AirScape 2.5 Скачать руководство пользователя страница 12

  START UP AND OPERATION

 Make sure that all wiring and connections have been made per this manual and acceptable wiring 

  standards and that all local codes and standards have been followed in the installation of this unit.

 Make sure that no tools or construction debris have been left in the 2.5/2.5e WHF. 

 Plug the damper unit power cord into a 120-volt grounded outlet. Alternatively, if you would like to 

  hardwire the unit, remove the power cord and provide 120-volt power to the unit through the circuit 
  breaker located on the unit mounted junction box.  A dedicated circuit is not required, however the 
  power requirements of 120 volts, 2.5 amps must be taken into account when allocating power 
  from existing circuits.

 The 2.5e WHF has a second power cord running from the fan that must also be plugged into a 

  120-volt grounded outlet. We do not recommend hardwiring the 2.5e fan power.

 Verify that the 2.5/2.5e WHF power switch is OFF and turn on electrical power at circuit breaker.

 Turn the unit ON in LOW speed. The damper doors will take a few seconds to open and   

       there will be a delay before the fan turns on. Once the fan starts running, switch the unit to HIGH.

 When the power is turned OFF, the fan will shut down and the damper door begin to close. 

  The door will shut tightly within 60 seconds.

 Allow for a slight delay when changing between speeds for the fan to adjust torque.

  SAFETY INFORMATION

  Not So Obvious - Please Read:

 Do not operate the 2.5/2.5e WHF without a window or door open. 

 This fan is meant for general ventilation.  It has 

NOT

 been designed to vent particle laden and/or

       explosive mixtures of air.

 Not for use in kitchens.

 Never force open the doors. Always use clutch releases located on Actuators before attempting to

  manually open or close damper doors.

 

AirScape 2.5/2.5e WHF Installation Manual 02-11                                                                         Page 

12

Содержание 2.5

Страница 1: ...lation please verify that you received all the accessories with the whole house fan The packages should include BOX 1 of 3 damper door enclosure with grille IOM 8 metal and 4 wood screws 4 S hooks dua...

Страница 2: ...r 3 wire cable 20g or larger thermostat wire will work and electrical box for mounting wall switch Only if no other controller has been ordered with unit WHERE TO LOCATE Let s start with a little theo...

Страница 3: ...the total vent opening minus the loss caused by the interference of the screen louver or grille covering the vent The AirScape 2 5 2 5e requires a MINIMUM of 5 sq ft of net free venting area in your a...

Страница 4: ...much net free venting you have please consult a roofing professional Net free venting area can be acquired by any combination of gable eyebrow soffit or ridge vents or any other means that provide ven...

Страница 5: ...serted into the attic Please follow the instructions that apply to your install There is an existing attic access large enough for the 2 5 2 5e fan to fit through 16 O C Framing Step 1 Install two 14...

Страница 6: ...all cut out Approximately of each cross piece should be visible from below Figure 4 FIGURE 4 16 O C Framing 24 O C Framing Step 1 Cut a 23 x 14 opening in the dry wall use an existing joist as the 23...

Страница 7: ...sition Use the remaining screws to attach the opposite side of the damper box Use a good quality latex caulk to seal all wood to wood and wood to metal joints to create an airtight enclosure This is i...

Страница 8: ...the fan using the remaining sheet metal screws Figure 9 Finish by wrapping the joint with the provided tape to make the seam airtight The duct should be gently bent 90 degrees for maximum sound atten...

Страница 9: ...FIGURE 8 Hanging the Fan FIGURE 9 Duct to Damper and Duct to Fan Connections AirScape 2 5 2 5e WHF Installation Manual 02 11 Page 9...

Страница 10: ...the provided wall mounted double switch This 3 wire cable is NOT supplied with the unit but is widely available doorbell or thermostat cable is acceptable Step 2 Connect the control wiring with wire n...

Страница 11: ...FIGURE 11 Low Voltage Wall Switch Wiring FIGURE 12 Control Board Diagram AirScape 2 5 2 5e WHF Installation Manual 02 11 Page 11...

Страница 12: ...olt grounded outlet We do not recommend hardwiring the 2 5e fan power Verify that the 2 5 2 5e WHF power switch is OFF and turn on electrical power at circuit breaker Turn the unit ON in LOW speed The...

Страница 13: ...trol where the cooling effect is focused by which windows you open Visualize the path the air will take between the open windows and the unit Generally the longer the path the more overall cooling eff...

Страница 14: ...ing to the switch or remote Symptom Damper does not open Possible causes No power to damper actuator or damper shaft loose Suggestion Check power to unit and wiring The actuator actuator mounted termi...

Страница 15: ...w or reconditioned or a comparable version of the defective item AirScape warrants any replaced product or part for a period of ninety 90 days from shipment or through the end of the original warranty...

Страница 16: ...witch Decora style Supplied with unit Optional remote control available Remote and wall switch not supplied together Insulation R10 insulated damper doors Warranty 3 years 2 5 WHF Fan Energy Consumpti...

Отзывы: