En-3

2. 4.  Optional parts

CAUTION

The following parts are optional parts speci

fi

 c to R410A refrigerant.

Do not use parts other than those listed below.

2. 4. 1.  Separation tube kit

Separation tube uses the following parts.

Separation tube

Total cooling capacity of indoor unit (kw)

UTP-AX054A

ALL

2. 4. 2.  Header

Header uses the following parts. A header is used for connecting the indoor units.

Header

Total cooling capacity of 

indoor unit (kw)

3-6 Branches

3-8 Branches

UTR-H0906L

UTR-H0908L

ALL

2. 4. 3.  External connect kit

Model

Usage

UTY-XWZXZ6

For External input

(CN131, CN132, CN133, CN134)

For External output

(Error status / CN136)

(Operation status / CN137)

UTY-XWZXZF

For External input (CN135)

UTY-XWZXZ9

For External output

(Base heater / CN115)

3. INSTALLATION WORK

Please obtain the approval of the customer when selecting the location of installation 
and installing the main unit.

3. 1.  Selecting an installation location

WARNING

Install the unit in a location that can withstand its weight, and where it will not topple or 
fall.

•  Calculate the proper refrigerant concentration if you will be installing it in an 

enclosed location.

Total amount of replenished 
refrigerant in refrigerant facility (kg)  
Capacity of smallest room where unit is installed (m

3

Refrigerant 
concentration (kg/m

3

)

(0.3kg/m

3

)

•  If the results of the calculation exceed the concentration limit, increase the room surface 

area or install a ventilation duct.

CAUTION

Please install the outdoor unit without slant. (within 3 degrees)

Install this unit in a location with good ventilation.

If the unit must be installed in an area within easy reach of the general public, install 
as necessary a protective fence or the like to prevent their access.

Install the unit in an area that would not inconvenience your neighbors, as they could 
be affected by the air

fl

 ow coming out from the outlet, noise, or vibration.

If it must be installed in proximity to your neighbors, be sure to obtain their approval.

If the unit is installed in a cold region that is affected by snow accumulation, snow fall, 
or freezing, take appropriate measures to protect it from those elements. 
To ensure a stable operation, install inlet and outlet ducts.

Install the unit in an area that would not cause problems even if the drain water is 
discharged from the unit. Otherwise, provide drainage that would not affect people or 
objects.

Install the unit in an area that has no heat sources, vapors, or the risk of the leakage 
of 

fl

 ammable gas in the vicinity.

Install the unit in an area that is away from the exhaust or vent ports that discharge 
vapor, soot, dust, or debris.

Install the indoor unit, outdoor unit, power supply cable, transmission cable and 
remote control cable at least 1 meter away from a television or radio. 
The purpose of this is to prevent TV reception interference or radio noise. (Even if 
they are installed more than 1 meter apart, you could still receive noise under some 
signal conditions.)

Keep the length of the piping of the indoor and outdoor units within the allowable 
range.

For maintenance purposes, do not bury the piping.

3. 2.  Drain processing

CAUTION

Perform drain work in accordance with this Manual, and ensure that the drain water 
is properly drained. If the drain work is not carried out correctly, water may drip down 
from the unit, wetting the furniture.

When the outdoor temperature is 0 °C or less, do not use the accessory drain pipe 
and drain cap. If the drain pipe and drain cap are used, the drain water in the pipe 
may freeze in extremely cold weather.

• As 

the 

drain 

water 

fl

 ows out of the outdoor unit during heating operation, install the 

drain pipe and connect it to a commercial 16mm hose.

•  When installing the drain pipe, plug all the holes other than the drain pipe mounting 

hole in the bottom of the outdoor unit with putty so there is no water leakage. 

341

296

315

140

438

278

40

622

Drain cap mounting hole ×7

(Unit: mm)

Drain pipe mounting hole ×1

Base

Drain pipe

Drain pipe mounting hole

3. 3.  Installation dimensions

CAUTION

Provide suf

fi

 cient installation space, such as transportation route, maintenance space, 

ventilation space, refrigerant piping space, and passageways.

Pay attention to the speci

fi

 cations of the installation space as shown in the 

fi

 gure. If 

the unit is not installed according to speci

fi

 cations, it may cause short circuit or poor 

performance. The unit may be prone to lapse into non-operation due to high pressure 
protection.

When there is a wall in front of the unit, provide a space of 500mm or more as main-
tenance space.
When there is a wall at the right side of the unit, provide a space of 25mm or more as 
maintenance space.

An outdoor temperature of 35 °C (DB) in air-conditioned operation is assumed for 
the installation space in this item. If the outdoor temperature exceeds 35 °C (DB) and 
the outdoor unit is operating at a load exceeding its rated ability, provide a larger inlet 
space.

If you are installing more outdoor units than indicated here, please ensure suf

fi

 cient 

space or consult your distributing agent as it may affect the performance due to short 
circuit and other problems.

Consider the transportation route, installation space, maintenance space, and access, 
and install the unit in a location with suf

fi

 cient space for the refrigerant piping.

Observe the installation space speci

fi

 cations that are shown in the 

fi

 gures.

Keep the same space at rear air intake.
Provide the same space for the air intake at the rear of the outdoor unit.
If the installation is not performed according to the speci

fi

 cations, it could cause a 

short circuit and result in a lack of operating performance. As a result, the outdoor unit 
might easily be stopped by high-pressure protection.

Air intake

Rear view

227

305

321

50

76

526

690

9380545057_IM.indb   3

9380545057_IM.indb   3

2014/9/15   11:27:02

2014/9/15   11:27:02

Содержание AJY040LCLAH

Страница 1: ...AL For authorized service personnel only INSTALLATIONSANLEITUNG Nur f r autorisiertes Fachpersonal MANUEL D INSTALLATION MANUAL DE INSTALACI N Pour le personnel agr uniquement nicamente para personal...

Страница 2: ...y performed electrical work can cause serious accidents such as electric shock or fire For wiring use the prescribed type of cables connect them securely making sure that there are no external forces...

Страница 3: ...one ground cable Improper grounding may cause electric shock Perform draining for the unit according to the Installation manual Check that the water is properly drained If the drain processing is impr...

Страница 4: ...this is to prevent TV reception interference or radio noise Even if they are installed more than 1 meter apart you could still receive noise under some signal conditions Keep the length of the piping...

Страница 5: ...ace as shown in the following example when an obstruction is present also in the upward area When the upward area is open Unit mm 1 Obstacles at rear only 300 2 Obstacles at front only 1500 or more 3...

Страница 6: ...s in the figure To reduce vibration do not install the unit directly on the ground Install it on a secure base such as concrete blocks The foundation shall support the legs of the unit and have a widt...

Страница 7: ...e model Model code of indoor unit Capacity kW 04 1 1 07 2 2 09 2 8 12 3 6 14 4 5 18 5 6 24 7 1 30 9 0 34 10 0 36 11 2 45 12 5 54 14 0 In the case of ARXD07GALH equivalent to model code of indoor unit...

Страница 8: ...Front connection Bottom connection Lateral connection Rear connection 5 2 Indoor unit pipe connections CAUTION For details refer to the Installation Instruction Sheet of each part Separation tube A B...

Страница 9: ...indoor unit and the outdoor unit cor rectly If the centering is improper the flare nut cannot be tightened smoothly If the flare nut is forced to turn the threads will be damaged Do not remove the fl...

Страница 10: ...to dust or water CAUTION The primary power supply capacity is for the air conditioner itself and does not include the concurrent use of other devices Do not use crossover power supply wiring for the...

Страница 11: ...rror Pay attention to the following points while attaching wires on the terminal board Do not attach 2 wires on one side Do not twist wires Do not cross the wires Do not shorted at edge at root PROHIB...

Страница 12: ...a screwdriver that is too small otherwise the screw heads may be damaged and prevent the screws from being properly tightened 5 Do not tighten the terminal screws too much otherwise the screws may bre...

Страница 13: ...onnected unit connected unit connected unit connected unit connected unit Input1 CN131 Yellow Input2 CN132 Green Input3 CN133 White Input4 CN134 Red Input5 CN135 Orange P C B Operation behavior Each i...

Страница 14: ...output signal for base heater Output signal ON when the outdoor tempera ture goes down below 2 C and signal OFF at the outdoor temperature 4 C 1 2 3 4 Voltage power supply input voltage cable 0 82mm2...

Страница 15: ...0 0 Factory setting 11 Cooling capacity shift Normal mode 1 1 0 0 Save energy mode 0 1 High power mode 1 0 2 High power mode 2 0 3 Forbidden 0 4 Set this item when necessary 12 Heating capacity shift...

Страница 16: ...ter pulse setting 2 Setting number 00xx 7 3 0 0 Setting number 01xx 0 1 Setting number 98xx 9 8 Setting number 99xx 9 9 Set the hundreds digit and thousands digit of the electricity meter pulse settin...

Страница 17: ...address setting Address must be set for the indoor unit Manual setting When setting with the switch inside the indoor unit refer to the indoor unit operating manual When setting with a remote control...

Страница 18: ...the pressure of nitrogen gas before blazing After completing the sealing test release the nitrogen gas from both valves Release the nitrogen gas slowly It may take about 10 minutes for completing the...

Страница 19: ...Set the cylinder vertical and fill with the liquid Liquid can be filled without turning bot tom up with the siphon inside Liquid Gas R410A Filling method for other cylinders Turn bottom up and fill wi...

Страница 20: ...ry indoor units 3 Are the cables connected to the terminals without loose ness and in accordance with the specifications 4 Are all the indoor units stopped Indoor unit connection check can not be perf...

Страница 21: ...d to test operation the unit If there are problems adjust immediately and recheck 9 3 Test run method Be sure to configure test run settings only when the outdoor unit has stopped operating Depending...

Страница 22: ...error E 7 4 1 Outside air temp thermistor error E 7 5 1 Outdoor unit suction gas temp thermistor error E 7 7 1 Outdoor unit heat sink temp thermistor error E 8 4 1 Outdoor unit current sensor 1 error...

Страница 23: ...ition is max cooling condition refer to item 16 9 Air circulation Air circulation 10 Noise level Noise level 11 Refrigerant Refrigerant type and initial charging amount 12 Max pressure HP LP Means pre...

Отзывы: