Ultima Compact™
Chillers
53
Ultima Compact 30-150kW Technical Manual 9690553 V1.2.0_10_2019
Notes:
Units
UCCL075SR-2AM0
UCCL075SR-2AP0
UCCL075DR-2AGG
SEPR
1,3,5
5.53
5.13
5.16
SEPR Tier
2 (2021)
2 (2021)
2 (2021)
Annual Electricity Consumption
kWh/a
89629.0
119010.0
97873.0
Rated Refrigerant Capacity P
A
1,3,5
kW
66.9
82.3
68.2
Rated Power Input D
A
kW
28.5
40.0
28.0
Rated EER
DC,A
2.35
2.06
2.44
Declared Refrigerant Capacity P
B
1,3,5
kW
74.8 / 40.2
92.5 / 66.6
76.2 / 36.7
Declared Power Input D
B
kW
22.2 / 10.2
32.0 / 19.3
21.7 / 11.6
Declared EER
DC,B
3.36 / 3.95
2.89 / 3.45
3.51 / 3.16
Declared Refrigerant Capacity P
C
1,3,5
kW
82.0 / 43.3
72.4 / 38.4
83.4 / 40.7
Declared Power Input D
C
kW
16.9 / 8.1
15.3 / 7.2
16.4 / 8.9
Declared EER
DC,C
4.86 / 5.35
4.73 / 5.33
5.08 / 4.55
Declared Refrigerant Capacity P
D
1,3,5
kW
88.6 / 46.6
78.2 / 41.5
90.1 / 44.2
Declared Power Input D
D
kW
12.5 / 6.3
11.8 / 5.5
12.2 / 6.7
Declared EER
DC,D
7.09 / 7.34
6.64 / 7.48
7.41 / 6.57
SSCEE
2,3,5
%
144.5%
144.6%
118.4%
SSCEE Tier
NOT Compliant NOT Compliant NOT Compliant
Rated Cooling Capacity P
rated,c
2,4,5
kW
n/a
n/a
n/a
Declared Cooling Capacity 35°C Pdc 2,3,5
kW
n/a
n/a
n/a
Declared EER
d
35°C
n/a
n/a
n/a
Declared Cooling Capacity 30°C Pdc 2,3,5
kW
n/a
n/a
n/a
Declared EER
d
30°C
n/a
n/a
n/a
Declared Cooling Capacity 25°C Pdc 2,3,5
kW
n/a
n/a
n/a
Declared EER
d
25°C
n/a
n/a
n/a
Declared Cooling Capacity 20°C Pdc 2,3,5
kW
n/a
n/a
n/a
Declared EER
d
20°C
n/a
n/a
n/a
Sound Power Level
dB(A)
n/a
n/a
n/a
Air Volume
m³/h
n/a
n/a
n/a
Off mode P
OFF
kW
n/a
n/a
n/a
Thermostat-off mode P
TO
kW
n/a
n/a
n/a
Standby Mode P
SB
kW
n/a
n/a
n/a
Crankcase heater mode P
CK
kW
n/a
n/a
n/a
Capacity Control
Staged
Staged
Staged
Technical Data
Ecodesign
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21.
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2018.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2018.
(5) All performance data based upon standard waterside configuration.
(6) Please contact Airedale regarding Non Compliant selections.