En-3

3.  INSTALLATION WORK

3.1.  Selecting an installation location

Correct initial installation location is important because it is difficult to move unit after it is 
installed.

 

WARNING

Select  installation  locations  that  can  properly  support  the  weight  of  the  indoor.  Install 
the units securely so that they do not topple or fall.

 

CAUTION

Do not install the unit in the following areas:
•  Area with high salt content, such as at the seaside. 
  It will deteriorate metal parts, causing the parts to fail or the unit to leak water.
•  Area  fi lled  with  mineral  oil  or  containing  a  large  amount  of  splashed  oil  or  steam, 

such as a kitchen. 

  It will deteriorate plastic parts, causing the parts to fail or the unit to leak water.
•  Area that generates substances that adversely aff ect the equipment, such as sulfuric 

gas, chlorine gas, acid, or alkali. 

  It  will  cause  the  copper  pipes  and  brazed  joints  to  corrode,  which  can  cause 

refrigerant leakage.

•  Area  that  can  cause  combustible  gas  to  leak,  contains  suspended  carbon  fi bers  or 

fl ammable dust, or volatile infl ammables such as paint thinner or gasoline. 

  If gas leaks and settles around the unit, it can cause a fi re.
•  Area where animals may urinate on the unit or ammonia may be generated.

Do not use the unit for special purposes, such as storing food, raising animals, growing 
plants, or preserving precision devices or art objects. 
It can degrade the quality of the preserved or stored objects.

Do not install where there is the danger of combustible gas leakage.

Do not install the unit near a source of heat, steam, or fl ammable gas.

Install the unit where drainage does not cause any trouble.

Install  the  indoor  unit,  power  supply  cable,  transmission  cable,  and  remote  controller 
cable at least 1 m away from a television or radio receivers. The purpose of this is to 
prevent TV reception interference or radio noise.
(Even  if  they  are  installed  more  than  1  m  apart,  you  could  still  receive  noise  under 
some signal conditions.)

If children under 10 years old may approach the unit, take preventive measures so that 
they cannot reach the unit.

Decide the mounting position with the customer as follows:

(1) Install the indoor unit on a place having a suffi  cient strength so that it withstands 

against the weight of the indoor unit.

(2) The inlet and outlet ports should not be obstructed; the air should be able to blow all 

over the room.

(3) Leave the space required to service the air conditioner.

(4) A place from where the air can be distributed evenly throughout the room by the unit.

(5) Install the unit where connection to the outdoor unit (or RB unit) is easy.

(6) Install the unit where the connection pipe can be easily installed.

(7) Install the unit where the drain pipe can be easily installed.

(8) Install the unit where noise and vibrations are not amplifi ed.

(9) Take servicing, etc., into consideration and leave the spaces. Also install the unit 

where the fi lter can be removed.

3.2.  Installation dimensions (Ceiling concealed type)

Provide a service access for inspection purposes. 
Do not place any wiring or illumination in the service space, as they will impede service.

Installation Dimensions

Left 
side

Strong and durable ceiling

Indoor unit

Right 
side

150 mm 
or more 

400 mm 
or more

Service access

Ceiling

2500 mm or more

(When no ceiling)

Floor

240 mm or more

20 mm or more

20 mm or more

300 mm or more

Adjust the wind direction in the room depending on the shape of blow out opening.

Service space

Indoor unit

300 mm or more

Service access

[Top view]

400 mm or 
more

100 mm 

or more

Air

Air

3.3.  Installation dimensions (Wall mounted type/Floor 

standing concealed type)

The wall mounted type/fl oor standing concealed type requires a temperature correction 
setting. Perform this in “7. FIELD SETTING”.

Strong and 
durable floor

10 mm 
or less

Left side

Left side

150 mm 
or more

150 mm 
or more

150 mm 
or more

150 mm 
or more

150 mm 
or more

150 mm 
or more

20 mm 
or more

20 mm 
or more

20 mm 
or more

20 mm 
or more

400 mm 
or more

400 mm 
or more

Inlet air

Inlet air

Strong and 
durable floor

Strong and 
durable floor

10 mm 
or less Right side 

(PIPE side)

Right side 
(PIPE side)

Grille

Duct

Grille

Strong and 
durable floor

3.4.  Installing the unit (Ceiling concealed type)

 

WARNING

Install the air conditioner in a location which can withstand a load of at least 5 times the 
weight of the main unit and which will not amplify sound or vibration. If the installation 
location is not strong enough, the indoor unit may fall and cause injuries.

If the job is done with the panel frame only, there is a risk that the unit will come loose. 
Please take care.

9374342549_IM.indb   3

9374342549_IM.indb   3

2/15/2019   5:45:54 PM

2/15/2019   5:45:54 PM

Содержание ARXD007GLEH

Страница 1: ...ipo conducto Pour le personnel agr uniquement nicamente para personal de servicio autorizado Italiano MANUALE DI INSTALLAZIONE UNIT INTERNA tipo a condotto A uso esclusivo del personale tecnico autori...

Страница 2: ...als that have been manufactured speci cally for R410A use Because the pressure of the R410A refrigerant is approximately 1 6 times higher than the R22 failure to use dedicated piping material or impro...

Страница 3: ...Application Operating manual 1 Installation manual 1 This book Installation template 1 For positioning the indoor unit Washer 8 For installing indoor unit Coupler heat insulation Large 1 For indoor s...

Страница 4: ...nst the weight of the indoor unit 2 The inlet and outlet ports should not be obstructed the air should be able to blow all over the room 3 Leave the space required to service the air conditioner 4 A p...

Страница 5: ...the duct to the outlet port of the indoor unit be sure to insulate the outlet port and the installation screws to prevent water from leaking around the port AR007 009 012 014 018 Model Set the static...

Страница 6: ...5 times the weight of the main unit and which will not amplify sound or vibration If the installation location is not strong enough the indoor unit may fall and cause injuries If the job is done with...

Страница 7: ...orts The grilles must be designed in such a way that cannot be removed without tools When connecting the duct to the outlet port of the indoor unit be sure to insulate the outlet port and the installa...

Страница 8: ...break after a prolonged period causing refrigerant to leak and generate hazardous gas if the refrigerant comes into contact with a ame 4 3 1 Flaring Use special are tool exclusive for R410A 1 Cut the...

Страница 9: ...he construction by using the visible portion of transparent drain port and the drain piping nal outlet on the body CAUTION Do not apply adhesive agent on the drain port of the body Use the attached dr...

Страница 10: ...ess 20 mm Hose band Drain hose Fasten the Hose band at the position where horizontal against earth ground The Hose band must be positioned at the right side of the Drain hose as in the gure 2 Be sure...

Страница 11: ...touched with your hand Perform wiring work in accordance with standards so that the air conditioner can be operated safely and positively Connect the connection cable firmly to the terminal board Imp...

Страница 12: ...otherwise the screw heads may be damaged and prevent the screws from being properly tightened 4 Do not tighten the terminal screws too much otherwise the screws may break 5 See the table for the termi...

Страница 13: ...pply Refer to Power indicator lamp status following CN150 Connect to the Grille 1 CN151 CN152 CNA01 Apply voltage terminal For external input CNA03 CNA02 Dry contact terminal CNA04 DIP switch SET 2 SW...

Страница 14: ...oltage terminal CNA01 CNA03 Input device 1 Input device 2 Input device 3 Load resistance Load resistance Load resistance 1 DC power supply 12 to 24V connected unit a a a P C B CNA01 CNA03 b 1 Make the...

Страница 15: ...setting Connector Input signal Command 60 09 Ch3 of CNA03 or CNA04 OFF ON No command ON OFF Refrigerant leak 2 External output A twisted pair cable 22AWG should be used Maximum length of cable is 25m...

Страница 16: ...AD SW 10 1 10 1 0 0 0 0 0 0 1 0 1 1 0 1 2 0 2 2 0 2 3 0 3 3 0 3 4 0 4 4 0 4 5 0 5 5 0 5 10 1 0 10 1 0 11 1 1 11 1 1 99 9 9 63 6 3 7 2 Custom code setting Selecting the custom code prevents the indoor...

Страница 17: ...he input to the external input terminals and Start Stop by a remote controller is restricted 01 Emergency stop 02 Forced stop Error report target 47 00 All Change the target for reporting errors Error...

Страница 18: ...room temp therm istor error 4 2 Indoor unit heat ex temp thermistor error 5 1 Indoor unit fan motor 1 error 5 2 Indoor unit coil expansion valve error 5 3 Indoor unit water drain abnormal 9 15 Outdoor...

Отзывы: