High Inlet Temperature Refrigerated Air Dryer
7
Refrigeration Circuit
Refrigerant is cycled through a closed loop
system commonly known as high pressure and
low pressure. Refrigerant is compressed by the
compressor to a gas with high temperature and
high pressure, which then travels to the condenser
(air/water cooled) to drop the temperature and
change from gas to liquid. Liquid travels through
to the evaporator (refrigerant-to-air part of the heat
exchanger) and back to the compressor suction side
and the process repeats itself. A thermal expansion
hot gas by-pass valve is used on the non-cycling
dryers from the high side to low side as a freeze
protector in low load conditions (125 scfm).
Compressed Air Circuit
The compressed air dryer circuit uses a patented
air-to-air heat exchanger, which acts as a precooler/
reheater (40 scfm rated model and higher). Hot,
saturated, compressed air first enters the air-to-air
heat exchanger, where it is pre-cooled by outgoing
air from the air-to-refrigerant heat exchanger.
This energy saving heat exchanger provides
several advantages, such as a reduction of the heat
load imposed on the refrigerant compressor and
condenser, providing more energy to the outlet air,
and preventing condensation of moisture on the
outside of the plant distribution air line piping.
From the air-to-air heat exchanger, air will enter
into the evaporator further reducing its temperature
to a desired pressure dew point. As the air is
cooled, moisture will be condensed, where it is then
separated and discharged through the condensate
drain. The cooled air then reenters the air-to-air
heat exchanger, in a direction opposite to the flow
of the warm, saturated incoming air. This counter
flow action assures high temperature differential
throughout the heat exchanger, resulting in a more
effective heat transfer.
compressor
liquid
receiver
air out
air in
refrigerant
inlet
refrigerant
outlet
air cooled
condensor
suction
accumulator
Air to Refrigerant Heat Exchanger
Refrigerant Circuit
Typical Schematic Flow Diagram (20 scfm rated models)
Содержание DHT-100
Страница 12: ...12 Typical Installation Aircel DHT Series Models 20 125 Typical Installation...
Страница 30: ...30 Wiring Diagram SCFM Rated 20 to 50 Models 1 Phase 120 Volt 60 Hz Aircel DHT Series Models 20 125...
Страница 32: ...32 Wiring Diagram SCFM Rated 125 Model 1 Phase 208 230 Volt 60 Hz Aircel DHT Series Models 20 125...
Страница 33: ...33 Service Notes Date Service Performed Notes High Inlet Temperature Refrigerated Air Dryer...
Страница 34: ...34 Service Notes continued Date Service Performed Notes Aircel DHT Series Models 20 125...
Страница 35: ...Service Notes continued Date Service Performed Notes 35 High Inlet Temperature Refrigerated Air Dryer...