background image

En-12

[In the case of “Pulse” input]

Connector

Input signal

Command

CNA01 or CNA02

Ch1

OFF 

 ON

Operation

Ch2

OFF 

 ON

Stop

*  The last command has priority.
*  The indoor units within the same remote controller group operates in the same mode.

 When function setting is “Emergency stop” mode.

[In the case of “Edge” input]

Connector

Input signal

Command

Ch1 of CNA01 or CNA02

OFF 

 ON

Emergency stop

ON 

 OFF

Normal

[In the case of “Pulse” input]

Connector

Input signal

Command

CNA01 or CNA02

Ch1

OFF 

 ON

Emergency stop

Ch2

OFF 

 ON

Normal

*  All indoor units of same refrigerant system stops when Emergency stop operates. 

 When function setting is “Forced stop” mode.

[In the case of “Edge” input]

Connector

Input signal

Command

Ch1 of CNA01 or CNA02

OFF 

 ON

Forced stop

ON 

 OFF

Normal

[In the case of “Pulse” input]

Connector

Input signal

Command

CNA01 or CNA02

Ch1

OFF 

 ON

Forced stop

Ch2

OFF 

 ON

Normal

*  When the forced stop is triggered, indoor unit stops and Operation/Stop operation by a 

remote controller is restricted.

*  When forced stop function is used with forming a remote controller group, connect the 

same equipment to each indoor unit within the group.

• Selection method of functions

“Operation/Stop” mode or “Emergency stop” mode, “Forced stop” mode can be selected 
with function setting of indoor unit.

 Forced thermostat off function

[“Edge” input only]

Connector

Input signal

Command

Ch3 of CNA03 or CNA04

OFF 

 ON

Thermostat off

ON 

 OFF

Normal

(2) External output

•  A twisted pair cable (22AWG) should be used. Maximum length of cable is 25m.
•  Use an external input and output cable with appropriate external dimension, depending 

on the number of cables to be installed.

•  Output voltage: Hi DC12V±2V, Lo 0V.
•  Permissible current: 50mA

Output select

 When indicator etc. are connected directly

Operation

indicator

Error

indicator

Indoor unit Fan

status indicator

connected unit

P.C.B

CNB

01

 When connecting with unit equipped with a power supply

CNB

01

P.C.B

Connected

device 1

Connected

device 2

Connected

device 3

connected unit

Relay (Field supply)

Operation behavior

Connector

Output voltage

Status

CNB01

External output1

Pins 1-2

0V

Stop

DC 12 V

Operation

External output2

Pins 1-3

0V

Normal

DC 12 V

Error

External output3 

Pins 1-4

0V

Indoor unit fan stop

DC 12 V

Indoor unit fan operation

(3) Connection methods

• Wire modi

fi

 cation

Remove insulation from wire attached to wire kit connector.
Remove insulation from 

fi

 eld supplied cable. Use crimp type insulated butt connector to 

join 

fi

 eld cable and wire kit wire.

Connect the wire with connecting wire with solder.

IMPORTANT:

 Be sure to insulate the connection between the wires.

Option parts 
External input/output wire

Solder and insulate the connected parts.

Field supply

• Connection terminals and wiring arrangement

In following 

fi

 gure, all the possible connectors are connected for description.

In actual installation, you cannot connect all the connectors at once.

Controller PCB

Clamps

Cable tie
(Field supply)

9373385141-01_IM.indb   Sec1:12

9373385141-01_IM.indb   Sec1:12

7/12/2012   11:16:16 AM

7/12/2012   11:16:16 AM

Содержание ARXA24GALH

Страница 1: ...ltyp Nur f r autorisiertes Fachpersonal MANUEL D INSTALLATION MANUAL DE INSTALACI N APPAREIL INT RIEUR type conduit UNIDAD INTERIOR Tipo conducto Pour le personnel agr uniquement nicamente para person...

Страница 2: ...e parts Always consult authorized service personnel to repairs When moving consult authorized service personnel for disconnection and installation of the unit 2 ABOUT THE UNIT 2 1 Precautions for usin...

Страница 3: ...indoor unit from ceiling Drain hose 1 For installing drain pipe VP25 O D 32 I D 25 Hose band 1 For installing drain hose Drain hose insulation 2 Insulates the drain hose and drain cap Wire 1 2 3 4 5...

Страница 4: ...sures so that they cannot reach the unit Decide the mounting position with the customer as follows 1 Install the indoor unit on a place having a sufficient strength so that it withstands against the w...

Страница 5: ...la tion WARNING When fastening the hangers make the bolt positions uniform The distance of is adjustable according to the place of the hanging bolts MAX 550 mm MIN 410 mm Slide the unit in the arrow d...

Страница 6: ...waste oil or water It is necessary to use seamless copper pipes Material Phosphor deoxidized seamless copper pipes It is desirable that the amount of residual oil is less than 40 mg 10 m Do not use c...

Страница 7: ...able below for the flare nut tightening torques CAUTION Be sure to install the pipe against the port on the indoor unit correctly If the centering is improper the flare nut cannot tighten smoothly If...

Страница 8: ...evenly until the gauge line and seal 3 Check the drainage 4 Install the heat insulation 5 Use the attached heat insulation to insulate the drain port and band parts of the body Ensure there is no spa...

Страница 9: ...earthing grounding may cause electric shock Do not connect power supply cables to the transmission or remote controller terminals as this will damage the product Never bundle the power supply cable an...

Страница 10: ...Terminal block Cable end Loop Cable end Loop Loop Screw with special washer Cable Cable WARNING When using solid core cables do not use the ring terminal If you use the solid core cables with the rin...

Страница 11: ...he PC board of the indoor unit may be damaged Remote controller cable DIP switch SW1 For 2 wire type For 3 wire type Connect the remote controller cable Y1 Non poler Y2 Non poler Y3 Do not connect 1 Y...

Страница 12: ...he current becomes DC10mA or less Select very low current use contacts usable at DC12V DC1mA or less b The polarity is for pin 1 and for pin 2 and 3 Connect correctly When connected to Apply voltage t...

Страница 13: ...03 or CNA04 OFF ON Thermostat off ON OFF Normal 2 External output A twisted pair cable 22AWG should be used Maximum length of cable is 25m Use an external input and output cable with appropriate exter...

Страница 14: ...ring arrangement Controller PCB Shield cable Cable tie Field supply Clamps Remove the existing connector and replace it with the remote sensor connector ensure that the correct connector is used The o...

Страница 15: ...tary switch Example 0 Rotary switch Example 0 Setting Setting range Type of switch Indoor unit address 0 to 63 Setting example 2 IU AD 10 IU AD 1 Refrigerant circuit address 0 to 99 Setting example 63...

Страница 16: ...tch SET 4 SW3 referring to the Table C DIP switch SET4 ON OFF SW 1 SW 2 SW 3 SW 4 Table C DIP switch SET 4 SW3 Cooling temperature setting range OFF Factory setting Standard 18 to 30 C ON Extension 18...

Страница 17: ...is complete be sure to check the following check items again CHECK ITEMS If not performed correctly CHECK BOX Has the indoor unit been installed correctly Vibration noise indoor unit may drop Has ther...

Страница 18: ...the remote controller 2 digit numbers are corresponding to the error code in the preceding table Touch the Next Page or previous page to switch to other indoor unit information UTY RNKY UTY RNKG UTY...

Отзывы: