En-14

NOTE :

When connected to multiple indoor units directly, it will cause breakdown.

Operation behavior

● Input signal type

The input signal type can be selected.
It is switched by DIP switch on the indoor unit PCB. 

Pulse

The width of pulse 
must be longer than  
200msec.

Edge

DIP switch [Set 2 SW2]

Input signal type

OFF (Factory setting)

Edge

ON

Pulse

● When function setting is “Operation/Stop” mode.

[In the case of “Edge” input]

Connector

Input signal

Command

Ch1 of CNA01 or CNA02

OFF → ON

Operation

ON → OFF

Stop

[In the case of “Pulse” input]

Connector

Input signal

Command

CNA01 or CNA02

Ch1

OFF → ON

Operation

Ch2

OFF → ON

Stop

*  The last command has priority.
*  The indoor units within the same remote controller group operates in the same mode.

● When function setting is “Emergency stop” mode.

[In the case of “Edge” input]

Connector

Input signal

Command

Ch1 of CNA01 or CNA02

OFF → ON

Emergency stop

ON → OFF

Normal

[In the case of “Pulse” input]

Connector

Input signal

Command

CNA01 or CNA02

Ch1

OFF → ON

Emergency stop

Ch2

OFF → ON

Normal

*  All indoor units of same refrigerant system stops when Emergency stop operates. 

● When function setting is “Forced stop” mode.

[In the case of “Edge” input]

Connector

Input signal

Command

Ch1 of CNA01 or CNA02

OFF → ON

Forced stop

ON → OFF

Normal

[In the case of “Pulse” input]

Connector

Input signal

Command

CNA01 or CNA02

Ch1

OFF → ON

Forced stop

Ch2

OFF → ON

Normal

*  When the forced stop is triggered, indoor unit stops and Operation/Stop operation by a 

remote controller is restricted.

*  When forced stop function is used with forming a remote controller group, connect the 

same equipment to each indoor unit within the group.

• Selection method of functions

“Operation/Stop” mode or “Emergency stop” mode, “Forced stop” mode can be selected 
with function setting of indoor unit.

● Forced thermostat off  function

[“Edge” input only]

Function 

setting

Connector

Input signal

Command

60-00

Ch3 of CNA03 or 
CNA04

OFF → ON

Thermostat off

ON → OFF

Normal

● Refrigerant leak detection function (only for J-IIIL series)

[“Edge” input only]

Function 

setting

Connector

Input signal

Command

60-09

Ch3 of CNA03 or 
CNA04

OFF → ON

No command

ON → OFF

Refrigerant leak

(2) External output

•  A twisted pair cable (22AWG) should be used. Maximum length of cable is 25m.
•  Use an external input and output cable with appropriate external dimension, depending 

on the number of cables to be installed.

•  Output voltage: Hi DC12V±2V, Lo 0V.
•  Permissible current: 50mA

Output select

● When indicator etc. are connected directly

Operation

indicator

Error

indicator

Indoor unit Fan

status indicator

connected unit

P.C.B

CNB

01

● When connecting with unit equipped with a power supply

CNB

01

P.C.B

Connected

device 1

Connected

device 2

Connected

device 3

connected unit

Relay (locally purchased)

Operation behavior

Connector

Output voltage

Status

CNB01

External output1
Pins 1-2

0V

Stop

DC 12 V

Operation

External output2
Pins 1-3

0V

Normal

DC 12 V

Error

External output3 
Pins 1-4

0V

Indoor unit fan stop

DC 12 V

Indoor unit fan operation

6.7.  Remote sensor (Optional parts)

Connection method

•  Remove the existing connector and replace it with the remote sensor connector (ensure 

that the correct connector is used).

•  The original connector should be insulated to ensure that it does not come into contact 

with other electrical circuitry.

•  Use conduit hole when external output cable is used.

Setting for room temperature correction

When a remote sensor is connected, set the function setting of indoor unit as indicated 
below.

•  Function Number “30”:

Set the Setting Number to “00”. (Default)

•  Function Number “31”:

Set the Setting Number to “02”.

* Refer to “7.6. Function setting” for details about Function Number and Setting Number

6.8.  IR receiver unit (Optional parts)

•  For the installation method, please refer to the INSTALLATION MANUAL of IR receiver 

unit. 

Connection method

•  Use 9 pins for receiver unit cable.
•  At fi rst, connect the receiver unit cable to the controller PCB.
•  Attach the core that comes between controller PCB and the clamp.
•  Use conduit hole when external output cable is used.

6.9.  Auto louver grille kit (Optional parts)

•  For the installation method, please refer to the INSTALLATION MANUAL of Auto louver 

grille kit. 

9374342549_IM.indb   14

9374342549_IM.indb   14

2/15/2019   5:46:09 PM

2/15/2019   5:46:09 PM

Содержание ARXD007GLEH

Страница 1: ...ipo conducto Pour le personnel agr uniquement nicamente para personal de servicio autorizado Italiano MANUALE DI INSTALLAZIONE UNIT INTERNA tipo a condotto A uso esclusivo del personale tecnico autori...

Страница 2: ...als that have been manufactured speci cally for R410A use Because the pressure of the R410A refrigerant is approximately 1 6 times higher than the R22 failure to use dedicated piping material or impro...

Страница 3: ...Application Operating manual 1 Installation manual 1 This book Installation template 1 For positioning the indoor unit Washer 8 For installing indoor unit Coupler heat insulation Large 1 For indoor s...

Страница 4: ...nst the weight of the indoor unit 2 The inlet and outlet ports should not be obstructed the air should be able to blow all over the room 3 Leave the space required to service the air conditioner 4 A p...

Страница 5: ...the duct to the outlet port of the indoor unit be sure to insulate the outlet port and the installation screws to prevent water from leaking around the port AR007 009 012 014 018 Model Set the static...

Страница 6: ...5 times the weight of the main unit and which will not amplify sound or vibration If the installation location is not strong enough the indoor unit may fall and cause injuries If the job is done with...

Страница 7: ...orts The grilles must be designed in such a way that cannot be removed without tools When connecting the duct to the outlet port of the indoor unit be sure to insulate the outlet port and the installa...

Страница 8: ...break after a prolonged period causing refrigerant to leak and generate hazardous gas if the refrigerant comes into contact with a ame 4 3 1 Flaring Use special are tool exclusive for R410A 1 Cut the...

Страница 9: ...he construction by using the visible portion of transparent drain port and the drain piping nal outlet on the body CAUTION Do not apply adhesive agent on the drain port of the body Use the attached dr...

Страница 10: ...ess 20 mm Hose band Drain hose Fasten the Hose band at the position where horizontal against earth ground The Hose band must be positioned at the right side of the Drain hose as in the gure 2 Be sure...

Страница 11: ...touched with your hand Perform wiring work in accordance with standards so that the air conditioner can be operated safely and positively Connect the connection cable firmly to the terminal board Imp...

Страница 12: ...otherwise the screw heads may be damaged and prevent the screws from being properly tightened 4 Do not tighten the terminal screws too much otherwise the screws may break 5 See the table for the termi...

Страница 13: ...pply Refer to Power indicator lamp status following CN150 Connect to the Grille 1 CN151 CN152 CNA01 Apply voltage terminal For external input CNA03 CNA02 Dry contact terminal CNA04 DIP switch SET 2 SW...

Страница 14: ...oltage terminal CNA01 CNA03 Input device 1 Input device 2 Input device 3 Load resistance Load resistance Load resistance 1 DC power supply 12 to 24V connected unit a a a P C B CNA01 CNA03 b 1 Make the...

Страница 15: ...setting Connector Input signal Command 60 09 Ch3 of CNA03 or CNA04 OFF ON No command ON OFF Refrigerant leak 2 External output A twisted pair cable 22AWG should be used Maximum length of cable is 25m...

Страница 16: ...AD SW 10 1 10 1 0 0 0 0 0 0 1 0 1 1 0 1 2 0 2 2 0 2 3 0 3 3 0 3 4 0 4 4 0 4 5 0 5 5 0 5 10 1 0 10 1 0 11 1 1 11 1 1 99 9 9 63 6 3 7 2 Custom code setting Selecting the custom code prevents the indoor...

Страница 17: ...he input to the external input terminals and Start Stop by a remote controller is restricted 01 Emergency stop 02 Forced stop Error report target 47 00 All Change the target for reporting errors Error...

Страница 18: ...room temp therm istor error 4 2 Indoor unit heat ex temp thermistor error 5 1 Indoor unit fan motor 1 error 5 2 Indoor unit coil expansion valve error 5 3 Indoor unit water drain abnormal 9 15 Outdoor...

Отзывы: