background image

En-5

 

CAUTION

  To prevent people from touching the parts inside the unit, be sure to install grilles on 

the inlet and outlet ports. The grilles must be designed in such a way that cannot be 
removed without tools.

  The static pressure outside the unit is as follows.
  ARXA24/30/36/45L Model: 30-150 Pa   
  ARXB24/30/36/45L Models: 0-80 Pa

  If an intake duct is installed, take care not to damage the temperature sensor (the 

temperature sensor is attached to the intake port 

fl

 ange).

  Install the air inlet grille for air circulation. The correct temperature can not be detected.

Unit

Outlet Grille

(Field supply)

Inlet Grille

(Field supply)

(Room)

Duct

(Field supply)

  Be sure to install the air 

fi

 lter in the air inlet. If the air 

fi

 lter is not installed, the heat 

exchanger may be clogged and its performance may decrease.

3.3.5. Fresh air intake

(Processing before use)

(1) When taking in fresh air, cut a slit shaped cabinet in the left side of the outer case 

with nippers.

Cut

Cut

Cabinet (Iron plate)

Round hole

 

CAUTION

  When removing the cabinet (iron plate), be careful not to damage the indoor unit 

internal parts and surrounding area (outer case).

  When processing the cabinet (iron plate), be careful not to injure yourself with burrs, 

etc.

(2) Install the round 

fl

 ange (optional parts) to the fresh air intake.

Round duct

(3) Connect the duct to the round 

fl

 ange.

(4) Seal with a band and vinyl tape, etc. so that air does not leak from the connection.

Duct

4. PIPE INSTALLATION

 

CAUTION

  Be more careful that foreign matter (oil, water, etc.) does not enter the piping than with 

refrigerant R410A models. Also, when storing the piping, securely seal the openings 
by pinching, taping, etc.

  While welding the pipes, be sure to blow dry nitrogen gas through them.

4.1. Selecting the pipe material

 

CAUTION

  Do not use existing pipes from another refrigeration system or refrigerant.

  Use pipes that have clean external and internal sides without any contamination which 

may cause trouble during use, such as sulfur, oxide, dust, cutting waste, oil, or water.

  It is necessary to use seamless copper pipes.
  Material : Phosphor deoxidized seamless copper pipes
  It is desirable that the amount of residual oil is less than 40 mg/10 m.

  Do not use copper pipes that have a collapsed, deformed, or discolored portion 

(especially on the interior surface). Otherwise, the expansion valve or capillary tube 
may become blocked with contaminants.

  Improper pipe selection will degrade performance. As an air conditioner using R410A 

incurs pressure higher than when using conventional (R22) refrigerant, it is necessary 
to choose adequate materials.1

• 

Thicknesses of copper pipes used with R410A are as shown in the table.

• 

Never use copper pipes thinner than those indicated in the table even if they are 
available on the market.

Thicknesses of Annealed Copper Pipes (R410A)

Pipe outside diameter [mm (in.)]

Thickness [mm]

6.35 (1/4)

0.80

9.52 (3/8)

0.80

12.70 (1/2)

0.80

15.88 (5/8)

1.00

19.05 (3/4)

1.20

4.2. Pipe requirement

 

CAUTION

  Refer to the Installation Manual of the outdoor unit for description of the length of 

connecting pipe or for difference of its elevation.

•  Use pipe with water-resistant heat insulation.

 

CAUTION

  Install heat insulation around both the gas and liquid pipes. Failure to do so may 

cause water leaks.

  Use heat insulation with heat resistance above 120 °C. (Reverse cycle model only)
  In addition, if the humidity level at the installation location of the refrigerant piping is 

expected to exceed 70 %, install heat insulation around the refrigerant piping. If the 
expected humidity level is 70 to 80 %, use heat insulation that is 15 mm or thicker and 
if the expected humidity exceeds 80 %, use heat insulation that is 20 mm or thicker. 
If heat insulation is used that is not as thick as speci

fi

 ed, condensation may form on 

the surface of the insulation. In addition, use heat insulation with heat conductivity of 
0.045 W/(m·K) or less (at 20 °C).

4.3. Flare connection (pipe connection)

 

WARNING

  Tighten the flare nuts with a torque wrench using the specified tightening method. 

Otherwise, the 

fl

 are nuts could break after a prolonged period, causing refrigerant to 

leak and generate hazardous gas if the refrigerant comes into contact with a 

fl

 ame.

9373385141-01_IM.indb   Sec1:5

9373385141-01_IM.indb   Sec1:5

7/12/2012   11:16:10 AM

7/12/2012   11:16:10 AM

Содержание ARXA24GALH

Страница 1: ...ltyp Nur f r autorisiertes Fachpersonal MANUEL D INSTALLATION MANUAL DE INSTALACI N APPAREIL INT RIEUR type conduit UNIDAD INTERIOR Tipo conducto Pour le personnel agr uniquement nicamente para person...

Страница 2: ...e parts Always consult authorized service personnel to repairs When moving consult authorized service personnel for disconnection and installation of the unit 2 ABOUT THE UNIT 2 1 Precautions for usin...

Страница 3: ...indoor unit from ceiling Drain hose 1 For installing drain pipe VP25 O D 32 I D 25 Hose band 1 For installing drain hose Drain hose insulation 2 Insulates the drain hose and drain cap Wire 1 2 3 4 5...

Страница 4: ...sures so that they cannot reach the unit Decide the mounting position with the customer as follows 1 Install the indoor unit on a place having a sufficient strength so that it withstands against the w...

Страница 5: ...la tion WARNING When fastening the hangers make the bolt positions uniform The distance of is adjustable according to the place of the hanging bolts MAX 550 mm MIN 410 mm Slide the unit in the arrow d...

Страница 6: ...waste oil or water It is necessary to use seamless copper pipes Material Phosphor deoxidized seamless copper pipes It is desirable that the amount of residual oil is less than 40 mg 10 m Do not use c...

Страница 7: ...able below for the flare nut tightening torques CAUTION Be sure to install the pipe against the port on the indoor unit correctly If the centering is improper the flare nut cannot tighten smoothly If...

Страница 8: ...evenly until the gauge line and seal 3 Check the drainage 4 Install the heat insulation 5 Use the attached heat insulation to insulate the drain port and band parts of the body Ensure there is no spa...

Страница 9: ...earthing grounding may cause electric shock Do not connect power supply cables to the transmission or remote controller terminals as this will damage the product Never bundle the power supply cable an...

Страница 10: ...Terminal block Cable end Loop Cable end Loop Loop Screw with special washer Cable Cable WARNING When using solid core cables do not use the ring terminal If you use the solid core cables with the rin...

Страница 11: ...he PC board of the indoor unit may be damaged Remote controller cable DIP switch SW1 For 2 wire type For 3 wire type Connect the remote controller cable Y1 Non poler Y2 Non poler Y3 Do not connect 1 Y...

Страница 12: ...he current becomes DC10mA or less Select very low current use contacts usable at DC12V DC1mA or less b The polarity is for pin 1 and for pin 2 and 3 Connect correctly When connected to Apply voltage t...

Страница 13: ...03 or CNA04 OFF ON Thermostat off ON OFF Normal 2 External output A twisted pair cable 22AWG should be used Maximum length of cable is 25m Use an external input and output cable with appropriate exter...

Страница 14: ...ring arrangement Controller PCB Shield cable Cable tie Field supply Clamps Remove the existing connector and replace it with the remote sensor connector ensure that the correct connector is used The o...

Страница 15: ...tary switch Example 0 Rotary switch Example 0 Setting Setting range Type of switch Indoor unit address 0 to 63 Setting example 2 IU AD 10 IU AD 1 Refrigerant circuit address 0 to 99 Setting example 63...

Страница 16: ...tch SET 4 SW3 referring to the Table C DIP switch SET4 ON OFF SW 1 SW 2 SW 3 SW 4 Table C DIP switch SET 4 SW3 Cooling temperature setting range OFF Factory setting Standard 18 to 30 C ON Extension 18...

Страница 17: ...is complete be sure to check the following check items again CHECK ITEMS If not performed correctly CHECK BOX Has the indoor unit been installed correctly Vibration noise indoor unit may drop Has ther...

Страница 18: ...the remote controller 2 digit numbers are corresponding to the error code in the preceding table Touch the Next Page or previous page to switch to other indoor unit information UTY RNKY UTY RNKG UTY...

Отзывы: