Units
UCCL050SX-2AJ0
UCCL050DX-2ADD
UCCL060SX-2AK0
SEPR
1,3,5
6.28
6.09
6.12
SEPR Tier
2 (2021)
2 (2021)
2 (2021)
Annual Electricity Consumption
kWh/a
57089.0
59860.0
65059.0
Rated Refrigerant Capacity P
A
1,3,5
kW
48.4
49.2
53.7
Rated Power Input D
A
kW
17.3
17.1
20.4
Rated EER
DC,A
2.79
2.87
2.63
Declared Refrigerant Capacity P
B
1,3,5
kW
53.5 / 27.9
54.4 / 26.0
59.7 / 31.3
Declared Power Input D
B
kW
13.4 / 6.5
13.3 / 7.2
15.7 / 7.5
Declared EER
DC,B
3.98 / 4.27
4.10 / 3.61
3.80 / 4.18
Declared Refrigerant Capacity P
C
1,3,5
kW
58.2 / 30.1
59.1 / 28.6
65.2 / 33.8
Declared Power Input D
C
kW
10.1 / 5.2
10.0 / 5.5
11.7 / 5.9
Declared EER
DC,C
5.74 / 5.82
5.93 / 5.23
5.55 / 5.74
Declared Refrigerant Capacity P
D
1,3,5
kW
62.7 / 32.3
63.7 / 31.3
70.5 / 36.4
Declared Power Input D
D
kW
7.2 / 3.9
7.0 / 4.0
8.4 / 4.5
Declared EER
DC,D
8.70 / 8.27
9.04 / 7.88
8.35 / 8.12
SSCEE
2,3,5
%
152.9%
131.5%
154.8%
SSCEE Tier
Tier 1 (2018) NOT Compliant Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5
kW
48.5
n/a
53.9
Declared Cooling Capacity 35°C Pdc 2,3,5
kW
48.4
n/a
53.7
Declared EER
d
35°C
2.79
n/a
2.63
Declared Cooling Capacity 30°C Pdc 2,3,5
kW
53.8 / 27.4
n/a
59.7 / 30.7
Declared EER
d
30°C
3.45 / 3.70
n/a
3.32 / 3.69
Declared Cooling Capacity 25°C Pdc 2,3,5
kW
30.2 / 0.0
n/a
33.8 / 0.0
Declared EER
d
25°C
4.57 / 0.00
n/a
4.67 / 0.00
Declared Cooling Capacity 20°C Pdc 2,3,5
kW
33.2 / 0.0
n/a
37.2 / 0.0
Declared EER
d
20°C
5.78 / 0.00
n/a
6.03 / 0.00
Sound Power Level
dB(A)
77
n/a
76
Air Volume
m³/h
24225
n/a
24225
Off mode P
OFF
kW
0.035
n/a
0.035
Thermostat-off mode P
TO
kW
0.356
n/a
0.392
Standby Mode P
SB
kW
0.052
n/a
0.052
Crankcase heater mode P
CK
kW
0.064
n/a
0.064
Capacity Control
Staged
Staged
Staged
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21.
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2018.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2018.
(5) All performance data based upon standard waterside configuration.
(6) Please contact Airedale regarding Non Compliant selections.
Technical Data
Ecodesign
Te
ch
nic
al