6.
INSTALLATION
RS232
DATA
LEAD
Cut
the
socket
(female)
connector
off
one
end
of
the
Serial
Data
lead
provided
in
the
kit.
Strip
‐
back
the
insulation
and
connect
3
wires
to
the
Touchsafe
Pro
panel
PAGER
terminals
using
the
colour
code
in
the
table
below.
It
is
important
that
the
RTS
and
CTS
wires
are
joined
together.
Note:
the
data
lead
can
be
extended
up
to
a
maximum
of
20
metres
using
LSF
(Low
Smoke
and
Fume)
screened
TCCA
8
core
alarm
cable.
This
cable
is
available
from
Aidcall
by
the
metre;
Part
No.
YW1730.
Plug
the
lead
into
the
RS232
INTERFACE
socket
on
the
rear
of
the
Maxpage
Terminal.
CONNECTION
DETAILS
It
is
possible
wire
colours
may
change
without
notice
‐
it
is
good
practice
to
check
continuity
of
each
wire
colour
to
the
relevant
9
Pin
“D”
Pin
No.
with
a
digital
meter
before
terminating.
Maximum
20m cable
length
between
Panel
and
Maxpage
Terminal
Cut
Socket
off
Lead
Plug
into
Maxpage
Terminal
1.8m
Lead
RS232
Interface
Connection
Pin
No.
Colour
Terminal
Connect
To…
1
Red
DCD
2
Orange
TXD
Touchsafe
Pro
Pager
Port
RX
3
Green
RXD
Touchsafe
Pro
Pager
Port
TX
4
Yellow
DTR
5
Black
0V
Touchsafe
Pro
Pager
Port
0V
6
Violet
DSR
7
White
RTS
IMPORTANT:
Link
RTS
to
CTS
by
joining
white
&
grey
wires
8
Grey
CTS
9
Blue
RI
Body
Brown
Screen
IMPORTANT
Loop
the
Cable
once
through
the
Ferrite
Sleeve
provided
with
the
Panel
Touchsafe
Pro
Panel
Pager
Port
Plug
into
Maxpage
Terminal
Socket
Not
Used
5
1
6
9