En-12

 

WARNING

Tighten the terminal screws to the specifi ed torques, otherwise, abnormal overheating 
may be produced and possibly cause heavy damage inside the unit.

Terminal number

Tightening torque

M3 screw (Transmission/X1, X2) 
(Remote controller/ Y1, Y2)

0.5 to 0.6 N·m 

(5 to 6 kgf·cm)

 

CAUTION

To  peel  the  fi lm  from  the  lead  cable,  use  a  dedicated  tool  that  will  not  damage  the 
conductor cable.

When installing a screw on the terminal block, do not cut the cable by overtightening 
the screw. On the other hand, an undertightened screw can cause faulty contact, which 
will lead to a communication failure.

6.4.  Connection of wiring

(1)  Remove the cover.
(2)  Connect the connection cable.

Cover

Screw

GND

L, N: Power supply cable

X1, X2: Transmission cable

Y1,Y2: Remote 
controller cable

Cable clamp

Cable tie (Medium) 
(Accessories)

Avoid covering the air 
inlet with the wiring.

Avoid touching the ceiling with the wiring

Ceiling

Power supply 
cable

Do not bind the power supply cable and other cables together.

6.5. Optional parts wiring

6.5.1. Layout of the indoor unit PCB

CN8

CN155

CN820

CN65

CN48

SW1 SW2 SW3 SW4

CNB01

CNA01

CNA03

CNA02

CNA04

Controller PCB

OFF 

ON

DIP switch 
(SET 2)

Power indicator 
lamp (green)

Name

Application

Power indicator 
lamp (green)

Indicates the state of the power supply. Refer to “Power indicator 
lamp status” following.

CN150

Connect to the Grille. (*1)

CN151
CN152
CNA01

Apply voltage terminal

For external input

CNA03
CNA02

Dry contact terminal

CNA04
DIP switch SET 2 
(SW2)

Input signal type switching

CNB01

Output terminal

For external outnput

CN8

For Remote sensor unit (*1)

CN48

For IR receiver unit (*1)

CN65

For one of the following.
• MODBUS® convertor (*1)
• Wireless LAN adapter (*1)

CN155

For Auto louver grille kit (*1)

CN820

For External power supply unit (*1)

*1:  For details, refer to each installation manual.

6.5.2. Power indicator lamp status

Power indicator lamp (Green)

Status contents

 Lit

Lit when the power is turned on.

  Fast flashing (every 0.1 

second)

There is a fault with the communication board or the 
main board.

  Blinking (repeat 3 seconds ON 

and 1 second OFF)

The indoor unit is turned off and power is supplied 
from the External power supply unit (optional) to the 
indoor unit PCB.

6.4.2  Connection methods

Wire modification for External 
input/output wire

(1)  Remove insulation from wire at-

tached to wire kit connector.

(2)  Remove insulation from field 

supplied cable. Use crimp type 
insulated butt connector to join field 
cable and wire kit wire.

(3)  Connect the wire with connecting 

wire with solder.

IMPORTANT:

Be sure to insulate the connection between the 
wires.

Locally 
purchased

Solder and insulate the connected parts.

Wire kit connector 
(optional parts)

9374342549_IM.indb   12

9374342549_IM.indb   12

2/15/2019   5:46:07 PM

2/15/2019   5:46:07 PM

Содержание ARXD007GLEH

Страница 1: ...ipo conducto Pour le personnel agr uniquement nicamente para personal de servicio autorizado Italiano MANUALE DI INSTALLAZIONE UNIT INTERNA tipo a condotto A uso esclusivo del personale tecnico autori...

Страница 2: ...als that have been manufactured speci cally for R410A use Because the pressure of the R410A refrigerant is approximately 1 6 times higher than the R22 failure to use dedicated piping material or impro...

Страница 3: ...Application Operating manual 1 Installation manual 1 This book Installation template 1 For positioning the indoor unit Washer 8 For installing indoor unit Coupler heat insulation Large 1 For indoor s...

Страница 4: ...nst the weight of the indoor unit 2 The inlet and outlet ports should not be obstructed the air should be able to blow all over the room 3 Leave the space required to service the air conditioner 4 A p...

Страница 5: ...the duct to the outlet port of the indoor unit be sure to insulate the outlet port and the installation screws to prevent water from leaking around the port AR007 009 012 014 018 Model Set the static...

Страница 6: ...5 times the weight of the main unit and which will not amplify sound or vibration If the installation location is not strong enough the indoor unit may fall and cause injuries If the job is done with...

Страница 7: ...orts The grilles must be designed in such a way that cannot be removed without tools When connecting the duct to the outlet port of the indoor unit be sure to insulate the outlet port and the installa...

Страница 8: ...break after a prolonged period causing refrigerant to leak and generate hazardous gas if the refrigerant comes into contact with a ame 4 3 1 Flaring Use special are tool exclusive for R410A 1 Cut the...

Страница 9: ...he construction by using the visible portion of transparent drain port and the drain piping nal outlet on the body CAUTION Do not apply adhesive agent on the drain port of the body Use the attached dr...

Страница 10: ...ess 20 mm Hose band Drain hose Fasten the Hose band at the position where horizontal against earth ground The Hose band must be positioned at the right side of the Drain hose as in the gure 2 Be sure...

Страница 11: ...touched with your hand Perform wiring work in accordance with standards so that the air conditioner can be operated safely and positively Connect the connection cable firmly to the terminal board Imp...

Страница 12: ...otherwise the screw heads may be damaged and prevent the screws from being properly tightened 4 Do not tighten the terminal screws too much otherwise the screws may break 5 See the table for the termi...

Страница 13: ...pply Refer to Power indicator lamp status following CN150 Connect to the Grille 1 CN151 CN152 CNA01 Apply voltage terminal For external input CNA03 CNA02 Dry contact terminal CNA04 DIP switch SET 2 SW...

Страница 14: ...oltage terminal CNA01 CNA03 Input device 1 Input device 2 Input device 3 Load resistance Load resistance Load resistance 1 DC power supply 12 to 24V connected unit a a a P C B CNA01 CNA03 b 1 Make the...

Страница 15: ...setting Connector Input signal Command 60 09 Ch3 of CNA03 or CNA04 OFF ON No command ON OFF Refrigerant leak 2 External output A twisted pair cable 22AWG should be used Maximum length of cable is 25m...

Страница 16: ...AD SW 10 1 10 1 0 0 0 0 0 0 1 0 1 1 0 1 2 0 2 2 0 2 3 0 3 3 0 3 4 0 4 4 0 4 5 0 5 5 0 5 10 1 0 10 1 0 11 1 1 11 1 1 99 9 9 63 6 3 7 2 Custom code setting Selecting the custom code prevents the indoor...

Страница 17: ...he input to the external input terminals and Start Stop by a remote controller is restricted 01 Emergency stop 02 Forced stop Error report target 47 00 All Change the target for reporting errors Error...

Страница 18: ...room temp therm istor error 4 2 Indoor unit heat ex temp thermistor error 5 1 Indoor unit fan motor 1 error 5 2 Indoor unit coil expansion valve error 5 3 Indoor unit water drain abnormal 9 15 Outdoor...

Отзывы: