En-3

3. INSTALLATION WORK

Correct initial installation location is important because it is dif

fi

 cult to move unit after it is 

installed.

3.1. Selecting an installation location

 

WARNING

  Select installation locations that can properly support the weight of the indoor. Install 

the units securely so that they do not topple or fall.

 

CAUTION

  Do not install the unit in the following areas:

• Area with high salt content, such as at the seaside. 
  It will deteriorate metal parts, causing the parts to fail or the unit to leak water.
• Area 

fi

 lled with mineral oil or containing a large amount of splashed oil or steam, such 

as a kitchen. 

  It will deteriorate plastic parts, causing the parts to fail or the unit to leak water.
• Area that generates substances that adversely affect the equipment, such as sulfuric 

gas, chlorine gas, acid, or alkali. 

  It will cause the copper pipes and brazed joints to corrode, which can cause 

refrigerant leakage.

• Area that can cause combustible gas to leak, contains suspended carbon 

fi

 bers  or 

fl

 ammable dust, or volatile in

fl

 ammables such as paint thinner or gasoline. 

  If gas leaks and settles around the unit, it can cause a 

fi

 re.

• Area where animals may urinate on the unit or ammonia may be generated.

  Do not use the unit for special purposes, such as storing food, raising animals, growing 

plants, or preserving precision devices or art objects. 

  It can degrade the quality of the preserved or stored objects.

  Do not install where there is the danger of combustible gas leakage.

  Do not install the unit near a source of heat, steam, or 

fl

 ammable gas.

  Install the unit where drainage does not cause any trouble.

  Install the indoor unit, power supply cable, transmission cable, and remote controller 

cable at least 1 m away from a television or radio receivers. The purpose of this is to 
prevent TV reception interference or radio noise.

  (Even if they are installed more than 1 m apart, you could still receive noise under 

some signal conditions.)

  If children under 10 years old may approach the unit, take preventive measures so that 

they cannot reach the unit.

• Decide the mounting position with the customer as follows:

(1)  Install the indoor unit on a place having a suf

fi

 cient strength so that it withstands 

against the weight of the indoor unit.

(2)  The inlet and outlet ports should not be obstructed; the air should be able to blow all 

over the room.

(3)  Leave the space required to service the air conditioner.
(4)  A place from where the air can be distributed evenly throughout the room by the unit.
(5)  Install the unit where connection to the outdoor unit (or RB unit) is easy.
(6)  Install the unit where the connection pipe can be easily installed.
(7)  Install the unit where the drain pipe can be easily installed.
(8)  Install the unit where noise and vibrations are not ampli

fi

 ed.

(9)  Take servicing, etc., into consideration and leave the spaces. Also install the unit 

where the 

fi

 lter can be removed.

(10) Providing as much space as possible between the indoor unit and the ceiling will 

make work much easier.

(11) If installing in a place where its humidity exceeds 80%, use heat insulation to 

prevent condensation.

3.2. Installation dimensions

• Provide the space around the unit as shown in the following 

fi

 gure.

 

400 mm or more

150 mm or more  *1

*

1 400 mm or more when drain from drain pipe.

• Provide a service hole for inspection purposes. 
• Do not place any wiring or illumination in the service space, as they will impede service.
• When an air 

fi

 lter is installed on the air inlet, provide enough service space to replace 

the 

fi

 lter.

Air

Air

Service hole

Control box

300 mm 
or more

500 mm

or more

500 mm 

or more

100 mm

Service space

Control box

300 mm
or more

1,550 mm or more

500 mm

 or more

100 mm

Intake panel

Air

Air

3.3. Installing the unit

 

WARNING

  Install the air conditioner in a location which can withstand a load of at least 5 times the 

weight of the main unit and which will not amplify sound or vibration. If the installation 
location is not strong enough, the indoor unit may fall and cause injuries.

  If the job is done with the panel frame only, there is a risk that the unit will come loose. 

Please take care.

3.3.1. Installing the hangers

Hanging bolt installation diagram.

 

(Top side)

(Right side)

270 mm

Air

Air

740 mm

477 mm

Air

Air

1,135 mm

1,177 mm

9373385141-01_IM.indb   Sec1:3

9373385141-01_IM.indb   Sec1:3

7/12/2012   11:16:08 AM

7/12/2012   11:16:08 AM

Содержание ARXA24GALH

Страница 1: ...ltyp Nur f r autorisiertes Fachpersonal MANUEL D INSTALLATION MANUAL DE INSTALACI N APPAREIL INT RIEUR type conduit UNIDAD INTERIOR Tipo conducto Pour le personnel agr uniquement nicamente para person...

Страница 2: ...e parts Always consult authorized service personnel to repairs When moving consult authorized service personnel for disconnection and installation of the unit 2 ABOUT THE UNIT 2 1 Precautions for usin...

Страница 3: ...indoor unit from ceiling Drain hose 1 For installing drain pipe VP25 O D 32 I D 25 Hose band 1 For installing drain hose Drain hose insulation 2 Insulates the drain hose and drain cap Wire 1 2 3 4 5...

Страница 4: ...sures so that they cannot reach the unit Decide the mounting position with the customer as follows 1 Install the indoor unit on a place having a sufficient strength so that it withstands against the w...

Страница 5: ...la tion WARNING When fastening the hangers make the bolt positions uniform The distance of is adjustable according to the place of the hanging bolts MAX 550 mm MIN 410 mm Slide the unit in the arrow d...

Страница 6: ...waste oil or water It is necessary to use seamless copper pipes Material Phosphor deoxidized seamless copper pipes It is desirable that the amount of residual oil is less than 40 mg 10 m Do not use c...

Страница 7: ...able below for the flare nut tightening torques CAUTION Be sure to install the pipe against the port on the indoor unit correctly If the centering is improper the flare nut cannot tighten smoothly If...

Страница 8: ...evenly until the gauge line and seal 3 Check the drainage 4 Install the heat insulation 5 Use the attached heat insulation to insulate the drain port and band parts of the body Ensure there is no spa...

Страница 9: ...earthing grounding may cause electric shock Do not connect power supply cables to the transmission or remote controller terminals as this will damage the product Never bundle the power supply cable an...

Страница 10: ...Terminal block Cable end Loop Cable end Loop Loop Screw with special washer Cable Cable WARNING When using solid core cables do not use the ring terminal If you use the solid core cables with the rin...

Страница 11: ...he PC board of the indoor unit may be damaged Remote controller cable DIP switch SW1 For 2 wire type For 3 wire type Connect the remote controller cable Y1 Non poler Y2 Non poler Y3 Do not connect 1 Y...

Страница 12: ...he current becomes DC10mA or less Select very low current use contacts usable at DC12V DC1mA or less b The polarity is for pin 1 and for pin 2 and 3 Connect correctly When connected to Apply voltage t...

Страница 13: ...03 or CNA04 OFF ON Thermostat off ON OFF Normal 2 External output A twisted pair cable 22AWG should be used Maximum length of cable is 25m Use an external input and output cable with appropriate exter...

Страница 14: ...ring arrangement Controller PCB Shield cable Cable tie Field supply Clamps Remove the existing connector and replace it with the remote sensor connector ensure that the correct connector is used The o...

Страница 15: ...tary switch Example 0 Rotary switch Example 0 Setting Setting range Type of switch Indoor unit address 0 to 63 Setting example 2 IU AD 10 IU AD 1 Refrigerant circuit address 0 to 99 Setting example 63...

Страница 16: ...tch SET 4 SW3 referring to the Table C DIP switch SET4 ON OFF SW 1 SW 2 SW 3 SW 4 Table C DIP switch SET 4 SW3 Cooling temperature setting range OFF Factory setting Standard 18 to 30 C ON Extension 18...

Страница 17: ...is complete be sure to check the following check items again CHECK ITEMS If not performed correctly CHECK BOX Has the indoor unit been installed correctly Vibration noise indoor unit may drop Has ther...

Страница 18: ...the remote controller 2 digit numbers are corresponding to the error code in the preceding table Touch the Next Page or previous page to switch to other indoor unit information UTY RNKY UTY RNKG UTY...

Отзывы: