Ultima Compact™
Chillers
33
Ultima Compact 30-150kW Technical Manual 9690553 V1.2.0_10_2019
Hydronics Data
Waterside Pressure Drops
Constant water flow MUST be maintained. Variable water volume is NOT recommended and may
invalidate warranty.
CAUTION
Use the formula below to calculate the External Head Available:
Total Pump Head Available - Chiller Pressure Drop = External Head Available
Example (UCCL 125DX-4AKK 8.0 l/s, standard single pump):
190 kPa - 75 kPa = 115 kPa
For glycol solutions, please refer to Glycol Data.
Pressure drops shown are for the standard unit without optional pumps and/or pipework.
Waterside Pressure Drops - Single Circuit
Evaporator Pressure Drop (kPa)
Waterflow (l/s)
UCCL30
UCCL40
UCCL50
UCCL60
UCCL75
UCCL85
UCCL100
UCCL125
0.00
50.00
100.00
150.00
200.00
250.00
0.0
2.0
4.0
6.0
8.0
10.0
12.0