IOM-PreciseAIR
Page
36
of
50
3.8.6.
Alarm History
Displays the log of the last 100 alarms.
Each alarm has the following information:
•
Date and time
•
Sequential number (001 in this case)
•
Short description for alarm
•
Values for 9 variables at the time when the
alarm occurred (to help with
troubleshooting):
•
R_T:
room temperature
•
R_RH: room relative humidity
•
E_In:
evaporator air entering
temperature
•
E_out: evaporator air leaving
temperature
•
H_out: heater air leaving temperature
•
C1_LP: compressor 1 low pressure
(suction)
•
C1_HP: compressor 1 high pressure
(discharge)
•
C2_LP: compressor 2 low pressure
(suction)
•
C2_HP: compressor 2 high pressure
(discharge)
Try to clear the alarm in the screen. If the alarm
is not cleared out repeat the process. Sometimes
multiple presses are necessary.