Troubleshooting
250
Electrical Control System
2.4.3.12. P4 malfunction
When
compressor discharge temperature is higher than 115°C, the unit will stop, and unit runs again when
compressor discharge temperature is lower than 90°C.
P4 display
Temperature protection of
compressor discharge
Check whether the
compressor discharge temp.
is more than 115°C ?
Check whether the wiring
connection is right between
compressor discharge temp.
sensor and PCB according
to wiring diagrams?
Method: Check whether the
resistance of compressor
discharge temp. sensor is
right refer to the
Appendix
2
No
Yes
Yes
Trouble is solved
No
Judge: The
discharge temp.
sensor is broken
Check whether the
refrigerant is leak
Correct the wiring connection
Stop leaking and add refrigerant
Replace the compressor discharge temp. sensor
No
Yes
Replace outdoor main board
Yes
Содержание AWAU-YLD012-H11
Страница 14: ...Dimensions Console Type 135 2 Dimensions AWSI XAD012 N11 AWSI XAD018 N11 ...
Страница 15: ...Service Space 136 Console Type 3 Service Space ...
Страница 16: ...Wiring Diagrams Console Type 137 4 Wiring Diagrams AWSI XAD012 N11 AWSI XAD018 N11 ...
Страница 21: ...Field Wiring 142 Console Type 10 Field Wiring AWSI XAD012 N11 AWSI XAD018 N11 ...
Страница 24: ...Exploded View and Spare Part list Console Type 145 Exploded View of indoor unit AWSI XAD018 N11 ...
Страница 31: ...Wiring Diagrams 152 Outdoor Units 4 Wiring Diagrams AWAU YLD012 H11 ...
Страница 32: ...Wiring Diagrams Outdoor Units 153 AWAU YLD018 H11 AWAU YLD024 H11 AWAU YLD030 H11 AWAU YLD036 H11 ...
Страница 33: ...Wiring Diagrams 154 Outdoor Units AWAU YLD036 H13 AWAU YLD048 H13 ...
Страница 34: ...Wiring Diagrams Outdoor Units 155 AWAU YLD060 H13 ...
Страница 40: ...Exploded View and Spare Part list Outdoor Units 161 Exploded View of outdoor unit AWAU YLD018 H11 ...