IOM-PreciseAIR
Page
39
of
50
3
Symptom 3
High Refrigerant Discharge Pressure
3.1
Dirty tube and fin surface (air cooled
condenser)
Clean with compressed air or water spray, Use fin comb
if fins bent.
3.2
Condenser problems
Check if the condenser is clogged.
Remove and clean if necessary.
3.3
Condenser water flow/pressure/temperature
Have mechanical personnel verify water flow to the
condenser.
Excessive piping pressure drop will cause low flow.
Check all pipe valves. Make sure they are open.
Verify if water temperature is well above design
(typically 90F).
3.4
Water regulating valve
Verify if the water regulating valve is operational.
Check connections with refrigerant high pressure side.
3.5
System overcharged with refrigerant
Remove excess refrigerant.
3.6
Non-condensable in system (air in system)
Have a refrigeration service technician evacuate the
system and recharge it.
3.7
Blower belts
Blower belts may be loose, requiring adjustment.
(if applicable).
3.8
High pressure control
Verify the High Pressure Control. It requires a manual
reset.
4
Symptom 4
Low Suction Pressure
4.1
Lack of refrigerant
Check for adequate refrigerant charge (bubbles or
misty sight glass indicates low charge). If charge is low,
have the system checked for leaks and recharged by a
refrigeration service technician.
4.2
Evaporator dirty
Clean chemically.
4.3
Clogged liquid line filter-drier
Replace cartridge(s).
4.4
Improperly Set Low Pressure parameters
Have refrigeration service technician reset control or
Pressure Control replace if defective.
4.5
Expansion valve malfunctioning
Check and reset for proper superheat. Replace if
necessary. Check the thermal bulb and capillary tube
for damage.
4.6
Condensing temperature too low
Check the condensing temperature regulation system.
4.7
Insufficient chilled water or air flow
Adjust flow rate across evaporator.
4.8
Process air temp.
Check entering air/water temperature. Verify the
system conditions and find out if the air/water is too
cold based on design conditions.
4.9
Flooding control valves
Have a refrigeration service technician check flooding
control valves for proper operation. Adjust valves or
replace if defective.
5
Symptom 5
Low Oil Pressure/Level
5.1
Low-oil level/pressure sensor defective
Replace sensor.
5.2
Flooding of refrigerant into crankcase
Adjust thermal expansion valve.
5.3
Crankcase heater failed
Have the electrician check fuses for power to the
crankcase heater.
5.4
Short cycling
Pumps oil out of the compressor and the unit does not
run long enough for the oil to return. Check for short
cycling.
Содержание PreciseAIR PCA Series
Страница 15: ...IOM PreciseAIR Page 15 of 50 2 13 Main Control Panel Layout and Components Figure 4 Main Control Panel Layout...
Страница 27: ...IOM PreciseAIR Page 27 of 50 3 6 Setpoint Screens...
Страница 28: ...IOM PreciseAIR Page 28 of 50...
Страница 49: ...IOM PreciseAIR Page 49 of 50 4 11 Maintenance Logs...