background image

En-11

6.1.  Setting the address

Manual address setting method

The indoor unit address and the refrigerant circuit address can also be set up through the 
wireless remote controller

 

CAUTION

Be sure to turn OFF the power before performing the field setting.

• Position and detail of the switches

4/7/9 model

30/36 model

In the 4/7/9 models, you need to remove 
the front panel. Refer to “8. FRONT PANEL 
REMOVAL AND INSTALLATION”.

4/7/9 model

30/36 model

SET3

×10  IU  AD  ×1

×10 REF AD ×1

SET4

For refrigerant 
circuit address

For indoor unit 
address

IU  AD

REF AD

RC AD

×10              ×1

×10             ×1

SET3

SET4

For refrigerant 
circuit address

For indoor 
unit address

• Please set it according to the following procedures when setting manually.

 

CAUTION

Use an insulated screwdriver to set the dip switches.

Be careful not to make mistakes for switch settings.

6.1.1  Indoor unit address

• Rotary switch (IU AD × 1)....Factory setting “0”
• Rotary switch (IU AD × 10)....Factory setting “0”
When connecting multiple indoor units to 1 refrigerant system, set the address at IU AD 
SW as shown in the Table A

6.1.2  Refrigerant circuit address

• Rotary switch (REF AD × 1)....Factory setting “0”
• Rotary switch (REF AD × 10)....Factory setting “0”
In the case of multiple refrigerant systems, set REF AD SW as shown in the Table A for 
each refrigerant system.
Set to the same refrigerant circuit address as the outdoor unit.

Setting

Setting range

Type of switch

Indoor unit 
address

0 to 63

Setting 
example 2

IU AD × 10

IU AD × 1

Refrigerant 
circuit address

0 to 99

Setting 
example 63

REF AD × 10

REF AD × 1

• If working in an environment where the wireless remote controller can be used, the ad-

dresses can also be set using the remote controller.

• If setting the addresses using the wireless remote controller, set the indoor unit address 

and refrigerant circuit address to “00”. 
(For information on setting using the wireless remote controller.)

Table A

Address

Rotary Switch Setting

Address

Rotary Switch Setting

Refrigerant circuit

REF AD SW

Indoor unit

IU AD SW

×

 10

×

 1

×

 10

×

 1

0

0

0

0

0

0

1

0

1

1

0

1

2

0

2

2

0

2

3

0

3

3

0

3

4

0

4

4

0

4

5

0

5

5

0

5

6

0

6

6

0

6

7

0

7

7

0

7

8

0

8

8

0

8

9

0

9

9

0

9

10

1

0

10

1

0

11

1

1

11

1

1

12

1

2

12

1

2

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

99

9

9

63

6

3

Do no

t set the indoor unit address (IU AD SW) at 64 to 99. It may result in failure.

6.2.  Custom code setting

• Selecting the custom code prevents the indoor unit mix-up. (figure below) 

(Up to 4 codes can be set.)

• Perform the setting for both the indoor unit and the remote controller.

Code change

Indoor unit

Remote 
controller

Confusion

A            B              C           D

A           B            C             D

• Custom code setting for indoor unit

Set the DIP switch SET3 SW1, 2, referring to the figure and table below.

4/7/9 model

30/36 model

SET3

×10  IU  AD  ×1

×10 REF AD ×1

SET4

DIP switch 
“SET3”

IU  AD

REF AD

RC AD

×10              ×1

×10             ×1

SET3

SET4

DIP switch “SET3”

SW

1

SW

2

SW

3

SW

4

ON

OFF

DIP switch “SET3”

DIP switch 

SET3

Custom code

A (Factory 

setting)

B

C

D

SW1

OFF

ON

OFF

ON

SW2

OFF

OFF

ON

ON

6.3. Function 

setting

 WARNING

Please make this setting after completing all construction works.

• FUNCTION SETTING can be performed with the wired or wireless remote controller. 

(The remote controller is optional equipment)

• Refer to the wired or wireless remote controller manual for detailed setting information.
• Refer to “6.1. Setting the address” for indoor unit address and refrigerant circuit address 

settings.

• Turn the power of the indoor unit ON before starting the setting.

*  Turning on the power to the indoor units initializes EEV, so make sure the piping air tight 

test and vacuuming have been conducted before turning on the power.

*  Also check again to make sure no wiring mistakes were made before turning on the 

power.

Function details

Function

Function 

number

Setting number

Default

Details

Filter 
indicator 
interval

11

00 Standard

Adjust the filter cleaning interval 
notification. If the notification is too 
early, change to setting 01. If the 
notification is too late, change to 
setting 02.

01 Longer

02 Shorter

Filter 
indicator 
action

13

00 Enable

Enable or disable the filter indica-
tor. Setting 02 is for use with a 
central remote controller.

01 Disable

02

Display only 
on central 
remote 
controller

(Forbid-
den)

23

00

 

9373370420-02_IM.indb   11

9373370420-02_IM.indb   11

2017/12/20   9:49:00

2017/12/20   9:49:00

Содержание ASUA4TLAV1

Страница 1: ...1 ASUB36TLAV1 TM Fran ais Espa ol MANUEL D INSTALLATION MANUAL DE INSTALACI N UNIT INT RIEURE Type montage mural UNIDAD INTERIOR Tipo montado en pared Pour le personnel agr uniquement nicamente para p...

Страница 2: ...k or repair electrical parts and wiring Keep your fingers and clothing away from any moving parts Clean up the site after you finish remembering to check that no metal scraps or bits of wiring have be...

Страница 3: ...ing a vacuum pump adapter A conventional vacuum pump can be used by installing a vacuum pump adapter Be sure that the pump oil does not back flow into the system Use one capable for vacuum suction of...

Страница 4: ...f the human sensor 30 36 model only CAUTION Do not hit or push the human sensor This may lead to damage or malfunction Do not touch the human sensor Any scratches or dirt may lead to incorrect detecti...

Страница 5: ...n hose Screw Drain fixture Remove the screw at the left of drain hose and pull out drain hose Vertically insert the drain hose toward the inside so that the drain fixture can accurately align with the...

Страница 6: ...pipes Failure to do so may cause water leaks Use heat insulation with heat resistance above 248 F 120 C Reverse cycle model only In addition if the humidity level at the installation location of the...

Страница 7: ...the flare nut cannot tightened smoothly If the flare nut is forced to turn the threads will be damaged Do not remove the flare nut from the indoor unit pipe until immediately before connect ing the co...

Страница 8: ...p B For strand wiring 1 Use ring terminals with insulating sleeves as shown in the figure below to connect to the terminal block 2 Securely clamp the ring terminals to the cables using an appropriate...

Страница 9: ...h installation manual 5 4 Wiring 1 Open the intake grille Refer to 8 FRONT PANEL REMOVAL AND INSTALLATION 2 Remove the wire cover and remove the cable clamp 4 7 9 model 30 36 model Screw Cable clamp W...

Страница 10: ...tached to wire kit connector 2 Remove insulation from field supplied cable Use crimp type insulated butt connector to join field cable and wire kit wire 3 Connect the wire with connecting wire with so...

Страница 11: ...hod of functions Operation Stop mode or Emergency stop mode Forced stop mode can be selected with function setting of indoor unit Forced thermostat off function Edge input only Connector Input signal...

Страница 12: ...1 0 1 1 0 1 2 0 2 2 0 2 3 0 3 3 0 3 4 0 4 4 0 4 5 0 5 5 0 5 6 0 6 6 0 6 7 0 7 7 0 7 8 0 8 8 0 8 9 0 9 9 0 9 10 1 0 10 1 0 11 1 1 11 1 1 12 1 2 12 1 2 99 9 9 63 6 3 Do not set the indoor unit address I...

Страница 13: ...For details of the connection ter minal functions see the Design Technical Manual 01 Mode 1 02 Mode 2 03 Mode 3 04 Mode 4 05 Mode 5 06 Mode 6 07 Mode 7 08 Mode 8 Control switching of external heaters...

Страница 14: ...F Center piping and G Left rear piping butt the connection pipe heat insulation and indoor unit pipe heat insulation together and bind them with vinyl tape so that there is no gap A Rear B Right and C...

Страница 15: ...f any obstacles No cooling No heating Does start and stop air conditioner operation by remote controller or external device No operation After installation is completed has the proper operation and ha...

Страница 16: ...r 4 1 Indoor unit room temp thermistor error 4 2 Indoor unit heat ex temp thermistor error 4 4 Human sensor error 5 1 Indoor unit fan motor 1 error 5 2 Indoor unit coil expan sion valve error 5 3 Indo...

Отзывы: