10. LED Status

You can determine the operating status by the lighting up and blinking of the LED dis-
play.
Check the status using the table below.

10. 1.  Normal operation mode

Mode

CODE

DESCRIPTION

Operation

C L

Cooling

H

t

Heating

o

r During oil recovery operation

d F During defrosting operation

P C During power saving operation

L n During low noise operation

10. 2.  Error codes

Mode

CODE

DESCRIPTION

Communication 
error

E

1

4.

2

Outdoor unit network communication 2 error

E

1

4.

5

The number of indoor unit shortage

Function setting 
error

E

2

2.

1

Indoor  unit  capacity  error

E

2

4.

2

Connection unit number error (Indoor unit)

E

2

6.

1

Indoor unit duplicate address error

E

2

8.

1

Auto address setting error

E

2

8.

4

Signal ampli

fi

 er auto address error

Indoor unit 
actuator error

E

5

U.

1

Indoor unit miscellaneous error

Outdoor unit 
PCB/Electrical 
component/ 
Switch error

E

6

2.

3

Outdoor unit EEPROM access error

E

6

2.

6

Outdoor unit inverters communication error

E

6

2.

8

Outdoor unit EEPROM data corruption error

E

6

3.

1

Outdoor unit inverter error

E

6

7.

2

Outdoor unit inverter PCB power short interrup-
tion error

E

6

8.

2

Outdoor unit rush current limiting resister temp. 
rise error (protective operation)

E

6

9.

1

Outdoor unit transmission PCB parallel com-
munication error

Outdoor unit 
sensor error

E

7

1.

1

Outdoor unit discharge temp. thermistor 1 error

E

7

2.

1

Outdoor unit compressor temp. thermistor 1 error

E

7

3.

3

Outdoor unit heat ex. liquid temp. thermistor error

E

7

4.

1

Outside air temp. thermistor error

E

7

5.

1

Outdoor unit suction gas temp. thermistor error

E

7

7.

1

Outdoor unit heat sink temp. thermistor error

E

8

4.

1

Outdoor unit current sensor 1 error 
(permanent stop)

E

8

6.

1

Outdoor unit discharge pressure sensor error

E

8

6.

3

Outdoor unit suction pressure sensor error

Outdoor unit 
actuator error

E

9

3.

1

Outdoor unit inverter compressor start up error

E

9

4.

1

Outdoor unit trip detection

E

9

5.

5

Outdoor unit compressor motor loss of synchro-
nization

E

9

7.

1

Outdoor unit fan motor 1 lock error

E

9

7.

4

Outdoor unit fan motor 1 undervoltage error

E

9

7.

5

Outdoor unit fan motor 1 temperature error 
(protective action)

E

9

A.

1

Outdoor unit coil 1 (expansion valve 1) error

Refrigerant 
system error

E

A

1.

1

Outdoor unit discharge temperature 1 error 
(permanent stop)

E

A

3.

1

Outdoor unit compressor 1 temperature error

E

A

4.

1

Outdoor unit high pressure error

E

A

5.

1

Outdoor unit low pressure error

E

A

C.

4

Outdoor unit heat sink temperature error

㪣㪜㪛㩷㫃㪸㫄㫇㩷㪑

㪣㪑

㪟㪑

㪡㪑

㪍㪑

㫅㪑

㫆㪑

㫉㪑

㫋㪑

㪬㪑

㪐㪑

㪏㪑

㪧㪑

㪻㪑

㪪㪑

㪘㪑

㪝㪑

㪚㪑

㪜㪑

㪇㪑

㪌㪑

㪊㪑

㪈㪑

㪉㪑

㪎㪑

㪋㪑

9. 4.  Checklist

Check description

Check method

Criteria

1

High and low pressure values 
are normal.

Check it with a pres-
sure gauge.

Cooling: low pressure 
approx. 0.8 MPa
Heating: high pressure 
approx. 3.0 MPa

2

Drain water is discharged 
smoothly through the drain 
hose.

Check it by pouring 
water.

3

Indoor and outdoor unit fans 
are operating.

Check them visually.

4

Compressor operates after 
the indoor unit operates.

Check the operating 
sound.

5

Difference between inlet and 
outlet temperatures is normal.

Measure the inlet and 
outlet temperatures.

Temperature difference 
10 degrees

6

Error is not displayed

Check the 7 segment 
display

Error blinking or no error 
code display

9380545057_IM.indb   21

9380545057_IM.indb   21

2014/9/15   11:27:07

2014/9/15   11:27:07

Содержание AJY040LCLAH

Страница 1: ...AL For authorized service personnel only INSTALLATIONSANLEITUNG Nur f r autorisiertes Fachpersonal MANUEL D INSTALLATION MANUAL DE INSTALACI N Pour le personnel agr uniquement nicamente para personal...

Страница 2: ...y performed electrical work can cause serious accidents such as electric shock or fire For wiring use the prescribed type of cables connect them securely making sure that there are no external forces...

Страница 3: ...one ground cable Improper grounding may cause electric shock Perform draining for the unit according to the Installation manual Check that the water is properly drained If the drain processing is impr...

Страница 4: ...this is to prevent TV reception interference or radio noise Even if they are installed more than 1 meter apart you could still receive noise under some signal conditions Keep the length of the piping...

Страница 5: ...ace as shown in the following example when an obstruction is present also in the upward area When the upward area is open Unit mm 1 Obstacles at rear only 300 2 Obstacles at front only 1500 or more 3...

Страница 6: ...s in the figure To reduce vibration do not install the unit directly on the ground Install it on a secure base such as concrete blocks The foundation shall support the legs of the unit and have a widt...

Страница 7: ...e model Model code of indoor unit Capacity kW 04 1 1 07 2 2 09 2 8 12 3 6 14 4 5 18 5 6 24 7 1 30 9 0 34 10 0 36 11 2 45 12 5 54 14 0 In the case of ARXD07GALH equivalent to model code of indoor unit...

Страница 8: ...Front connection Bottom connection Lateral connection Rear connection 5 2 Indoor unit pipe connections CAUTION For details refer to the Installation Instruction Sheet of each part Separation tube A B...

Страница 9: ...indoor unit and the outdoor unit cor rectly If the centering is improper the flare nut cannot be tightened smoothly If the flare nut is forced to turn the threads will be damaged Do not remove the fl...

Страница 10: ...to dust or water CAUTION The primary power supply capacity is for the air conditioner itself and does not include the concurrent use of other devices Do not use crossover power supply wiring for the...

Страница 11: ...rror Pay attention to the following points while attaching wires on the terminal board Do not attach 2 wires on one side Do not twist wires Do not cross the wires Do not shorted at edge at root PROHIB...

Страница 12: ...a screwdriver that is too small otherwise the screw heads may be damaged and prevent the screws from being properly tightened 5 Do not tighten the terminal screws too much otherwise the screws may bre...

Страница 13: ...onnected unit connected unit connected unit connected unit connected unit Input1 CN131 Yellow Input2 CN132 Green Input3 CN133 White Input4 CN134 Red Input5 CN135 Orange P C B Operation behavior Each i...

Страница 14: ...output signal for base heater Output signal ON when the outdoor tempera ture goes down below 2 C and signal OFF at the outdoor temperature 4 C 1 2 3 4 Voltage power supply input voltage cable 0 82mm2...

Страница 15: ...0 0 Factory setting 11 Cooling capacity shift Normal mode 1 1 0 0 Save energy mode 0 1 High power mode 1 0 2 High power mode 2 0 3 Forbidden 0 4 Set this item when necessary 12 Heating capacity shift...

Страница 16: ...ter pulse setting 2 Setting number 00xx 7 3 0 0 Setting number 01xx 0 1 Setting number 98xx 9 8 Setting number 99xx 9 9 Set the hundreds digit and thousands digit of the electricity meter pulse settin...

Страница 17: ...address setting Address must be set for the indoor unit Manual setting When setting with the switch inside the indoor unit refer to the indoor unit operating manual When setting with a remote control...

Страница 18: ...the pressure of nitrogen gas before blazing After completing the sealing test release the nitrogen gas from both valves Release the nitrogen gas slowly It may take about 10 minutes for completing the...

Страница 19: ...Set the cylinder vertical and fill with the liquid Liquid can be filled without turning bot tom up with the siphon inside Liquid Gas R410A Filling method for other cylinders Turn bottom up and fill wi...

Страница 20: ...ry indoor units 3 Are the cables connected to the terminals without loose ness and in accordance with the specifications 4 Are all the indoor units stopped Indoor unit connection check can not be perf...

Страница 21: ...d to test operation the unit If there are problems adjust immediately and recheck 9 3 Test run method Be sure to configure test run settings only when the outdoor unit has stopped operating Depending...

Страница 22: ...error E 7 4 1 Outside air temp thermistor error E 7 5 1 Outdoor unit suction gas temp thermistor error E 7 7 1 Outdoor unit heat sink temp thermistor error E 8 4 1 Outdoor unit current sensor 1 error...

Страница 23: ...ition is max cooling condition refer to item 16 9 Air circulation Air circulation 10 Noise level Noise level 11 Refrigerant Refrigerant type and initial charging amount 12 Max pressure HP LP Means pre...