En-9

 Apply voltage terminal ([CNA01], [CNA03])

When a power supply must be provided at the input device you want to connect, use the 
Apply voltage terminal ([CNA01], [CNA03]).

*a

*b

*1

CNA01

CNA03

*a

*a

Input

de

vic

e 1

Input

de

vic

e 2

Input

de

vic

e 3

Load 
resistance

Load 
resistance

Load 
resistance

DC power supply
12 to 24V

Connected unit

P.C.B

*1: Make the power supply DC 12 to 24 V. Select a power supply capacity with an ample 

surplus for the connected load.
Do not impress a voltage exceeding 24 V across pins 1-2, and 1-3.

*a: The allowable current is DC 5 mA to 10 mA. (Recommended: DC 5 mA)

Provide a load resistance such that the current becomes DC 10 mA or less.
Select very low current use contacts (usable at DC 12 V, DC 1 mA or less).

*b: The polarity is [+] for pin 1 and [-] for pin 2 and 3. Connect correctly.

When connected to Apply voltage terminals of multiple indoor units with a connected unit, 
be sure to make a branch outside the indoor unit using a pull box, etc. as shown on below 
example.

CNA01

CNA01

CNA01

DC power supply 
12 to 24V

Connected unit

Load 
resistance

P.C.B

P.C.B

P.C.B

Input

de

vic

e 1

Input

de

vic

e 2

Indo

or

 unit

Indo

or

 unit

Indo

or

 unit

Load 
resistance

 Dry contact terminal ([CNA02], [CNA04])

When a power supply is unnecessary at the input device you want to connect, use the Dry 
contact terminal ([CNA02], [CNA04]).

CNA02

*c

*c

*c

*d

CNA04

P.C.B

GND

Ch 1

Ch 3

Ch 2

Connected unit

*c: Select very low current use contacts (usable at DC 12 V, DC 1 mA or less).
*d: The wiring is different from Apply voltage terminals. Be sufficiently careful when wiring.

5.5.2 Connection methods

Wire modification

(1)  Remove insulation from wire at-

tached to wire kit connector.

(2)  Remove insulation from field 

supplied cable. Use crimp type 
insulated butt connector to join field 
cable and wire kit wire.

(3)  Connect the wire with connecting 

wire with solder.

IMPORTANT:

Be sure to insulate the connection between the 
wires.

Locally 
purchased

Solder and insulate the connected parts.

Wire kit connector 
(optional parts)

Wiring arrangement

In following figure, all the possible connectors are connected for description.
In actual installation, you cannot connect all the connectors at once.

CNA02

CNA01

CNA03

CNA04

CNB01

CN65

CNA02

CNA01

CNA03

CNA04

CNB01

CN65

4/7/9 model

30/36 model

Controller PCB

Connecting cables

When replacing the control box cover, be sure to attach the wire with the screw.

Wire

Control box 
cover

Screw

Wire

Control box 
cover

Screw

4/7/9 model

30/36 model

5.6.  External input and external output (Optional parts)

In this setting, you need to remove the front panel. Refer to “8. FRONT PANEL REMOVAL 
AND INSTALLATION”.

5.6.1 External input

• Indoor unit can be Operation/Stop, Emergency stop or Forced stop by using indoor unit 

PCB CNA01 or CNA02.

• “Operation/Stop” mode, “Emergency stop” mode or “Forced stop” mode can be selected 

with function setting of indoor unit.

• Indoor unit can be Forced thermostat off by using indoor unit PCB CNA03 or CNA04.
• A twisted pair cable (22 AWG) should be used. Maximum length of cable is 192 ft (150 

m).

• Use an external input and output cable with appropriate external dimension, depending 

on the number of cables to be installed.

• The wire connection should be separate from the power cable line.

Input select

Use either one of these types of terminal according to the application. (Both types of 
terminals cannot be used simultaneously.)

9373370420-02_IM.indb   9

9373370420-02_IM.indb   9

2017/12/20   9:49:00

2017/12/20   9:49:00

Содержание ASUA4TLAV1

Страница 1: ...1 ASUB36TLAV1 TM Fran ais Espa ol MANUEL D INSTALLATION MANUAL DE INSTALACI N UNIT INT RIEURE Type montage mural UNIDAD INTERIOR Tipo montado en pared Pour le personnel agr uniquement nicamente para p...

Страница 2: ...k or repair electrical parts and wiring Keep your fingers and clothing away from any moving parts Clean up the site after you finish remembering to check that no metal scraps or bits of wiring have be...

Страница 3: ...ing a vacuum pump adapter A conventional vacuum pump can be used by installing a vacuum pump adapter Be sure that the pump oil does not back flow into the system Use one capable for vacuum suction of...

Страница 4: ...f the human sensor 30 36 model only CAUTION Do not hit or push the human sensor This may lead to damage or malfunction Do not touch the human sensor Any scratches or dirt may lead to incorrect detecti...

Страница 5: ...n hose Screw Drain fixture Remove the screw at the left of drain hose and pull out drain hose Vertically insert the drain hose toward the inside so that the drain fixture can accurately align with the...

Страница 6: ...pipes Failure to do so may cause water leaks Use heat insulation with heat resistance above 248 F 120 C Reverse cycle model only In addition if the humidity level at the installation location of the...

Страница 7: ...the flare nut cannot tightened smoothly If the flare nut is forced to turn the threads will be damaged Do not remove the flare nut from the indoor unit pipe until immediately before connect ing the co...

Страница 8: ...p B For strand wiring 1 Use ring terminals with insulating sleeves as shown in the figure below to connect to the terminal block 2 Securely clamp the ring terminals to the cables using an appropriate...

Страница 9: ...h installation manual 5 4 Wiring 1 Open the intake grille Refer to 8 FRONT PANEL REMOVAL AND INSTALLATION 2 Remove the wire cover and remove the cable clamp 4 7 9 model 30 36 model Screw Cable clamp W...

Страница 10: ...tached to wire kit connector 2 Remove insulation from field supplied cable Use crimp type insulated butt connector to join field cable and wire kit wire 3 Connect the wire with connecting wire with so...

Страница 11: ...hod of functions Operation Stop mode or Emergency stop mode Forced stop mode can be selected with function setting of indoor unit Forced thermostat off function Edge input only Connector Input signal...

Страница 12: ...1 0 1 1 0 1 2 0 2 2 0 2 3 0 3 3 0 3 4 0 4 4 0 4 5 0 5 5 0 5 6 0 6 6 0 6 7 0 7 7 0 7 8 0 8 8 0 8 9 0 9 9 0 9 10 1 0 10 1 0 11 1 1 11 1 1 12 1 2 12 1 2 99 9 9 63 6 3 Do not set the indoor unit address I...

Страница 13: ...For details of the connection ter minal functions see the Design Technical Manual 01 Mode 1 02 Mode 2 03 Mode 3 04 Mode 4 05 Mode 5 06 Mode 6 07 Mode 7 08 Mode 8 Control switching of external heaters...

Страница 14: ...F Center piping and G Left rear piping butt the connection pipe heat insulation and indoor unit pipe heat insulation together and bind them with vinyl tape so that there is no gap A Rear B Right and C...

Страница 15: ...f any obstacles No cooling No heating Does start and stop air conditioner operation by remote controller or external device No operation After installation is completed has the proper operation and ha...

Страница 16: ...r 4 1 Indoor unit room temp thermistor error 4 2 Indoor unit heat ex temp thermistor error 4 4 Human sensor error 5 1 Indoor unit fan motor 1 error 5 2 Indoor unit coil expan sion valve error 5 3 Indo...

Отзывы: