'RZQÀRZ&KLOOHG:DWHU
Electrical Data
SC15D035 - SC15D060
SC15D035-C000-0
SC15D060-C000-0
Unit Data Full Function
Nominal Run Amps
(1)
A
37.2
50.5
Maximum Start Amps
A
37.2
50.5
Recommended Mains Fuse Size
A
50
80
Unit Data Cooling Only
Nominal Run Amps
(2)
A
6.8
12.6
Maximum Start Amps
A
6.8
12.6
Recommended Mains Fuse Size
A
10
16
Max Mains Incoming Cable Size
mm²
35
35
Mains Supply
V
400V / 3PH + N / 50HZ
Control Circuit
VAC
24
24
Evaporator Fan - Motor Per Fan
Motor Type
EC
EC
Quantity x Motor Size
(3)
kW
2 x 1.7
2 x 3.6
Full Load Amps
A
2.9
5.8
Locked Rotor Amps
A
2.9
5.8
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat
2
2
Number of Elements
6
6
Rating
kW
15
15
Curent per Phase
A
21.65
21.65
+XPLGL¿HU
Capacity
kg/hr
8
15
Rating
kW
6
11.25
Full Load Amps
A
8.7
16.2
First upgrade EC Motor - Per Fan
Quantity x Motor Size
(3)
kW
2 x 3.6
N/A
Full Load Amps
A
5.8
N/A
Locked Rotor Amps
A
5.8
N/A
Mechanical
(QWHULQJDLU&5+ZDWHU&&
)DQ*DLQ)DQSRZHULQSXWEDVHGXSRQIDQRSHUDWLQJZLWKGHVLJQDLUÀRZDW3D(63WKHVHYDOXHVPD\FKDQJHZLWKGLIIHUHQW(63
(3) Machine weight excludes a refrigerant charge For refrigerant charges, refer to Unit Refrigerant Charge (kg/circuit).
%DFNZDUGFXUYHG(&IDQRSWLRQVTXRWHHOHFWULFDOSRZHU$OORWKHURSWLRQVTXRWHVKDIWSRZHU
Electrical
9DOXHVJLYHQIRUIXQFWLRQXQLWVZLWKVWDQGDUGVHOHFWLRQVIRUKHDWLQJKXPLGL¿FDWLRQVXSSO\DLUIDQV
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables
Precision Air Conditioning
SmartCool™ 16 - 60
79
SmartCool Technical Manual 7525371 V1.2.0_03_2013
T
e
c
h
n
ic
a
l
C
0
0
0
D
F
Содержание R410A
Страница 1: ...6PDUW RRO RZQÀRZ 16 to 60kW R410A Technical Manual ...
Страница 85: ......