T E C H N I C A L S P E C I F I C A T I O N S
2 8
Impulse voltage
•
Network connections 12 kV
•
Low voltage lines 6 kV
Burst
•
IEC 61000-4-4
level 3, 2 kV with base current
level 4, 4 kV with no load
Static electricity
•
IEC 61000-4-2 level 4,
8 kV contact discharge, 15 kV air discharge
RF interference
•
IEC 61000-4-3 level 3, 10 V/m
Vibration test
•
IEC 60068-2-6, 9.8 m/s
2
(1 g)
Current
•
Continuous 15 A
•
Short duration 300 A, 1 second
Storage temperature
•
-40
°
C to +80
°
C
Table 8. The Option Module characteristics
Option Module E7O1
Communication
•
Serial port RS232
•
EN61107 and SCTM™ compatible
Option Module E7O2
Communication
•
Serial port RS485
•
EN61107 and SCTM™ compatible
Option Module E7O3
Outputs
•
Five (5) S0-outputs, according to DIN 43864
•
18...27 V, 10 ... 27 mA
•
Maximum pulse frequency 17 Hz
Inputs
•
Two (2) S0 inputs according to DIN 43864
•
Maximum pulse frequency 17 Hz
Option Module E7O4
Version E7O4.1
Outputs
•
Six (6) semiconductor relay outputs
•
Max 230 Vac/Vdc (all relays must have the same supply voltage!)
•
120 mA
•
Maximum pulse frequency 17 Hz
Inputs
•
One (1) S0 input in accordance with DIN 43864, maximum pulse frequency 17 Hz
•
Eight (8) high voltage inputs (230V)
Communication
•
Serial port RS232 and RS485
•
EN61107 and SCTM™ compatible
Version E7O4.2
•
Same as E7O4.1, except with 100/110 Vac lines
©
Enermet Oy
E700
Manual for Installation and Use v. 6.31
ACTIVE INFORMATION MANAGEMENT