Installation
Liquid Sub Cooling
7KHGHJUHHRIOLTXLGVXEFRROLQJUHTXLUHGWRSUHYHQWÀDVKLQJRIOLTXLGUHIULJHUDQWFDQEHFDOFXODWHGE\WKHIROORZLQJ
method.
Given the following as an example:
Refrigerant R410A
Condensing temperature (54.4°C) equivalent
FRQGHQVLQJSUHVVXUHDW& %DU
Liquid lift 20m
Piping friction loss 0.21 bar
/RVVHVWKURXJKYDOYHVDQG¿WWLQJV%DU
Pressure Loss due to Liquid Lift
Note:- At normal liquid temperatures
the static pressure loss due to
elevation at the top of a liquid lift
0.115 bar/m.
Lift = H x spl
Where
H
= Height (m)
spl
= Static pressure loss
Lift = 20 x 0.115 = 2.3 bar
Total Pressure Loss in Liquid Line
TPL Liquid = Lift + PFL + Valves
Where
3)/
3LSHIULFWLRQORVV%DU
9DOYHV /RVVHVWKURXJK9DOYHVDQG¿WWLQJV
= 0.21 +0.5 + 2.3
7RWDOSUHVVXUHORVVLQOLTXLGOLQH %DU
Nett Pressure at Expansion Valve
= Condensing pressure - Total pressure loss in liquid line
Saturation temperature at the nett pressure
at expansion valve (30.99 bar) = 52°C
(from refrigerant tables)
Sub Cooling Required
= Condensing temperature - Saturation temperature
= 34 - 3.01 = 30.99 bar
Subcooling = Condensing temperature — Saturation temperature (Nett pressure at expansion valve)
= 54.4 - 52 = 2.4 °C
Therefore liquid sub cooling required to prevent liquid
ÀDVKLQJ &
Precision Air Conditioning
SmartCool™ 16 - 60
37
SmartCool Technical Manual 7525371 V1.2.0_03_2013