CONTROL
SYSTEM
module protective signal is detected, stop the unit with module protection immediately. If the
module protection is resumed and compressor has stopped for 3min, the unit will be allowed
to operate.
If the module protection continuously occurs for 6 times, it should not be resumed
automatically, it can resume by pressing ON/OFF.
11.12.9 Compressor overload protection
If the compressor OLP is over 115
o
C, the system will stop as protection
If the OLP is below 95
o
C and compressor has stopped for 3min, the unit will be allowed to
operate.
If the unit stops as compressor overload protection occurred for 6 times continuously, it can
not resume running automatically and display malfunction, it can resume by pressing
ON/OFF.
11.13
Operating the Unit from the ON/OFF Button
The ON/OFF button allows to operate the unit in AUTO mode, the microcomputer will monitor the
room temperature and select the (COOL, HEAT, FAN) mode automatically, and temperature/Fan
speed settings can not be changed.
11.14
Indoor Unit Controllers and Indicators
The following is schematic drawing for the display:
11-12
SM HGD-009/012 1-A.1 GB
RUN INDICATOR
1.
Lights up when the Air Conditioner is connected to
power and the mode is STBY.
2.
When the unit is turned on remotely, the RUN LED
goes out while the current setting running mode is
displayed
DEICING INDICATOR
1. Lights up when the Air Conditioner is under deicing
protection
HEAT LED
COOL
DRY LED
LED
RUN LED
DEICING LED
IR RECEIVER
Содержание AWAU-YGD009-H11
Страница 10: ...OUTLINE DIMENSION 4 OUTLINE DIMENSION 4 1 Indoor HGD009 012 4 2 Outdoor YGD009 SM HGD 009 012 1 A 1 GB 4 1 ...
Страница 11: ...OUTLINE DIMENSION 4 3 Outdoor YGD012 4 2 SM HGD 009 012 1 A 1 GB ...
Страница 24: ...WIRING DIAGRAMS 8 3 YGD009 8 4 YGD012 8 2 SM HGD 009 012 1 A 1 GB ...
Страница 25: ...REFRIGERATION DIAGRAM 9 REFRIGERATION DIAGRAMS 9 1 HGD009 YGD009 9 2 HGD012 YGD012 SM HGD 009 012 1 A 1 GB 9 1 ...
Страница 50: ...EXPLODED VIEW SPARE PART LIST 13 4 Exploded view of outdoor unit YGD009 13 4 SM HGD 009 012 1 A 1 GB ...
Страница 52: ...EXPLODED VIEW SPARE PART LIST 13 6 Exploded view of outdoor unit YGD012 13 6 SM HGD 009 012 1 A 1 GB ...
Страница 54: ...APPENDIX SM HDD HED 009 012 1 A 1 GB 13 1 APPENDIX ...