background image

En-12

Be sure to use one side of a twisted-pair cable when using transmission cable with 2 sets 
of twisted-pair cables.

Wind with insulation tape to prevent short circuit

Use one side of the 
twisted-pair cable

Connect both ends of sealed cable to earth.

6. 6.  External input and external output

6. 6. 1.  Terminal position

Base heater
(CN115:Black)

Outdoor unit 
PC board

Input 4
(CN134:Red)

Input 3
(CN133:White)

Input 2
(CN132:Green)

Input 1
(CN131:Yellow)

BASE HEATER

CN115 (BLK)

Input 5

(CN135 : 

Orange)

PULSE 
IN

CN134

CN133

CN132

CN1

35

CN1

36

CN1

37

CN131

EXT.
OUT. 1

EXT.
IN. 4

EXT.
IN. 3

EXT.
IN. 2

EXT.
IN. 1

EXT.
OUT. 2

(ORG)

(RED)

(WHT)

(GRN)

(YEL)

(BLK)

(BLU)

Output 1 
(CN136 : 
Black)

Output 2

(CN137: 
Blue)

CAUTION

Do not bundle the cable for base heater with other cables.

When connecting cable to Input2

Cable (for external input and output)

Cable tie (tightened with transmission cable)

Cable (for external input and output)

* If the outdoor unit is not installed in the wall, cover the exposed part of cable 

with a 1 mm thick or more insulation tubing.

6. 6. 2.  External input terminal

•  Setting to low noise mode, cooling priority/heating priority selection, outdoor unit 

operation peak control setting, emergency/batch stop and electricity meter pulse are 
possible from the outside.

Wiring method and speci

fi

 cations

* A 

twisted 

pair 

cable 

(0.33mm

2

 (22AWG)) should be used. Maximum length of cable is 

150m.

*  

Use an external input and output cable with appropriate external dimension, depend-
ing on the number of cables to be installed

*  For each input, pin No.1 is of positive polarity and pin No.2 is of ground level.

connected unit connected unit connected unit

connected unit connected unit

Input1

CN131 

(Yellow)

Input2

CN132 

(Green)

Input3

CN133 

(White)

Input4

CN134 

(Red)

Input5

CN135 

(Orange)

P.C.B

Operation behavior

Each input terminal works as follows.

Connector

Input signal

Status

Input1
CN131 (Yellow)

OFF

Normal operation

ON

Low noise mode operation

Input2
CN132 (Green) *1

OFF

Cooling priority

ON

Heating priority

Input3
CN133 (White)

OFF

Normal operation

ON

Outdoor unit operation peak control

Input4
CN134 (Red)

OFF

Normal operation

ON

Batch stop or Emergency stop operation *2, *3

Input5
CN135 (Orange) *4

No pulse

No information from electricity meter

Pulse

Power usage information from electricity meter

The operations of each input terminal and the selection of function are set with the push button  
on the PC board of outdoor unit. About the setting, please refer to 7.4. Push button setting.

Note: 
*1:  The “external input priority mode” must be set by pressing push button on PC 

board of outdoor unit. (Refer to “7.FIELD SETTING”.)

*2:  Batch stop or Emergency stop pattern can be selected by outdoor unit PC board 

push button. (Refer to “7.FIELD SETTING”.)

*3:  The emergency stop function mounted in the J-II does not guarantee the regulations 

of each country. For this reason, suf

fi

cient checking is necessary regarding use. 

Especially, since the fact that the equipment may not be emergency-stopped in the 
case of breaking of the wiring to the external input terminals and communication 
line, communication error due to noise, VRF external input circuit trouble, etc. must 
be considered, the provision of double measures that add direct interruption of the 
power supply by switch, etc. is recommended as a precaution.

*4:  Pulse input to CN135 must be width 50ms or more, and must be interval 50ms or more.

9380545057_IM.indb   12

9380545057_IM.indb   12

2014/9/15   11:27:05

2014/9/15   11:27:05

Содержание AJY040LCLAH

Страница 1: ...AL For authorized service personnel only INSTALLATIONSANLEITUNG Nur f r autorisiertes Fachpersonal MANUEL D INSTALLATION MANUAL DE INSTALACI N Pour le personnel agr uniquement nicamente para personal...

Страница 2: ...y performed electrical work can cause serious accidents such as electric shock or fire For wiring use the prescribed type of cables connect them securely making sure that there are no external forces...

Страница 3: ...one ground cable Improper grounding may cause electric shock Perform draining for the unit according to the Installation manual Check that the water is properly drained If the drain processing is impr...

Страница 4: ...this is to prevent TV reception interference or radio noise Even if they are installed more than 1 meter apart you could still receive noise under some signal conditions Keep the length of the piping...

Страница 5: ...ace as shown in the following example when an obstruction is present also in the upward area When the upward area is open Unit mm 1 Obstacles at rear only 300 2 Obstacles at front only 1500 or more 3...

Страница 6: ...s in the figure To reduce vibration do not install the unit directly on the ground Install it on a secure base such as concrete blocks The foundation shall support the legs of the unit and have a widt...

Страница 7: ...e model Model code of indoor unit Capacity kW 04 1 1 07 2 2 09 2 8 12 3 6 14 4 5 18 5 6 24 7 1 30 9 0 34 10 0 36 11 2 45 12 5 54 14 0 In the case of ARXD07GALH equivalent to model code of indoor unit...

Страница 8: ...Front connection Bottom connection Lateral connection Rear connection 5 2 Indoor unit pipe connections CAUTION For details refer to the Installation Instruction Sheet of each part Separation tube A B...

Страница 9: ...indoor unit and the outdoor unit cor rectly If the centering is improper the flare nut cannot be tightened smoothly If the flare nut is forced to turn the threads will be damaged Do not remove the fl...

Страница 10: ...to dust or water CAUTION The primary power supply capacity is for the air conditioner itself and does not include the concurrent use of other devices Do not use crossover power supply wiring for the...

Страница 11: ...rror Pay attention to the following points while attaching wires on the terminal board Do not attach 2 wires on one side Do not twist wires Do not cross the wires Do not shorted at edge at root PROHIB...

Страница 12: ...a screwdriver that is too small otherwise the screw heads may be damaged and prevent the screws from being properly tightened 5 Do not tighten the terminal screws too much otherwise the screws may bre...

Страница 13: ...onnected unit connected unit connected unit connected unit connected unit Input1 CN131 Yellow Input2 CN132 Green Input3 CN133 White Input4 CN134 Red Input5 CN135 Orange P C B Operation behavior Each i...

Страница 14: ...output signal for base heater Output signal ON when the outdoor tempera ture goes down below 2 C and signal OFF at the outdoor temperature 4 C 1 2 3 4 Voltage power supply input voltage cable 0 82mm2...

Страница 15: ...0 0 Factory setting 11 Cooling capacity shift Normal mode 1 1 0 0 Save energy mode 0 1 High power mode 1 0 2 High power mode 2 0 3 Forbidden 0 4 Set this item when necessary 12 Heating capacity shift...

Страница 16: ...ter pulse setting 2 Setting number 00xx 7 3 0 0 Setting number 01xx 0 1 Setting number 98xx 9 8 Setting number 99xx 9 9 Set the hundreds digit and thousands digit of the electricity meter pulse settin...

Страница 17: ...address setting Address must be set for the indoor unit Manual setting When setting with the switch inside the indoor unit refer to the indoor unit operating manual When setting with a remote control...

Страница 18: ...the pressure of nitrogen gas before blazing After completing the sealing test release the nitrogen gas from both valves Release the nitrogen gas slowly It may take about 10 minutes for completing the...

Страница 19: ...Set the cylinder vertical and fill with the liquid Liquid can be filled without turning bot tom up with the siphon inside Liquid Gas R410A Filling method for other cylinders Turn bottom up and fill wi...

Страница 20: ...ry indoor units 3 Are the cables connected to the terminals without loose ness and in accordance with the specifications 4 Are all the indoor units stopped Indoor unit connection check can not be perf...

Страница 21: ...d to test operation the unit If there are problems adjust immediately and recheck 9 3 Test run method Be sure to configure test run settings only when the outdoor unit has stopped operating Depending...

Страница 22: ...error E 7 4 1 Outside air temp thermistor error E 7 5 1 Outdoor unit suction gas temp thermistor error E 7 7 1 Outdoor unit heat sink temp thermistor error E 8 4 1 Outdoor unit current sensor 1 error...

Страница 23: ...ition is max cooling condition refer to item 16 9 Air circulation Air circulation 10 Noise level Noise level 11 Refrigerant Refrigerant type and initial charging amount 12 Max pressure HP LP Means pre...

Отзывы: