background image

En-6

 

CAUTION

Earth (Ground) the unit.
Do not connect the earth (ground) cable to a gas pipe, water pipe, lightning rod, or a 
telephone earth (ground) cable. 
Improper earthing (grounding) may cause electric shock.

Do not connect power supply cable to the transmission or remote controller terminals, 
as this will damage the product.

Never bundle the power supply cable and transmission cable, remote controller cable 
together. 
Separate these cable by 2 in (50 mm) or more. 
Bundling these cables together will cause miss operation or breakdown.

When handling PCB, static electricity charged in the body may cause malfunction of the 
PCB. Follow the cautions below:
• Establish an earth (ground) for the indoor and outdoor units and peripheral devices.
• Cut power (breaker) off.
• Touch metal part of the indoor units for more than 10 seconds to discharge static 

electricity charged in the body.

• Do not touch terminals of parts and patterns implemented on PCB.

5.1. Electrical 

requirement

• Select the power cable type and size 

in accordance with relevant local and 
national regulations.

Voltage rating

208/230 V

Operating range

187 to 253 V

• Specifications for local wiring power cord and branch wiring are in compliance with local 

code.

• Max. wire length: Set a length so that the voltage drop is less than 2%. Increase the wire 

diameter when the wire length is long.

Breaker should be installed at every refrigerant system. Do not use a breaker in a different 
refrigerant system.
Refer to the table for the breaker specifications of each installation condition. Perform 
the power crossover wiring within the range of the same refrigerant system. When the 
crossover wiring is done, make a connection for indoor units to satisfy conditions A and B 
below.

A. Current breaker requirements

Model

MCA

MAX. CKT. BKR 

(Fuse capacity)

• MCA: Minimum Circuit Ampacity
• MAX. CKT. BKR : Maximum Circuit 

Breaker

When the power crossover wiring is 
done, make it so that the total of the 
MCA of the connected RB units and 
indoor units does not exceed the 11 A. 
For RB unit MCA, refer to the RB unit 
installation manual.

ASUA4TLAV1

0.22 A

15 A

ASUA7TLAV1

0.32 A

ASUA9TLAV1

0.52 A

ASUB30TLAV1

0.90 A

ASUB36TLAV1

1.18 A

If the capacity of connected RB units and indoor units exceeds the upper limit, either add 
breakers or use a breaker with a greater capacity.

B. Earth leakage breaker requirements

Breaker capacity

Maximum connect-
able “indoor units” 

or “indoor units + 

RB units” (*1)

*1:  Heat pump type: indoor units, 

Heat recovery type: indoor units 
and RB units.

*2:  If the 100 mA capacity breaker is 

not provided, split the quantity of 
the indoor units into small groups 
of 9 units or less and provide a 
breaker with capacity of 30 mA for 
each group.

30 mA, 0.1 sec or less

36 or less

100 mA, 0.1 sec or less

37 to 121 (*2)

5.1.1 Cable speci

fi

 cations

Cable size

Cable type

Remarks

Transmission 
cable

22 AWG
(0.33 mm²)

LEVEL 4 (NEMA) non-polar 
2 core, twisted pair solid core 
diameter 0.026 in (0.65mm)

LONWORKS ® 
compatible cable

Remote con-
troller cable 
(2-wire type)

22 AWG to 16 AWG 
(0.33 to 1.25 mm²)

Sheathed PVC cable

Non polar 2 core, 
twisted pair

18AWG

Thermostat cable 2 core

Use sheathed non 
twisted pair cable

4.3.3 Pipe connection

When the flare nut is tightened properly by your hand, hold the body side coupling with a 
separate spanner, then tighten with a torque wrench.

 

CAUTION

Be sure to install the pipe against the port on the indoor unit and the outdoor unit cor-
rectly. If the centering is improper, the flare nut cannot tightened smoothly. If the flare 
nut is forced to turn, the threads will be damaged.

Do not remove the flare nut from the indoor unit pipe until immediately before connect-
ing the connection pipe.

Do not use mineral oil on flared part. Prevent mineral oil from getting into the system as 
this would reduce the lifetime of the units.

Hold the torque wrench at its grip, keeping it at a right angle with the pipe, in order to 
tighten the flare nut correctly.

Flare nut 
[in (mm)]

Tightening torque 

[lbf·ft (N·m)]

Connection pipe

Torque 
wrench

Indoor unit pipe 
(Body side)

Tighten with 2 wrenches.

Holding 
wrench

Flare 
nut

1/4 (6.35) dia.

11.8 to 13.3 (16 to 18)

3/8 (9.52) dia.

23.6 to 31.0 (32 to 42)

1/2 (12.70) dia.

36.1 to 45.0 (49 to 61)

5/8 (15.88) dia.

46.5 to 55.3 (63 to 75)

3/4 (19.05) dia.

66.4 to 81.1 (90 to 110)

5. ELECTRICAL 

WIRING

 

WARNING

Electrical work must be performed in accordance with this Manual by a person certified 
under the national or regional regulations. Be sure to use a dedicated circuit for the unit. 
An insufficient power supply circuit or improperly performed electrical work can cause 
serious accidents such as electric shock or fire.

Before starting work, check that power is not being supplied to the all units.

Use the included connection cables and power cables or ones specified by the 
manufacturer. Improper connections, insufficient insulation, or exceeding the allowable 
current can cause electric shock or fire.

For wiring, use the prescribed type of cables, connect them securely, making sure that 
there are no external forces of the cables applied to the terminal connections. Improp-
erly connected or secured cables can cause serious accidents such as overheating the 
terminals, electric shock, or fire.

Do not modify the power cables, use extension cables, or use any branches in the wir-
ing. Improper connections, insufficient insulation, or exceeding the allowable current can 
cause electric shock or fire.

Match the terminal board numbers and connection cable colors with those of the out-
door unit (or RB unit). Erroneous wiring may cause burning of the electric parts.

Securely connect the connection cables to the terminal board. In addition, secure the 
cables with wiring holders. Improper connections, either in the wiring or at the ends of 
the wiring, can cause a malfunction, electric shock, or fire.

Always fasten the outside covering of the connection cable with the cable clamp. (If the 
insulator is chafed, electric discharge may occur.)

Securely install the electrical box cover on the unit. An improperly installed electrical box 
cover can cause serious accidents such as electric shock or fire through exposure to 
dust or water.

Install sleeves into any holes made in the walls for wiring. Otherwise, a short circuit 
could result.

We suggest installing GFEB breakers or follow local electrical code. When installing 
this system, install using ground fault equipment breakers (GFEB) to reduce the risk of 
leaking current which result in electric shock or potential fire.

Always connect the earth (ground) cable.
Improper earthing (grounding) work can cause electric shocks.

Install the remote controller cables so as not to be direct touched with your hand.

Perform wiring work in accordance with standards so that the air conditioner can be 
operated safely and positively.

Connect the connection cable firmly to the terminal board. Imperfect installation may 
cause a fire.

If the supply cable is damaged, it must be replaced by the manufacturer, its service 
agent or similarly qualified persons in order to avoid a hazard.

9373370420-02_IM.indb   6

9373370420-02_IM.indb   6

2017/12/20   9:49:00

2017/12/20   9:49:00

Содержание ASUA4TLAV1

Страница 1: ...1 ASUB36TLAV1 TM Fran ais Espa ol MANUEL D INSTALLATION MANUAL DE INSTALACI N UNIT INT RIEURE Type montage mural UNIDAD INTERIOR Tipo montado en pared Pour le personnel agr uniquement nicamente para p...

Страница 2: ...k or repair electrical parts and wiring Keep your fingers and clothing away from any moving parts Clean up the site after you finish remembering to check that no metal scraps or bits of wiring have be...

Страница 3: ...ing a vacuum pump adapter A conventional vacuum pump can be used by installing a vacuum pump adapter Be sure that the pump oil does not back flow into the system Use one capable for vacuum suction of...

Страница 4: ...f the human sensor 30 36 model only CAUTION Do not hit or push the human sensor This may lead to damage or malfunction Do not touch the human sensor Any scratches or dirt may lead to incorrect detecti...

Страница 5: ...n hose Screw Drain fixture Remove the screw at the left of drain hose and pull out drain hose Vertically insert the drain hose toward the inside so that the drain fixture can accurately align with the...

Страница 6: ...pipes Failure to do so may cause water leaks Use heat insulation with heat resistance above 248 F 120 C Reverse cycle model only In addition if the humidity level at the installation location of the...

Страница 7: ...the flare nut cannot tightened smoothly If the flare nut is forced to turn the threads will be damaged Do not remove the flare nut from the indoor unit pipe until immediately before connect ing the co...

Страница 8: ...p B For strand wiring 1 Use ring terminals with insulating sleeves as shown in the figure below to connect to the terminal block 2 Securely clamp the ring terminals to the cables using an appropriate...

Страница 9: ...h installation manual 5 4 Wiring 1 Open the intake grille Refer to 8 FRONT PANEL REMOVAL AND INSTALLATION 2 Remove the wire cover and remove the cable clamp 4 7 9 model 30 36 model Screw Cable clamp W...

Страница 10: ...tached to wire kit connector 2 Remove insulation from field supplied cable Use crimp type insulated butt connector to join field cable and wire kit wire 3 Connect the wire with connecting wire with so...

Страница 11: ...hod of functions Operation Stop mode or Emergency stop mode Forced stop mode can be selected with function setting of indoor unit Forced thermostat off function Edge input only Connector Input signal...

Страница 12: ...1 0 1 1 0 1 2 0 2 2 0 2 3 0 3 3 0 3 4 0 4 4 0 4 5 0 5 5 0 5 6 0 6 6 0 6 7 0 7 7 0 7 8 0 8 8 0 8 9 0 9 9 0 9 10 1 0 10 1 0 11 1 1 11 1 1 12 1 2 12 1 2 99 9 9 63 6 3 Do not set the indoor unit address I...

Страница 13: ...For details of the connection ter minal functions see the Design Technical Manual 01 Mode 1 02 Mode 2 03 Mode 3 04 Mode 4 05 Mode 5 06 Mode 6 07 Mode 7 08 Mode 8 Control switching of external heaters...

Страница 14: ...F Center piping and G Left rear piping butt the connection pipe heat insulation and indoor unit pipe heat insulation together and bind them with vinyl tape so that there is no gap A Rear B Right and C...

Страница 15: ...f any obstacles No cooling No heating Does start and stop air conditioner operation by remote controller or external device No operation After installation is completed has the proper operation and ha...

Страница 16: ...r 4 1 Indoor unit room temp thermistor error 4 2 Indoor unit heat ex temp thermistor error 4 4 Human sensor error 5 1 Indoor unit fan motor 1 error 5 2 Indoor unit coil expan sion valve error 5 3 Indo...

Отзывы: