Condensing Units
ULTIMA COMPACT
Condensers & Condensing Units
23
Installation & Maintenance : 6259675 IM V1.9.0 04/2016
Chill
ers
ULT
IM
A CO
M
PACT
Installation Data
ELECTRICAL DATA
UCCU75D-2/1
UCCU100D-2/1
UCCU110D-4/2
UCCU125D-3/1
UCCU130D-4/2
UCCU150D-3/1
Unit Data
Nominal Run Amps
(1) A
54
68
75
89
95
109
Maximum Start Amps
(2) A
140
172
179
238
244
258
Permanent Supply
VAC
230 V 1 PH 50 Hz
Mains Supply
VAC
400 V 3 PH 50 Hz
Rec Permanent Fuse Size
A
16
16
16
16
16
16
Rec Mains Fuse Size
A
63
80
100
125
125
125
Max Permanent Incoming Cable Size
mm²
4 mm² terminals
Max Mains Incoming Cable Size
mm²
70 (Direct to
MCCB)
70 (Direct to
MCCB)
Direct to Bus Bar
70 (Direct to
MCCB)
Direct to Bus Bar
70 (Direct to
MCCB)
Control Circuit
VAC
24V/230V AC
Condenser Fan - Per Fan
Full Load Amps
A
1.75
1.75
3.00
1.75
3.00
1.75
Locked Rotor Amps
A
6.20
6.20
7.00
6.20
7.00
6.20
Motor Rating
kW
0.98
0.98
1.75
0.98
1.75
0.98
Compressor - Per Compressor
Quantity
4
4
4
2 + 2
2 + 2
4
Motor Rating
kW
6.2
8.1
8.1
8.1 / 11.7
8.1 / 11.7
11.7
Nominal Run Amps
(1) A
12.7
16.1
16.1
16.1/ 26.0
16.1 / 26.0
26.0
Crankcase Heater Rating
W
65.0
65.0
65.0
65.0 / 75.0
65.0 / 75.0
75.0
Start Amps
(2)
98.0
120.0
120.0
120.0 / 175.0
120.0 / 175.0
175.0
Type Of Start
Direct on line
QUIET DQ
UCCU75DQ-2/1
UCCU100DQ-2/1
UCCU110DQ-4/2
UCCU125DQ-3/1
UCCU130DQ-4/2
UCCU150DQ-4/1
All data as above except:
Condenser Fan - Per Fan
Full Load Amps
A
1.15
1.15
1.25
1.15
1.25
1.15
Locked Rotor Amps
A
2.10
2.10
4.50
2.10
4.50
2.10
Motor Rating
kW
0.68
0.68
0.69
0.68
0.69
0.68
SUPER QUIET DSQ
UCCU75DSQ-3/1
UCCU100DSQ-3/1
UCCU110DSQ-4/2
UCCU125DSQ-4/1
UCCU130DSQ-6/2
UCCU150DSQ-4/1
All data as above except:
Condenser Fan - Per Fan
Full Load Amps
A
0.83
0.83
0.78
0.83
0.78
0.83
Locked Rotor Amps
A
1.50
1.50
1.50
1.50
1.50
1.50
Motor Rating
kW
0.32
0.32
0.48
0.32
0.48
0.32
OPTIONAL EXTRAS
Power Factor Correction
Nominal Run Amps
(1) A
49
61
68
80
86
97
Maximum Start Amps
(2) A
140
172
179
238
244
258
Recommended Mains Fuse
A
63
80
100
125
125
125
Compressor Nominal Run Amps
- Per Compressor
A
4 x 11
4 x 13
4 x 13
2 x 20 / 2 x 13
2 x 20 / 2 x 13
4 x 20
Electronic Soft-start
Nominal Run Amps
(1) A
54
68
75
89
95
109
Maximum Start Amps
(2) A
100
124
131
168
174
188
Recommended Mains Fuse
A
63
80
100
125
125
125
(1)
Based at 7.2°C Evaporating and 54.4°C Condensing temperatures.
(2)
Starting amps refers to the direct on line connections.