background image

En-8

5. 4.  Pipe connection

 

CAUTION

Do not use mineral oil on a 

fl

 ared part. Prevent mineral oil from getting into the system 

as this would reduce the lifetime of the units.

While brazing the pipes, be sure to blow dry nitrogen gas through them.

5. 4. 1.  Flaring

•  Use special pipe cutter and 

fl

 are tool exclusive for R410A.

(1)  Cut the connection pipe to the necessary length with a pipe cutter.
(2)  Hold the pipe downward so that the cuttings will not enter the pipe and remove any 

burrs.

(3) Insert the 

fl

 are nut (always use the 

fl

 are nut attached to the indoor and outdoor 

units respectively) onto the pipe and perform the 

fl

 are processing with a 

fl

 are tool. 

Leakage of refrigerant may result if other 

fl

 are nuts are used.

(4)  Protect the pipes by pinching them or with tape to prevent dust, dirt, or water from 

entering the pipes.

L

Check if [L] is 

fl

 ared uniformly 

and is not cracked or scratched.

Pipe

A

B

Die

Pipe outside 

diameter [mm (in.)]

Dimension A (mm)

Dimension B   0

- 0.4

[mm]

Flare tool for R410A, 

clutch type

6.35 (1/4)

0 to 0.5 

9.1

9.52 (3/8)

13.2

12.70 (1/2)

16.6

15.88 (5/8)

19.7

19.05 (3/4)

24.0

• When 

using 

conventional 

fl

 are tools to 

fl

 are R410A pipes, the dimension A should 

be approximately 0.5mm more than indicated in the table (for 

fl

 aring with R410A 

fl

 are tools) to achieve the speci

fi

 ed 

fl

 aring. Use a thickness gauge to measure the 

dimension A.

Pipe outside 

diameter 

[mm (in.)]

Width across 

fl

 ats 

of Flare nut 

[mm]

6.35 (1/4)

17

9.52 (3/8)

22

12.70 (1/2)

26

15.88 (5/8)

29

19.05 (3/4)

36

Width across 

fl

 ats

5. 4. 2.  Bending pipes

 

CAUTION

To prevent breaking of the pipe, avoid sharp bends. Bend the pipe with a radius of 
curvature of 100mm or more.

If the pipe is bent repeatedly at the same place, it will break.

•  If pipes are shaped by hand, be careful not to collapse them.
•  Do not bend the pipes at an angle of more than 90°.
•  When pipes are repeatedly bent or stretched, the material will harden, making it dif-

fi

 cult to bend or stretch them any more.

•  Do not bend or stretch the pipes more than 3 times.

5. 4. 3.  Pipe connection

 

CAUTION

Be sure to install the pipe against the port on the indoor unit and the outdoor unit cor-
rectly. If the centering is improper, the 

fl

 are nut cannot be tightened smoothly. 

If the 

fl

 are nut is forced to turn, the threads will be damaged.

Do not remove the 

fl

 are nut from the outdoor unit pipe until immediately before connect-

ing the connection pipe.

After installing the piping, make sure that the connection pipes do not touch the 
compressor or outer panel. If the pipes touch the compressor or outer panel, they will 
vibrate and produce noise.

(1)   Detach the caps and plugs from the pipes. 
(2)   Center the pipe against the port on the outdoor unit, and then turn the 

fl

 are nut by hand.

(3)   Tighten the 

fl

 are nut of the connection pipe at the outdoor unit valve connector.

(4)   After tightening the 

fl

 are nut by hand, use a torque wrench to fully tighten it.

3-way valve (Liquid)

3-way valve 
(Gas)

Connection pipe 
(Liquid)

Flare nut

Connection 
pipe (Gas)

Flare nut

 

CAUTION

Hold the torque wrench at its grip, keeping it in a right angle with the pipe, in order to 
tighten the 

fl

 are nut correctly.

•  Outer panel may be distorted if fastened only with a wrench. Be sure to 

fi

 x the el-

ementary part with a holding wrench (spanner) and fasten with a torque wrench (refer 
to below diagram). Do not apply force to the blank cap of the valve or hang a wrench, 
etc., on the cap. If blank cap is broken, it may cause leakage of refrigerant.

Blank cap

Flare nut

90°

Torque wrench

Holding 
wrench

Torque wrench

Flare nut 

[mm (in.)]

Tightening torque 

[N·m (kgf·cm)]

6.35 (1/4) dia.

16 to 18 (160 to 180)

9.52 (3/8) dia.

32 to 42 (320 to 420)

12.70 (1/2) dia.

49 to 61 (490 to 610)

15.88 (5/8) dia.

63 to 75 (630 to 750)

19.05 (3/4) dia.

90 to 110 (900 to 1100)

5. 4. 4.  Handling precautions for the valves

• Mounted 

part 

of 

Blank 

cap 

is sealed for protection.

• Fasten 

blank 

cap 

tightly 

after 

opening 

valves.

Operating the valves

• Use 

hexagon 

wrench 

(size 

4mm).

• Opening  (1) Insert 

the 

hexagon 

wrench into the valve shaft, and turn it 

  

counterclockwise.

 

(2)  Stop turning when the valve shaft can no longer be turned. 

  

(Open 

position)

• Closing  (1) Insert 

the 

hexagon 

wrench into the valve shaft, and turn it 

  

clockwise.

 

(2)  Stop turning when the valve shaft can no longer be turned. 

  

(Closed 

position)

Opening direction

Hexagon wrench

Seal (blank cap 
installation portion)

Liquid pipe

Gas pipe

Opening direction

9380545057_IM.indb   8

9380545057_IM.indb   8

2014/9/15   11:27:04

2014/9/15   11:27:04

Содержание AJY040LCLAH

Страница 1: ...AL For authorized service personnel only INSTALLATIONSANLEITUNG Nur f r autorisiertes Fachpersonal MANUEL D INSTALLATION MANUAL DE INSTALACI N Pour le personnel agr uniquement nicamente para personal...

Страница 2: ...y performed electrical work can cause serious accidents such as electric shock or fire For wiring use the prescribed type of cables connect them securely making sure that there are no external forces...

Страница 3: ...one ground cable Improper grounding may cause electric shock Perform draining for the unit according to the Installation manual Check that the water is properly drained If the drain processing is impr...

Страница 4: ...this is to prevent TV reception interference or radio noise Even if they are installed more than 1 meter apart you could still receive noise under some signal conditions Keep the length of the piping...

Страница 5: ...ace as shown in the following example when an obstruction is present also in the upward area When the upward area is open Unit mm 1 Obstacles at rear only 300 2 Obstacles at front only 1500 or more 3...

Страница 6: ...s in the figure To reduce vibration do not install the unit directly on the ground Install it on a secure base such as concrete blocks The foundation shall support the legs of the unit and have a widt...

Страница 7: ...e model Model code of indoor unit Capacity kW 04 1 1 07 2 2 09 2 8 12 3 6 14 4 5 18 5 6 24 7 1 30 9 0 34 10 0 36 11 2 45 12 5 54 14 0 In the case of ARXD07GALH equivalent to model code of indoor unit...

Страница 8: ...Front connection Bottom connection Lateral connection Rear connection 5 2 Indoor unit pipe connections CAUTION For details refer to the Installation Instruction Sheet of each part Separation tube A B...

Страница 9: ...indoor unit and the outdoor unit cor rectly If the centering is improper the flare nut cannot be tightened smoothly If the flare nut is forced to turn the threads will be damaged Do not remove the fl...

Страница 10: ...to dust or water CAUTION The primary power supply capacity is for the air conditioner itself and does not include the concurrent use of other devices Do not use crossover power supply wiring for the...

Страница 11: ...rror Pay attention to the following points while attaching wires on the terminal board Do not attach 2 wires on one side Do not twist wires Do not cross the wires Do not shorted at edge at root PROHIB...

Страница 12: ...a screwdriver that is too small otherwise the screw heads may be damaged and prevent the screws from being properly tightened 5 Do not tighten the terminal screws too much otherwise the screws may bre...

Страница 13: ...onnected unit connected unit connected unit connected unit connected unit Input1 CN131 Yellow Input2 CN132 Green Input3 CN133 White Input4 CN134 Red Input5 CN135 Orange P C B Operation behavior Each i...

Страница 14: ...output signal for base heater Output signal ON when the outdoor tempera ture goes down below 2 C and signal OFF at the outdoor temperature 4 C 1 2 3 4 Voltage power supply input voltage cable 0 82mm2...

Страница 15: ...0 0 Factory setting 11 Cooling capacity shift Normal mode 1 1 0 0 Save energy mode 0 1 High power mode 1 0 2 High power mode 2 0 3 Forbidden 0 4 Set this item when necessary 12 Heating capacity shift...

Страница 16: ...ter pulse setting 2 Setting number 00xx 7 3 0 0 Setting number 01xx 0 1 Setting number 98xx 9 8 Setting number 99xx 9 9 Set the hundreds digit and thousands digit of the electricity meter pulse settin...

Страница 17: ...address setting Address must be set for the indoor unit Manual setting When setting with the switch inside the indoor unit refer to the indoor unit operating manual When setting with a remote control...

Страница 18: ...the pressure of nitrogen gas before blazing After completing the sealing test release the nitrogen gas from both valves Release the nitrogen gas slowly It may take about 10 minutes for completing the...

Страница 19: ...Set the cylinder vertical and fill with the liquid Liquid can be filled without turning bot tom up with the siphon inside Liquid Gas R410A Filling method for other cylinders Turn bottom up and fill wi...

Страница 20: ...ry indoor units 3 Are the cables connected to the terminals without loose ness and in accordance with the specifications 4 Are all the indoor units stopped Indoor unit connection check can not be perf...

Страница 21: ...d to test operation the unit If there are problems adjust immediately and recheck 9 3 Test run method Be sure to configure test run settings only when the outdoor unit has stopped operating Depending...

Страница 22: ...error E 7 4 1 Outside air temp thermistor error E 7 5 1 Outdoor unit suction gas temp thermistor error E 7 7 1 Outdoor unit heat sink temp thermistor error E 8 4 1 Outdoor unit current sensor 1 error...

Страница 23: ...ition is max cooling condition refer to item 16 9 Air circulation Air circulation 10 Noise level Noise level 11 Refrigerant Refrigerant type and initial charging amount 12 Max pressure HP LP Means pre...

Отзывы: