CR12 - CR165 50/60Hz
CONDENSERS
Commissioning Checklist
System Readings
Condensing temperature (as read on the discharge gauge) should be in the region of 40 to 41°C with an external
ambient temperature of 30°C (condensing is normally 10°C. above ambient) at full fan speed.
Running Checks
Once the system has been charged, the following running checks should be carried out:
Check the operation of the fan speed controller by observing an increase in fan speed if the outdoor coil is temporarily
partially blocked.
37
Condenser Technical Manual 6666879 V1.2.0_05_2013