General Description
UNIT IDENTIFICATION
AIR COOLED CONDENSING UNIT
UCCU
U
ltima
C
ompact
C
ondensing
U
nit - Cooling Only
30 - 450
Model Size (Expressed as Nominal Cooling in kW)
SQ-
S
ingle Circuit -
Q
uiet (Models 30-80 (Except 75) Only)
SSQ-
S
ingle Circuit -
S
uper
Q
uiet (Models 30-80 (Except 75) Only)
D-
D
ouble Circuit - Standard
DQ-
D
ouble Circuit -
Q
uiet
DSQ-
D
ouble Circuit -
S
uper
Q
uiet
2-16
Number of Fans
/1 or /2
Single or Double Row of Fans
Example
UCCU250DQ-8/2
INTRODUCTION
The Airedale range of Ultima Compact air cooled condensing units covers the nominal
capacity range 30kW to 450kW in 24 model sizes. The range is available with many
optional variations including
Q
uiet and
S
uper
Q
uiet sound level variants.
The range is suitable for a wide range of split-system applications such as Cold Storage,
large Retail Comfort Cooling, Process Cooling, Healthcare, Hi-Tech environments
and leisure.
Attention has been placed on maximising the unit’s performance while keeping the sound
and vibration levels and footprint to an absolute minimum.
CE DIRECTIVE
Airedale certify that the equipment detailed in this manual conforms with the following
EC Directives:
Electromagnetic Compatibility Directive (EMC)
2014/30/EU
Low Voltage Directive (LVD)
2014/35/EU
Machinery Directive (MD)
89/392/EEC in the version 98/37/EC
Pressure Equipment Directive (PED)
97/23/EC
Article 13 of 2014/68/EU
To comply with these directives appropriate national & harmonised standards have been
applied. These are listed on the Declaration of Conformity, supplied with each product.
Maximum and Minimum Operation Temperature (TS) and Pressure (PS)
Operating Temperature (TS), TS = Min -20°C to Max 120°C *
Maximum Operating Pressure (PS) PS = High Side 26 Barg
*Based upon the maximum machine running temperatures.
REFRIGERANTS
The range has been designed and optimised for operation with the ozone benign
R407C refrigerant.
STANDARD FEATURES
All models sizes.
Construction
The base is fabricated from galvanised steel to ensure a tough, durable,
weatherproof construction.
The superstructure is manufactured from galvanised sheet steel coated with epoxy baked
powder paint to provide a durable and weatherproof finish. Standard unit colour is Light
Grey (RAL 7035).
Compressors and heat exchangers are mounted on a rigid galvanised heavy-duty sub
frame. Fully weatherproofed electrical panels are situated at one end of the unit. Access
to the compressors is via end panels adjacent to the electrical control panel.
Other features include:
Dedicated Compressor Enclosure
Condenser Fan Discharge Plenum