IOM-PreciseAIR
Page
12
of
50
•
Pipe strainer
o
Mesh no larger than 0.9 mm recommended for cooling coils/evaporators.
o
0.5 to 1.5 mm mesh recommended for condensers.
•
Water pressure gauge with shutoff valves.
•
Water temperature gauge.
•
Low point drain.
•
Relief valve (required if water pressure may exceed 125 psig at any time, including upset
conditions. Customer to review shut off pressure of system pumps).
•
Flexible hose connection to unit.
Leaving Water Piping
•
Isolation valve (located downstream from all components listed below).
•
Water pressure gauge with shutoff valves.
•
Water temperature gauge.
•
High point vent.
•
Flexible hose connection to unit.
•
Balancing Valve.
CAUTION
Use Piping Strainers!
To prevent condenser damage, pipe strainers must be installed in the water supplies
to protect components from water borne debris. AIR is not responsible for equipment
damage caused by water borne debris. 0.5 to 1.5 mm mesh recommended.
Proper Water Treatment!
The use of untreated or improperly treated water may result in inefficient operation and tube
damage due to scaling, erosion, corrosion, algae or slime. It is recommended that the services of
a qualified water treatment specialist be engaged to determine what water treatment is required.
AIR assumes no responsibility for equipment failures which result from untreated or
improperly treated water, or saline or brackish water.
Condenser or Water Coil Damage!
To prevent damage to water components, do not allow pressure
(maximum working pressure) to exceed 125 psig @ 150°F.