 INSTALLATION – DAMPER BOX

Position the 2.5/2.5e damper enclosure on top of the joists so that the damper doors are aligned with 
the framed rough opening, being sure that there is easy access to the electrical box located on the 
side of the unit (

Figure 6

). 

The actuator end of the damper box has two “key holes” which are used to attach the damper box to 
the joists. Mark the location of the “key holes” on the joists by placing the damper box over the rough 
opening. Remove the damper box and fasten two of the provided wood screws so that the screw head 
is slightly above the joist. Position the damper box over the “key holes” and slide to lock into position. 
Use the remaining screws to attach the opposite side of the damper box.  

Use a good quality latex caulk to seal all wood-to-wood and wood-to-metal joints to create an airtight 
enclosure. This is important to ensure that all air drawn in by the fan will be from inside the house.

Attach the interior grille to the joists with the included wood screws.

FIGURE 6 – 2.5/2.5e WHF Damper Enclosure Installed

  INSTALLATION – DAMPER COLLAR

  Remove the two screws that hold the damper collar in place for shipping.

  Position elliptical collar over damper box opening.

  

Secure 2 screws (

Figure 7, step 1

).

  Stretch the collar until the 2 holes line up with the holes on the damper box body. Fasten with two 

   screws (

Figure 7, step 2.1

).

  Fasten all remaining screws, including the 2 original screws (

Figure 7, step 2.2

).

 

AirScape 2.5/2.5e WHF Installation Manual 02-11                                                                          Page 

7

Содержание 2.5

Страница 1: ...lation please verify that you received all the accessories with the whole house fan The packages should include BOX 1 of 3 damper door enclosure with grille IOM 8 metal and 4 wood screws 4 S hooks dua...

Страница 2: ...r 3 wire cable 20g or larger thermostat wire will work and electrical box for mounting wall switch Only if no other controller has been ordered with unit WHERE TO LOCATE Let s start with a little theo...

Страница 3: ...the total vent opening minus the loss caused by the interference of the screen louver or grille covering the vent The AirScape 2 5 2 5e requires a MINIMUM of 5 sq ft of net free venting area in your a...

Страница 4: ...much net free venting you have please consult a roofing professional Net free venting area can be acquired by any combination of gable eyebrow soffit or ridge vents or any other means that provide ven...

Страница 5: ...serted into the attic Please follow the instructions that apply to your install There is an existing attic access large enough for the 2 5 2 5e fan to fit through 16 O C Framing Step 1 Install two 14...

Страница 6: ...all cut out Approximately of each cross piece should be visible from below Figure 4 FIGURE 4 16 O C Framing 24 O C Framing Step 1 Cut a 23 x 14 opening in the dry wall use an existing joist as the 23...

Страница 7: ...sition Use the remaining screws to attach the opposite side of the damper box Use a good quality latex caulk to seal all wood to wood and wood to metal joints to create an airtight enclosure This is i...

Страница 8: ...the fan using the remaining sheet metal screws Figure 9 Finish by wrapping the joint with the provided tape to make the seam airtight The duct should be gently bent 90 degrees for maximum sound atten...

Страница 9: ...FIGURE 8 Hanging the Fan FIGURE 9 Duct to Damper and Duct to Fan Connections AirScape 2 5 2 5e WHF Installation Manual 02 11 Page 9...

Страница 10: ...the provided wall mounted double switch This 3 wire cable is NOT supplied with the unit but is widely available doorbell or thermostat cable is acceptable Step 2 Connect the control wiring with wire n...

Страница 11: ...FIGURE 11 Low Voltage Wall Switch Wiring FIGURE 12 Control Board Diagram AirScape 2 5 2 5e WHF Installation Manual 02 11 Page 11...

Страница 12: ...olt grounded outlet We do not recommend hardwiring the 2 5e fan power Verify that the 2 5 2 5e WHF power switch is OFF and turn on electrical power at circuit breaker Turn the unit ON in LOW speed The...

Страница 13: ...trol where the cooling effect is focused by which windows you open Visualize the path the air will take between the open windows and the unit Generally the longer the path the more overall cooling eff...

Страница 14: ...ing to the switch or remote Symptom Damper does not open Possible causes No power to damper actuator or damper shaft loose Suggestion Check power to unit and wiring The actuator actuator mounted termi...

Страница 15: ...w or reconditioned or a comparable version of the defective item AirScape warrants any replaced product or part for a period of ninety 90 days from shipment or through the end of the original warranty...

Страница 16: ...witch Decora style Supplied with unit Optional remote control available Remote and wall switch not supplied together Insulation R10 insulated damper doors Warranty 3 years 2 5 WHF Fan Energy Consumpti...

Отзывы: