En-7

4.  PIPE INSTALLATION

 

CAUTION

Be more careful that foreign matter (oil, water, etc.) does not enter the piping than with 
refrigerant R410A models. Also, when storing the piping, securely seal the openings by 
pinching, taping, etc.

While welding the pipes, be sure to blow dry nitrogen gas through them.

4.1.  Selecting the pipe material

 

CAUTION

Do not use existing pipes from another refrigeration system or refrigerant.

Use pipes that have clean external and internal sides without any contamination which 
may cause trouble during use, such as sulfur, oxide, dust, cutting waste, oil, or water.

It is necessary to use seamless copper pipes.
Material : Phosphor deoxidized seamless copper pipes
It is desirable that the amount of residual oil is less than 40 mg/10 m.

Do  not  use  copper  pipes  that  have  a  collapsed,  deformed,  or  discolored  portion 
(especially  on  the  interior  surface).  Otherwise,  the  expansion  valve  or  capillary  tube 
may become blocked with contaminants.

Improper pipe selection will degrade performance. As an air conditioner using R410A 
incurs pressure higher than when using conventional (R22) refrigerant, it is necessary 
to choose adequate materials.

• 

Thicknesses of copper pipes used with R410A are as shown in the table.

• 

Never use copper pipes thinner than those indicated in the table even if they are 
available on the market.

Thicknesses of Annealed Copper Pipes (R410A)

Pipe outside diameter [mm (in)]

Thickness [mm]

6.35 (1/4)

0.80

9.52 (3/8)

0.80

12.70 (1/2)

0.80

15.88 (5/8)

1.00

19.05 (3/4)

1.20

4.2.  Pipe requirement

 

CAUTION

Refer  to  the  Installation  Manual  of  the  outdoor  unit  for  description  of  the  length  of 
connecting pipe or for diff erence of its elevation.

•  Use pipe with water-resistant heat insulation.

 

CAUTION

Install heat insulation around both the gas and liquid pipes. Failure to do so may cause 
water leaks.
Use heat insulation with heat resistance above 120 °C. (Reverse cycle model only)
In  addition,  if  the  humidity  level  at  the  installation  location  of  the  refrigerant  piping  is 
expected  to  exceed  70  %,  install  heat  insulation  around  the  refrigerant  piping.  If  the 
expected humidity level is 70 to 80 %, use heat insulation that is 15 mm or thicker and 
if the expected humidity exceeds 80 %, use heat insulation that is 20 mm or thicker. 
If heat insulation is used that is not as thick as specifi ed, condensation may form on 
the surface of the insulation. In addition, use heat insulation with heat conductivity of 
0.045 W/(m·K) or less (at 20 °C).

4.3.  Flare connection (Pipe connection)

 

WARNING

Tighten  the  flare  nuts  with  a  torque  wrench  using  the  specified  tightening  method. 
Otherwise,  the  fl are  nuts  could  break  after  a  prolonged  period,  causing  refrigerant  to 
leak and generate hazardous gas if the refrigerant comes into contact with a fl ame.

4.3.1. Flaring

Use special fl are tool exclusive for R410A.

(1) Cut the connection pipe to the necessary length with a pipe cutter.
(2)  Hold  the  pipe  downward  so  that  cuttings  will  not  enter  the  pipe  and  remove  any 

burrs.

(3)  Insert the fl are nut (always use the fl are nut attached to the indoor and outdoor units 

(or RB unit) respectively) onto the pipe and perform the fl are processing with a fl are 
tool. Use the special R410A fl are tool, Leakage of refrigerant may result if other fl are 
nuts are used.

(4)  Protect the pipes by pinching them or with tape to prevent dust, dirt, or water from 

entering the pipes.

Check if [L] is fl ared uniformly 
and is not cracked or scratched.

Die

Pipe

B

A

L

Pipe outside diameter 

[mm (in)]

Dimension A [mm]

Dimension B

-

0

0.4 

[mm]

Flare tool for R410A, 

clutch type

6.35 (1/4)

0 to 0.5

9.1

9.52 (3/8)

13.2

12.70 (1/2)

16.6

15.88 (5/8)

19.7

19.05 (3/4)

24.0

When using conventional (R22) fl are tools to fl are R410A pipes, the dimension A should 
be approximately 0.5 mm more than indicated in the table (for fl aring with R410A fl are 
tools) to achieve the specifi ed fl aring. Use a thickness gauge to measure the dimension A. 
It is recommended that a R410A fl aring tool is used.

Width across 

fl ats

Pipe outside diameter 

[mm (in)]

Width across flats of 

Flare nut [mm]

6.35 (1/4)

17

9.52 (3/8)

22

12.70 (1/2)

26

15.88 (5/8)

29

19.05 (3/4)

36

4.3.2. Bending pipes

• 

If pipes are shaped by hand, be careful not to collapse them.

• 

Do not bend the pipes in an angle more than 90°.

• 

When pipes are repeatedly bend or stretched, the material will harden, making it 
diffi  cult to bend or stretch them any more. 

• 

Do not bend or stretch the pipes more than 3 times.

 

CAUTION

To prevent breaking of the pipe, avoid sharp bends. 

If the pipe is bent repeatedly at the same place, it will break.

4.3.3. Pipe connection

 

CAUTION

Be sure to install the pipe against the port on the indoor unit correctly. If the centering 
is improper, the fl are nut cannot tighten smoothly. If the fl are nut is forced to turn, the 
threads will be damaged.

Do  not  remove  the  flare  nut  from  the  indoor  unit  pipe  until  immediately  before 
connecting the connection pipe.

Hold the torque wrench at its grip, keeping it at a right angle with the pipe, in order to 
tighten the fl are nut correctly.

Connect the piping so that the control box cover can easily be removed for servicing 
when necessary.

In order to prevent water from leaking into the control box, make sure that the piping is 
well insulated.

When the fl are nut is tightened properly by your hand, hold the body side coupling with 
a separate spanner, then tighten with a torque wrench. (See the table below for the fl are 
nut tightening torques.)

9374342549_IM.indb   7

9374342549_IM.indb   7

2/15/2019   5:46:02 PM

2/15/2019   5:46:02 PM

Содержание ARXD007GLEH

Страница 1: ...ipo conducto Pour le personnel agr uniquement nicamente para personal de servicio autorizado Italiano MANUALE DI INSTALLAZIONE UNIT INTERNA tipo a condotto A uso esclusivo del personale tecnico autori...

Страница 2: ...als that have been manufactured speci cally for R410A use Because the pressure of the R410A refrigerant is approximately 1 6 times higher than the R22 failure to use dedicated piping material or impro...

Страница 3: ...Application Operating manual 1 Installation manual 1 This book Installation template 1 For positioning the indoor unit Washer 8 For installing indoor unit Coupler heat insulation Large 1 For indoor s...

Страница 4: ...nst the weight of the indoor unit 2 The inlet and outlet ports should not be obstructed the air should be able to blow all over the room 3 Leave the space required to service the air conditioner 4 A p...

Страница 5: ...the duct to the outlet port of the indoor unit be sure to insulate the outlet port and the installation screws to prevent water from leaking around the port AR007 009 012 014 018 Model Set the static...

Страница 6: ...5 times the weight of the main unit and which will not amplify sound or vibration If the installation location is not strong enough the indoor unit may fall and cause injuries If the job is done with...

Страница 7: ...orts The grilles must be designed in such a way that cannot be removed without tools When connecting the duct to the outlet port of the indoor unit be sure to insulate the outlet port and the installa...

Страница 8: ...break after a prolonged period causing refrigerant to leak and generate hazardous gas if the refrigerant comes into contact with a ame 4 3 1 Flaring Use special are tool exclusive for R410A 1 Cut the...

Страница 9: ...he construction by using the visible portion of transparent drain port and the drain piping nal outlet on the body CAUTION Do not apply adhesive agent on the drain port of the body Use the attached dr...

Страница 10: ...ess 20 mm Hose band Drain hose Fasten the Hose band at the position where horizontal against earth ground The Hose band must be positioned at the right side of the Drain hose as in the gure 2 Be sure...

Страница 11: ...touched with your hand Perform wiring work in accordance with standards so that the air conditioner can be operated safely and positively Connect the connection cable firmly to the terminal board Imp...

Страница 12: ...otherwise the screw heads may be damaged and prevent the screws from being properly tightened 4 Do not tighten the terminal screws too much otherwise the screws may break 5 See the table for the termi...

Страница 13: ...pply Refer to Power indicator lamp status following CN150 Connect to the Grille 1 CN151 CN152 CNA01 Apply voltage terminal For external input CNA03 CNA02 Dry contact terminal CNA04 DIP switch SET 2 SW...

Страница 14: ...oltage terminal CNA01 CNA03 Input device 1 Input device 2 Input device 3 Load resistance Load resistance Load resistance 1 DC power supply 12 to 24V connected unit a a a P C B CNA01 CNA03 b 1 Make the...

Страница 15: ...setting Connector Input signal Command 60 09 Ch3 of CNA03 or CNA04 OFF ON No command ON OFF Refrigerant leak 2 External output A twisted pair cable 22AWG should be used Maximum length of cable is 25m...

Страница 16: ...AD SW 10 1 10 1 0 0 0 0 0 0 1 0 1 1 0 1 2 0 2 2 0 2 3 0 3 3 0 3 4 0 4 4 0 4 5 0 5 5 0 5 10 1 0 10 1 0 11 1 1 11 1 1 99 9 9 63 6 3 7 2 Custom code setting Selecting the custom code prevents the indoor...

Страница 17: ...he input to the external input terminals and Start Stop by a remote controller is restricted 01 Emergency stop 02 Forced stop Error report target 47 00 All Change the target for reporting errors Error...

Страница 18: ...room temp therm istor error 4 2 Indoor unit heat ex temp thermistor error 5 1 Indoor unit fan motor 1 error 5 2 Indoor unit coil expansion valve error 5 3 Indoor unit water drain abnormal 9 15 Outdoor...

Отзывы: