CR12 - CR165 50/60Hz
CONDENSERS
Mean Condensing
Ambient
Temperature °C
25°C
30°C
35°C
40°C
45°C
48°C
Output kW
Output kW
Output kW
Output kW
Output kW
Output kW
CR12
35
8.8
3.3
-
-
-
-
40
13.8
8.8
3.4
-
-
-
45
19
14
8.9
3.6
-
-
50
24.4
19.2
14.1
9.1
3.8
-
55
29.8
24.7
19.5
14.4
9.3
4.1
CR16
35
11.9
5
-
-
-
-
40
18.2
12
5.2
-
-
-
45
24.7
18.4
12.1
5.4
-
-
50
31.3
25
18.6
12.3
5.6
-
55
38.2
31.8
25.4
19
12.6
6.5
CR22
35
15.4
6.2
-
-
-
-
40
24
15.5
6.4
-
-
-
45
32.8
24.2
15.7
6.7
-
-
50
41.7
33.1
24.6
16
7
-
55
51
42.3
33.7
25.1
16.4
7.7
CR30
35
19.8
8.1
-
-
-
-
40
30.6
20
8.4
-
-
-
45
41.7
30.9
20.2
8.7
-
-
50
53.1
42.1
31.3
20.5
9.2
-
55
64.8
53.8
42.8
31.9
21
9.8
CR50
35
33.7
13.7
-
-
-
-
40
52.6
34
14.2
-
-
-
45
71.7
53.1
34.4
14.8
-
-
50
91.3
72.5
53.8
35.1
15.5
-
55
111.5
92.6
73.7
54.8
35.9
16.9
Technical Data
Performance Data
(1)
Output kW refers to the condenser heat rejection.
Standard Variable Speed Head Pressure Control
Minimum Ambient Air DB °C
-20°C
Maximum Ambient Air DB °C
+48
Optional On/Off Head Pressure Control
Minimum Ambient Air DB °C
-0°C
Maximum Ambient Air DB °C
+48
Operating Limit
(1)
For conditions outside those quoted, please contact Airedale.
(2)
Low ambient kits are available for applications with temperatures below those quoted, please contact Airedale.