CONTROL SYSTEM
SM HGD-009/012 1-A.1 GB
11-9
11.12.1 Indoor Coil Defrost Protection
Conditions for Start Controlling
Judge the controlling start with the ICT (Indoor Coil Temperature) after
6min
from operation start.
During cooling operation, the signals being sent from the indoor unit allow the operating frequency
limitation and then prevent freezing of the indoor heat exchanger.
Compressor will operate at reduced frequency when ICT
≤
2
o
C
Compressor will stop when ICT
≤
-1
o
C for continuous 3 mins. And the indoor fan and louver will
remain at the original state.
Compressor will resume its original operation state when ICT
≥
10
o
C AND Comp OFF time
≥
3min
If the unit stops as such protection for 6 times, it can not resume running automatically and display
malfunction, it can resume by pressing ON/OFF.
11.12.2 Indoor Coil over Heating Protection
Conditions for Start Controlling
Judge the controlling start with the ICT after 2 sec from operation start.
During heating operation, the signals being sent from the indoor unit allow the operating frequency
limitation and prevent abnormal high pressure.
Compressor frequency is prohibited going up when ICT
≥
53
o
C
Compressor will operate at reduced frequency when ICT
≥
56
o
C
Compressor will stop when ICT
≥
60
o
C. And the indoor fan will stop after residual heating blowing
function finished.
Compressor will resume its original operation state when ICT
≤
50
o
C AND Comp OFF time
≥
3min
If the unit stops as such protection for 6 times, it can not resume running automatically and display
malfunction, it can resume by pressing ON/OFF.
11.12.3 Outdoor Coil over Heating Protection
Conditions for Start Controlling
Judge the controlling start with the OCT after 2 sec from operation start.
During heating operation, the signals being sent from the outdoor unit allow the operating frequency
limitation and prevent abnormal high pressure.
Compressor frequency is prohibited going up when OCT
≥
55
o
C
Compressor will operate at reduced frequency when OCT
≥
58
o
C
Compressor will stop when OCT
≥
62
o
C. And the indoor fan will run at preset speed.
Содержание AWAU-YGD009-H11
Страница 10: ...OUTLINE DIMENSION 4 OUTLINE DIMENSION 4 1 Indoor HGD009 012 4 2 Outdoor YGD009 SM HGD 009 012 1 A 1 GB 4 1 ...
Страница 11: ...OUTLINE DIMENSION 4 3 Outdoor YGD012 4 2 SM HGD 009 012 1 A 1 GB ...
Страница 24: ...WIRING DIAGRAMS 8 3 YGD009 8 4 YGD012 8 2 SM HGD 009 012 1 A 1 GB ...
Страница 25: ...REFRIGERATION DIAGRAM 9 REFRIGERATION DIAGRAMS 9 1 HGD009 YGD009 9 2 HGD012 YGD012 SM HGD 009 012 1 A 1 GB 9 1 ...
Страница 50: ...EXPLODED VIEW SPARE PART LIST 13 4 Exploded view of outdoor unit YGD009 13 4 SM HGD 009 012 1 A 1 GB ...
Страница 52: ...EXPLODED VIEW SPARE PART LIST 13 6 Exploded view of outdoor unit YGD012 13 6 SM HGD 009 012 1 A 1 GB ...
Страница 54: ...APPENDIX SM HDD HED 009 012 1 A 1 GB 13 1 APPENDIX ...