Commissioning Data
Refrigerant Charging
It is important that the system is charged with the correct amount of refrigerant. Remember, a seriously over or
undercharged system may lead to major component failure.
The final refrigerant charge level should be set by the design evaporating and condensing pressures, together with a full
or nearly full sight glass.
The suction and discharge pressures should be constantly monitored whilst charging is in progress.
To calculate the system refrigeration charge, please refer to the indoor unit data.
CR12
CR16
CR22
CR30
Refrigeration
Single Circuit
Refrigerant Type
R410A
Coil Volume
l
3.0
6.0
4.7
9.3
Refrigerant Charge
(1)
kg
1.4
2.7
2.2
4.3
CR50
CR65
CR80
CR105
Refrigeration
Single Circuit
Refrigerant Type
R410A
Coil Volume
l
10.7
21.4
18.3
36.6
Refrigerant Charge
(1)
kg
4.9
9.8
8.4
16.7
CR130
CR140
CR165
Refrigeration
Single Circuit
Refrigerant Type
R410A
Coil Volume
l
36.6
Refrigerant Charge
(1)
kg
16.7
(1)
For guidance only.
40
Condenser Technical Manual 6666879 V1.2.0_05_2013