  TROUBLESHOOTING

Before servicing the unit, switch power off at the electrical panel to reduce the risk of 
electrical shock, fire, or injury.

The 2.5/2.5e WHF has been factory tested. If you have problems with the unit please take a few 
minutes to run through the following troubleshooting procedures before calling for assistance.

Symptom: Unit does not start 

Possible causes: No power to unit. 

Suggestion 1: Check power to the unit and wiring at both the switch and the unit mounted junction box. 
Suggestion 2: Check the re-settable circuit breaker on damper enclosure electrical box. 
Suggestion 3: If power is verified at the unit, remove all control wiring from the low voltage control side. 
Jumper COM (RED) terminal to START (BLK) terminal.  Jumper testing must be done with power 
supplied to the unit. The unit will not operate if jumper wires are attached to unit prior to supplying 
power to the unit. The damper door should open and the fan should start.  When the jumper is 
removed the fan should stop and the damper should close.  If the start/stop sequence checks out then 
there is an issue with field wiring to the switch or remote.

Symptom: Damper does not open

Possible causes: No power to damper actuator or damper shaft loose.

Suggestion: Check power to unit and wiring.  The actuator (actuator mounted terminal block, not circuit 
board) should always have power to terminal 3, and terminal 2 when the fan is running (open damper). 
Terminal 1 should be the neutral.  Verify that the actuator jaws are closed tight on the damper shaft.

Symptom: Unit does not run on low speed

Possible causes: Wiring issue.

Suggestion: Verify wiring connections to the wall switch and the 120v wires from the control board to 
the fan. (shown in 

Figure 12

 on page 11).

Symptom: Unit does not run on high speed

Possible causes: Wiring issue.

Suggestion: Verify wiring connections to the wall switch and the 120v wires from the control board to 
the fan. (shown in 

Figure 12

 on page 11

).

Symptom: Damper door opens but fan does not start

Possible causes: Wiring issue between fan and damper enclosure.
Suggestion: Verify all wiring connections between fan and damper enclosure electrical box. 

If you continue to have issues with the unit, or have questions about the installation and wiring, please 
contact AirScape technical support by email at [email protected] or call 1-866-448-4187.

 

AirScape 2.5/2.5e WHF Installation Manual 02-11                                                                         Page 

14

Содержание 2.5

Страница 1: ...lation please verify that you received all the accessories with the whole house fan The packages should include BOX 1 of 3 damper door enclosure with grille IOM 8 metal and 4 wood screws 4 S hooks dua...

Страница 2: ...r 3 wire cable 20g or larger thermostat wire will work and electrical box for mounting wall switch Only if no other controller has been ordered with unit WHERE TO LOCATE Let s start with a little theo...

Страница 3: ...the total vent opening minus the loss caused by the interference of the screen louver or grille covering the vent The AirScape 2 5 2 5e requires a MINIMUM of 5 sq ft of net free venting area in your a...

Страница 4: ...much net free venting you have please consult a roofing professional Net free venting area can be acquired by any combination of gable eyebrow soffit or ridge vents or any other means that provide ven...

Страница 5: ...serted into the attic Please follow the instructions that apply to your install There is an existing attic access large enough for the 2 5 2 5e fan to fit through 16 O C Framing Step 1 Install two 14...

Страница 6: ...all cut out Approximately of each cross piece should be visible from below Figure 4 FIGURE 4 16 O C Framing 24 O C Framing Step 1 Cut a 23 x 14 opening in the dry wall use an existing joist as the 23...

Страница 7: ...sition Use the remaining screws to attach the opposite side of the damper box Use a good quality latex caulk to seal all wood to wood and wood to metal joints to create an airtight enclosure This is i...

Страница 8: ...the fan using the remaining sheet metal screws Figure 9 Finish by wrapping the joint with the provided tape to make the seam airtight The duct should be gently bent 90 degrees for maximum sound atten...

Страница 9: ...FIGURE 8 Hanging the Fan FIGURE 9 Duct to Damper and Duct to Fan Connections AirScape 2 5 2 5e WHF Installation Manual 02 11 Page 9...

Страница 10: ...the provided wall mounted double switch This 3 wire cable is NOT supplied with the unit but is widely available doorbell or thermostat cable is acceptable Step 2 Connect the control wiring with wire n...

Страница 11: ...FIGURE 11 Low Voltage Wall Switch Wiring FIGURE 12 Control Board Diagram AirScape 2 5 2 5e WHF Installation Manual 02 11 Page 11...

Страница 12: ...olt grounded outlet We do not recommend hardwiring the 2 5e fan power Verify that the 2 5 2 5e WHF power switch is OFF and turn on electrical power at circuit breaker Turn the unit ON in LOW speed The...

Страница 13: ...trol where the cooling effect is focused by which windows you open Visualize the path the air will take between the open windows and the unit Generally the longer the path the more overall cooling eff...

Страница 14: ...ing to the switch or remote Symptom Damper does not open Possible causes No power to damper actuator or damper shaft loose Suggestion Check power to unit and wiring The actuator actuator mounted termi...

Страница 15: ...w or reconditioned or a comparable version of the defective item AirScape warrants any replaced product or part for a period of ninety 90 days from shipment or through the end of the original warranty...

Страница 16: ...witch Decora style Supplied with unit Optional remote control available Remote and wall switch not supplied together Insulation R10 insulated damper doors Warranty 3 years 2 5 WHF Fan Energy Consumpti...

Отзывы: