En-6

4. 2.  Pipe selection

CAUTION

This unit is designed speci

fi

 cally for use with the R410A refrigerant.

Pipes for R407C or R22 may not be used with this unit.

Do not use existing pipes.

Improper pipe selection will degrade performance.

First separation 

tube (optional)

Separation tube 

(optional)

Pipe size 

(table B)

Pipe size 

(table C)

Pipe size 

(table D)

Indoor 

unit

Indoor 

unit

Indoor 

unit

Indoor 

unit

Indoor 

unit

Indoor 

unit

Table. A  (Wall  thickness  and  pipe  material  for  each  diameter)

Outside Diameter

mm
(in.)

6.35

(1/4)

9.52

(3/8)

12.70

(1/2)

15.88

(5/8)

Wall Thickness

*2

mm
(in.)

0.8

(0.032)

0.8

(0.032)

0.8

(0.032)

1.0

(0.039)

Material

COPPER

*1

 

JIS H3300 C1220T-O or equivalent

Please select the pipe size in accordance with local rules.
*1. Allowable tensile stress 

 33 (N/mm

2

)

*2.  Endurance pressure of the pipes 4.2MPa

Table. B    (Diameter of piping used between outdoor unit and 

fi

 rst separation 

tubes or headers)

Diameter of piping [mm(in.)]

Liquid pipe

Gas pipe

9.52

(3/8)

15.88

(5/8)

Table. C    (Diameter of piping used between separation tubes)

Outside diameter [mm(in.)]

Separation tube *3

Header *3

Liquid pipe

Gas pipe

9.52

(3/8)

15.88

(5/8)

UTP-AX054A

UTR-H0906L
UTR-H0908L

*3.  For the installation method, please refer to the installation manuals for indoor 

unit, separation tubes or headers. 

Use a standard separation tube for pipe branching. Do not use a T tube as it does not 
separate the refrigerant evenly.

Table. D    (Diameter  of  piping  used  between separation tube and indoor unit)

Model code of 

indoor unit 

Outside diameter [mm(in.)]

Liquid pipe

Gas pipe

04 to 14

6.35 (1/4)

12.70 (1/2)

18 to 34

9.52 (3/8)

15.88 (5/8)

36 to 54

9.52 (3/8)

19.05 (3/4)

Table. E     (Indoor unit capacity comparison table - The indication of power is dif-

ferent depending on the model.)

Model code of indoor unit

Capacity [kW]

04

1.1

07

2.2

09

2.8

12

3.6

14

4.5

18

5.6

24

7.1

30

9.0

34

10.0

36

11.2

45

12.5

54

14.0

In the case of ARXD07GALH: equivalent to model code of indoor unit

 Model 

code 

07 

 Capacity = 2.2kW

If indoor unit whose cooling capacity is 1.1 kW is connected, calculate the value according 
to the following restrictions.
Maximum cooling capacity of connectable indoor unit

1.1 kW cooling capacity 

indoor unit is NOT 

connected

1.1 kW cooling capacity indoor unit is connected

9.0 kW or larger cool-

ing capacity AU or AR 

is NOT connected

9.0 kW or larger cooling capacity 

AU or AR is connected 

130%

117%

110%

4. 3.  Protection of pipes

Location

Working period

Protection method

Outdoor

1 month or more

Pinch pipes

Less than 1 month

Pinch or tape pipes

Indoor

Pinch or tape pipes

•  Protect the pipes to prevent the entry of moisture and dust.
•  Especially pay attention when passing the pipes through a hole or connecting the end 

of a pipe to the outdoor unit.

5. PIPE INSTALLATION

5. 1.  Brazing

CAUTION

If air or another type of refrigerant 
enters the refrigeration cycle, the 
internal pressure in the refrigera-
tion cycle will become abnormally 
high and prevent the unit from 
exerting its full performance.

Pressure regulating valve

Cap

Fig.

Nitrogen gas

Brazing area

Apply nitrogen gas while brazing the pipes.
Nitrogen gas pressure: 0.02 MPa (= pressure felt suf

fi

 ciently on the back of your 

hand)

If a pipe is brazed without applying nitrogen gas, it will create an oxidation 

fi

 lm.

This can degrade performance or damage the parts in the unit (such as the compres-
sor or valves).

Do not use 

fl

 ux to braze pipes. If the 

fl

 ux is the chlorine type, it will cause the pipes to 

corrode.
In addition, if the 

fl

 ux contains 

fl

 uoride, it will affect the refrigerant piping system due to 

deterioration of refrigerant oil.

For brazing material, use phosphor copper that does not require 

fl

 ux.

9380545057_IM.indb   6

9380545057_IM.indb   6

2014/9/15   11:27:03

2014/9/15   11:27:03

Содержание AJY040LCLAH

Страница 1: ...AL For authorized service personnel only INSTALLATIONSANLEITUNG Nur f r autorisiertes Fachpersonal MANUEL D INSTALLATION MANUAL DE INSTALACI N Pour le personnel agr uniquement nicamente para personal...

Страница 2: ...y performed electrical work can cause serious accidents such as electric shock or fire For wiring use the prescribed type of cables connect them securely making sure that there are no external forces...

Страница 3: ...one ground cable Improper grounding may cause electric shock Perform draining for the unit according to the Installation manual Check that the water is properly drained If the drain processing is impr...

Страница 4: ...this is to prevent TV reception interference or radio noise Even if they are installed more than 1 meter apart you could still receive noise under some signal conditions Keep the length of the piping...

Страница 5: ...ace as shown in the following example when an obstruction is present also in the upward area When the upward area is open Unit mm 1 Obstacles at rear only 300 2 Obstacles at front only 1500 or more 3...

Страница 6: ...s in the figure To reduce vibration do not install the unit directly on the ground Install it on a secure base such as concrete blocks The foundation shall support the legs of the unit and have a widt...

Страница 7: ...e model Model code of indoor unit Capacity kW 04 1 1 07 2 2 09 2 8 12 3 6 14 4 5 18 5 6 24 7 1 30 9 0 34 10 0 36 11 2 45 12 5 54 14 0 In the case of ARXD07GALH equivalent to model code of indoor unit...

Страница 8: ...Front connection Bottom connection Lateral connection Rear connection 5 2 Indoor unit pipe connections CAUTION For details refer to the Installation Instruction Sheet of each part Separation tube A B...

Страница 9: ...indoor unit and the outdoor unit cor rectly If the centering is improper the flare nut cannot be tightened smoothly If the flare nut is forced to turn the threads will be damaged Do not remove the fl...

Страница 10: ...to dust or water CAUTION The primary power supply capacity is for the air conditioner itself and does not include the concurrent use of other devices Do not use crossover power supply wiring for the...

Страница 11: ...rror Pay attention to the following points while attaching wires on the terminal board Do not attach 2 wires on one side Do not twist wires Do not cross the wires Do not shorted at edge at root PROHIB...

Страница 12: ...a screwdriver that is too small otherwise the screw heads may be damaged and prevent the screws from being properly tightened 5 Do not tighten the terminal screws too much otherwise the screws may bre...

Страница 13: ...onnected unit connected unit connected unit connected unit connected unit Input1 CN131 Yellow Input2 CN132 Green Input3 CN133 White Input4 CN134 Red Input5 CN135 Orange P C B Operation behavior Each i...

Страница 14: ...output signal for base heater Output signal ON when the outdoor tempera ture goes down below 2 C and signal OFF at the outdoor temperature 4 C 1 2 3 4 Voltage power supply input voltage cable 0 82mm2...

Страница 15: ...0 0 Factory setting 11 Cooling capacity shift Normal mode 1 1 0 0 Save energy mode 0 1 High power mode 1 0 2 High power mode 2 0 3 Forbidden 0 4 Set this item when necessary 12 Heating capacity shift...

Страница 16: ...ter pulse setting 2 Setting number 00xx 7 3 0 0 Setting number 01xx 0 1 Setting number 98xx 9 8 Setting number 99xx 9 9 Set the hundreds digit and thousands digit of the electricity meter pulse settin...

Страница 17: ...address setting Address must be set for the indoor unit Manual setting When setting with the switch inside the indoor unit refer to the indoor unit operating manual When setting with a remote control...

Страница 18: ...the pressure of nitrogen gas before blazing After completing the sealing test release the nitrogen gas from both valves Release the nitrogen gas slowly It may take about 10 minutes for completing the...

Страница 19: ...Set the cylinder vertical and fill with the liquid Liquid can be filled without turning bot tom up with the siphon inside Liquid Gas R410A Filling method for other cylinders Turn bottom up and fill wi...

Страница 20: ...ry indoor units 3 Are the cables connected to the terminals without loose ness and in accordance with the specifications 4 Are all the indoor units stopped Indoor unit connection check can not be perf...

Страница 21: ...d to test operation the unit If there are problems adjust immediately and recheck 9 3 Test run method Be sure to configure test run settings only when the outdoor unit has stopped operating Depending...

Страница 22: ...error E 7 4 1 Outside air temp thermistor error E 7 5 1 Outdoor unit suction gas temp thermistor error E 7 7 1 Outdoor unit heat sink temp thermistor error E 8 4 1 Outdoor unit current sensor 1 error...

Страница 23: ...ition is max cooling condition refer to item 16 9 Air circulation Air circulation 10 Noise level Noise level 11 Refrigerant Refrigerant type and initial charging amount 12 Max pressure HP LP Means pre...

Отзывы: