Outdoor Units 161 Exploded View of outdoor unit AWAU YLD018 H11 ...